76-05 51 Avenue

Queens, NY 11373BBL 4-02451-0021Map

Owner of record: Twin Music INC

76-05 51 Avenue is a school building built in 1930 in Queens, 11373. The owner of record is Twin Music INC. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
0
ECB violations
48
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 0

No DOB violations on record

ECB violations · 48

  • Class - 2

    Reissued ecb#35720092j failure to maintain building in code-compliant manner.noted:storage in electrical switch gear room including gas meter room with miscellaneous items with janitorial equipment,suppliers d

    Apr 13, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue ecb#35720091h failure to maintain building in code-compliant manner.noted:fire rated smoke classroom doors not self-closing due to binding missing or faulty hardware on smoke door at cafeteria main entr

    Apr 13, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue on ecb#35720090k failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:emergency illumination discharges and exit s

    Apr 13, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue on ecb#35720089z failure to maintain building in code-compliant manner.noted:roof leaks in room 119 from water coming in from roof hvac unit duct work not from faulty roofing materials observed upon ins

    Apr 13, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:public assembly sign missing in cafeteria with a large open space with clearly over 75 chairs available for students at one given time observed upon i

    Apr 13, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.use of prohibited door and/or hardware per bc 1008.1.8;27-371(j).noted:installation ofkick stops on fire rated classrooms,smoke doors and emergency exit ext

    Apr 13, 2026 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted at 1 floor 103, cafeteria by c103 and 108, m113, p116 and smoke by exit 2 doorsnot closing properly. remedy: repair and/or replace.

    May 22, 2025 · Penalty $1,250

    Active
  • Class - 2

    Reissue #35672791p. failure to maintain building in code-compliant manner. note a electrical room door is out of alignment not closing. alsostorage of machines, filing cabinent and boxes. remedy: repair and/or

    May 22, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue #35677527z. failure to maintain building in code-compliant manner. noted at roof level leaking water penetration at rooms s119, cafeteria, 101 and room by exit 2. remedy: repair and/or replace roof.

    May 22, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue #35677525p. failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted at 1 floor 30 emergency and exit lights are i

    May 22, 2025 · Penalty $3,125

    Active
Show 38 more ↓
  • Class - 2

    Reissue 35672792r. failure to maintain building in code-compliant manner: illumination for exit, exit discharges and public corridors per bc1006.1; 27-381. emergency lights/exit signs 30 units not working when

    Jun 6, 2024 · Penalty $1,562

    Active
  • Class - 2

    Reissue 35672791p. failure to maintain building in code-compliant manner. main door to main electrical room broken and does not close. room is a rated rooms. remedy: repair and/or replace.

    Jun 6, 2024 · Penalty $1,562

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. water leak coming into building from roof units leak in room m113, s119, 100 cafeteria. remedy: repair and/or replace.

    Jun 6, 2024 · Penalty $625

    Active
  • Class - 2

    Re-issue #35655065x failure to maintain building in code-compliant manner. noted: electric meter room door doesn't close properly at time of inspection. remedy: repair and/or replace.

    Jun 16, 2023 · Penalty $1,562

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner illuminate for exit, exit discharges and public corridors per bc 1006.1;27-381. noted: at 1st floor more than (2) emergency lights are not working at time o

    Jun 16, 2023 · Penalty $625

    Active
  • Class - 2

    Re-issue:#35557859z-failure to maintain bldg. in code-compliant mannerat main electrical room the door doesn't close properly. remedy:repair &/or replace

    May 13, 2022 · Penalty $1,562

    Active
  • Class - 2

    Failure to maintain bldg in code compliant manner.noted:rm sign have tiles missing from ceiling due to water leak. remedy:repair &/or replace

    May 13, 2022 · Penalty $625

    Resolve
  • Class - 2

    Reissue38498148p failure to maintain bldg in codecompliant manner:illumination for exits,exit discharges&public corridors per bc1006.1;27-381.noted:@emergency light9 by 155,inside general office above entrance

    May 24, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner.noted:@main electrical meter rm located inside rm151,door isnt working properly.repair &/orreplace.

