roofy

50-40 Jacobus Street

Queens, NY 11373BBL 4-02450-0017Map

Owner of record: NYC Department Of Education

50-40 Jacobus Street is a school building built in 1994 in Queens, 11373. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
65
ECB violations
63
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 65

  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 in 2020

    Jun 20, 2021

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 5, 2018

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
Show 40 more ↓
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Residential elevator periodic inspection/test elevatorrequired

    Failure to perform category 5 inspection

    Jun 1, 2016

    Dob violation - dismissed
  • Residential elevator periodic inspection/test elevatorrequired

    Failure to perform category 5 inspection

    Jun 1, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 4, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 4, 2015

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    Nyc department of education

    May 28, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    Nyc department of education

    May 28, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    Nyc department of education

    May 28, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 26, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 26, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 26, 2013

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2011 inspection/test

    Oct 1, 2012

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 20, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 20, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 20, 2012

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2010 inspection/test

    Dec 13, 2011

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 28, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 28, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 28, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 24, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 24, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 24, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 28, 2009

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 28, 2009

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 28, 2009

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 16, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 16, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 16, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 18, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 14, 2007

    Dob violation - resolved

ECB violations · 63

  • Class - 2

    Reissue #35720039k date of issue: 05/22/2025. failure to maintain building in code-compliant manner. at the time of inspection observed and noted at cellar level electrical room(meter) water penetration from un

    Apr 13, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue #35720038z date of issue: 05/22/2025. failure to maintain building in code-compliant manner. at the time of inspection observed and noted at cellar level electric meter room wall from right has running

    Apr 13, 2026 · Penalty $3,125

    Active
  • Class - 2

    Exit door not self-closing properly at the time of inspection at 4th fl stairway b one exit door. at 3rd floor near rm 325 one exit door and1st floor exit-3 one exit door not self-closing properly at the time o

    Apr 13, 2026 · Penalty $625

    Active
  • Class - 2

    Reissue #35677532m. failure to maintain building in code-compliant manner. at cellar level electric meter room, running step crack in cmu block wall, by secondary door. remedy: repair and/or replace.

    May 22, 2025 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. at cellar electrical meter room, water penetrating from under equipment floor slab. heavy stains and rusted electrical equipment. remedy: repair and/or rep

    May 22, 2025 · Penalty $1,250

    Active
  • Class - 2

    Reissue 35672789x. failure to maintain building in code-compliant manner. cellar level electric meter room walls on right step cracks on black wall. remedy: repair and/or replace.

    May 31, 2024 · Penalty $1,562

    Active
  • Class - 2

    Reissued #35655064y failure to maintain building in code-compliant manner. noted: at cellar level electric meter room the wall from right has running step cracks on the block wall. remedy: repair & replace

    Jun 13, 2023 · Penalty $1,562

    Active
  • Class - 2

    Re-issue:#35557857p-failure to maintain bldg in code-compliant manner:electrical at right door has a step crack in cmu. remedy:comply w/code

    May 13, 2022 · Penalty $3,125

    Active
  • Class - 2

    Missing ladder & platform boiler over 8' high ,missing valve on oil suction line b/4 anti syphon valve

    Jun 15, 2021 · Penalty $625

    Active
  • Class - 2

    Missing ladder & platform boiler over 8' high

    Jun 15, 2021 · Penalty $625

    Active
Show 40 more ↓
  • Class - 2

    Exit door not self closing noted at the 3rd floor (smoke) by 302, exit door smoe by exit 5 and the smoke by teh main entrance to the building teh eixt doors arenot working properly repair/replace door

    May 24, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner noted at the cellar level electrical meter room the wall on the right has running step cracks on the cmu block wall repir and or replace

    May 24, 2021 · Penalty $625

    Active
  • Class - 2

    Exit door ot self closing, at first floor main entrance at stair"a" inside one door is not self closing, at 2nd floor stair "c1" left side one door is not self closing properly at the time of inspection when

    May 7, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. use or prohibited door/and or hardware per bc 1008.1.8 27-371. at floors 1,2,3 cross over corridor doors have locking device (dead bolt) which requires a k

    May 9, 2018

    Resolve
  • Class - 2

    Faiilure to maintain bldg in code-compliant manner:metal flashing detached from wall at c-mod roof and multiple areas of roof.rem:repair and/or replace.

    Jul 25, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner.no firestopper per bc 712.3;27-345.in all electrical rms on each fl,there are wall penetrations w/no fire stopping.each fl has 4 electrical rms.rem:provide/main

    Jul 25, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner.noted:@ 4th fl stairway landing roof leak & same door leading to the roof there is approx 12"hole around the drain causing tripping hazard.rem:repair &/or repla

    Sep 15, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner.noted:at 4th floor lstairway landing water penetration observed indicating roof leak.rem:repair and/or replace.

    Sep 15, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner.noted:at 4th floor stairway landing door leading to the roof,there is approx.12"hole around the drain causing tripping hazard.rem:repair and/or replace.

    Sep 15, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner per bc 1016.2,27-369noted:combustible material in corridor @ cellar level.storage of chairs,tables,paper boxes @ both sides of corridor.rem:provide proper corri

    Sep 15, 2015

    Resolve
  • Class - 2

    Re-issue # 34949681r. altered/changed building occupied without a valid certificate of occupancy. expired temporary c of o alt 1 job # 401334855y023 expired 8/31/2011. remedy: obtain a valid c of o or discontin

    Feb 26, 2014

    Resolve
  • Class - 3

    Failure to maintain building in code-compliant manner. door racked or not operating/closing correctly. doors at rm a307,d-mod,stair a next to rm 213 & various other doors throughout building. remedy: repair

    Feb 26, 2014

    Resolve
  • Class - 2

    Combustible materials in corridor. at cellar level storage of gas operated equipment,stoves,maintenance equipment,chairs,tables,paper & various other combustibles at both sides of corridor. remedy: remove from

    Feb 26, 2014

    Resolve
  • Class - 2

    Expired temp certificate of occupancy. alt 1 job #401334855t023 expired 8/31/2011. remedy: obtain a valid c/o or discontinue illegal use.

    Apr 10, 2012

    Resolve
  • Class - 2

    Reissue:34854641k.exterior leading to the gas meter room is covered by a stair grating @ the top of the staircase.rem:obtain approvals and permits

    Mar 22, 2011

    Resolve
  • Class - 2

    Reissue:34854643y.interior ceiling plaster is spalling located @ stair c bulkhead.rem:repair &/or replace plaster

    Mar 22, 2011

    Resolve
  • Class - 2

    Reissue:34854645h exterior concrete coping stone is spalling on the inside of parapet wall @ roof level.rem:repair &/or replace concrete coping stone

    Mar 22, 2011

    Resolve
  • Class - 2

    Failure to maintain bldg.. reissue nov #34761427r. exterior staircase leading to gas meter room steel grating weld at top sealing staircase rem: obtain approvals and permits.

    May 6, 2010

    Resolve
  • Class - 2

    Failure to maintain bldg. exterior, noted: roof level coping stone on inside part of parapet is spalding where it meets 1st row of bricks. this may be causing a leak into room403 of d-mod. rem: maintain buildin

    May 6, 2010

    Resolve
  • Class - 2

    Sec 27-361: failure to maintain egress clear and unobstructed. noted: main entrance @ jacobus st. security desk blocks egress to one exit door, from auditorium center exit into room a325 after exit corridor blo

    May 6, 2010

    Resolve
  • Class - 2

    Failure to maintain building interior. stair c-1 bulkhead ceiling spalding plaster because of water penetration. rem: maintain bldg, fix leak, repair ceiling.

    May 6, 2010

    Resolve
  • Class - 2

    Failure to maintain bldg exterior. reissue #34760740z, water penetration through foundation wall in boiler room and electric room. rem: maintain bldg. waterproof foundation walls.

    May 6, 2010

    Resolve
  • Class - 2

    Reissue: 34711869r. missing corridor doors 2nd fl near room 225 & nextto gym (307), 3rd fl. remedy: install door.

    Feb 11, 2009

    Resolve
  • Class - 2

    Re 34711807n. water penetration through foundation wall into electrical panel room. remedy: seal foundation wall.

    Feb 11, 2009

    Resolve
  • Class - 2

    Re 34711808p. failure to maintain existing staircase to gas meter roomby putting metal grating over staircase. remedy: obtain all necessary permits for changes.

    Feb 11, 2009

    Resolve
  • Class - 2

    Corridor smoke door are missing located on the 2nd flr adjacent to room 225. remedy: replace missing corridor smoke door.

    Oct 17, 2008

    Resolve
  • Class - 2

    Reissue: 34592423p roof has become porous and allowing rain water into the building causing interior damages located at staircase c1 at the 4th flr. remedy: water proof exterior roof.

    Oct 17, 2008

    Resolve
  • Class - 2

    Reissue: 34592421l foundation wall has become porous and allowing rain into the building located at electrical/boiler room at cellar level. remedy: water-proof foundation wall.

    Oct 17, 2008

    Resolve
  • Class - 2

    Reissue: 34592422n exterior stairs leading to the gas meter room is covered with a metal grill at cellar level. remedy: remove metal grill or obtain permit.

    Oct 17, 2008

    Resolve
  • Hazardous

    Reissue:34400803h exterior foundation wall has become porous & allowing rain water in the bldg causing interior damages located in the boiler room & oil tank on cellar level.remedy:water-proof exterior foundati

    Aug 15, 2007

    Resolve
  • Hazardous

    Reissue:34400804j exterior stairs leading to the gas meter room ao19ato cellar level is covered by a metal gate & locked leading to the public st on the north side.remedy:remove metal gate or obtain a permit.

    Aug 15, 2007

    Resolve
  • Hazardous

    Interior classroom door is missing the glass panel w/the wire mesh inside the door located at room b305 on the 3rd level.remedy:replace missing glass wire panel.

    Aug 15, 2007

    Resolve
  • Hazardous

    Auditorium door is missing door handle on the 3rd level.across from room a328.remedy:replace door handle at door.

    Aug 15, 2007

    Resolve
  • Non-hazardous

    Roof leak in ceiling at 4th floor stair c1. remedy: repair roof. make all necessary repairs.

    May 17, 2006

    Resolve
  • Hazardous

    Reissue: #34474970r. northside exterior stair down to cellar gas meterroom a019a is completely covered stair w/bolted down section of gratingrating. remedy: obtain permit or remove grating.

    May 17, 2006

    Resolve
  • Non-hazardous

    Reissue: #34474965m cellar ground water penetrating into boiler, oil tank & electrical equipment rooms through floor & wall. corridor floor behind boiler room has ground water. remedy: stop all ground water.

    May 17, 2006

    Resolve
  • Non-hazardous

    86-bb-05

    Nov 15, 2005

    Resolve
  • Non-hazardous

    86-bb-05

    Nov 15, 2005

    Resolve
  • Non-hazardous

    Noted:north side exterior stair down to cellar gas meter room a019a iscompletely covered stair with bolted down gratings.remedy:remove gratings or provide access immediately.obtain a permit or restore prior leg

    Apr 29, 2005

    Resolve
  • Non-hazardous

    Failure to maintain building.defect noted:kneeland street side perimeter fence gate to dumpsters is bent and not usable.remedy:replace gate.

    Apr 29, 2005

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1994
Floors
4
Residential units
—
Building area
183,506 ft²
Lot area
98,790 ft²
Zoning
M1-1
Community board
404
Council district
30
Block / lot
2450 / 17
Assessed value
$25,467,300
Landmark / historic district
No

Questions about 50-40 Jacobus Street

Who owns 50-40 Jacobus Street?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 50-40 Jacobus Street have violations?

NYC HPD has no housing violations on record for this property.

Is 50-40 Jacobus Street rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 50-40 Jacobus Street built?

City records list 1994 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.