    May 24, 2021 · Penalty $625

    Active
  • Class - 2

    Reissue #35422248l failure to maintain bdlg in code compliant manner illumination for exits exit discharges and public corridors per bc 1006.1:27-381 1st floor exit lights not working properly throughout repair

    Jul 2, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue #35422249n exit door not self closing most door throughout are not closing properly repair and or replace

    Jul 2, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner illumination forexits,exit discharges and public corridors per bc 1006.1;27-381 at 1stfl near exit-3 light box#29 one place 2 lights and 1st fl near exit 2

    May 8, 2019 · Penalty $312

    Active
  • Class - 2

    Exit door not self-closing. at 1st fl near rm p 116 cafeteria door onedoor is not self closing properly,at 1st fl near rm#c103&near exit 3 each place 1 door not self closing properly at the time of inspection w

    May 8, 2019 · Penalty $312

    Active
  • Class - 2

    Failure to maintain bldg in code-compliant manner.illuminatin for exitexit discharges and public corridors per bc 1006.1;27-381-emergency lights at the following areas are not working:2 in gym area, 1 in corrid

    Jul 25, 2017

    Resolve
  • Class - 2

    Re-issue#35216405z.failure to maintain bldg in code-compliant manner.wate penetrating through roof over classrm #m113, s19 and c103 in areas of ventilation duct/ceiling.rem:maintain ext bldg wall.

    Jul 25, 2017

    Resolve
  • Class - 2

    Bc 28-301.1:unlaw placement of furnishings,decorations or other objects at exits that obstruct access to egress to and from or visibility thereof per fdny 2008 code.in meter rm.rem:comply w/nov

    Jul 25, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg wall(s) or appurtenances.note:water penetrating through roof over classroom #m113,s119 and c103 in areas of ventilation duct/ceiling.rem:seal penetration.

    Oct 21, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner:lack of emergency lighting for exits,exit discharges & public corridors per bc1006;27-542.noted:inoperative emergency light w/ battery back up over cafiteria al

    Sep 15, 2015

    Resolve
  • Class - 2

    Reissue: 34949678x failure to provide fire stopping. noted: the gas meter room is lacking fire stopping at the 1st floor level. rmdy: provide/maintain fire stopping.

    Jul 30, 2013

    Resolve
  • Class - 2

    27-369:excessive combustible art work. at 1st flr corridor numerous hanging combustible banners in fire corridors. rem:remove all items fromceiling.

    Apr 10, 2012

    Resolve
  • Class - 2

    Missing fire stop. at gas meter service room no fire stop above t-bar drop ceiling fire wall to concealed space in room 117 gym adjacent. rem:provide fire stopping.

    Apr 10, 2012

    Resolve
  • Class - 2

    27-369:partial obstruction. at 1st flr corridor,tables,chairs,& art work displays partially obstructs passageway. rem:remove all items,maintain corridor width clear.

    Apr 10, 2012

    Resolve
  • Class - 2

    Reissue : 34854647l roof has become porous and allowing rain into the bldg causing interior damage in the class rooms below. remedy: water proof exterior roof

    Mar 16, 2011

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. use of prohibited door and/or hardware per bc1008.1.8, 27-371(j). noted: door kick stops are installed on the majority of classroom doors and auxiliary room do

    May 7, 2010

    Resolve
  • Class - 2

    Failure to maintain bldg, exterior a/c roof units are leaking water into rooms s and n. rem: maintain building. repair and/or replace roof units.

    May 7, 2010

    Resolve
  • Class - 2

    Failure to maintain bldg. interior gas room has no permanent supply offresh air supply. installed light switch located on the inside of room& is not the approved type. remedy: maintain bldg repair and / or repl

    May 7, 2010

    Resolve
  • Class - 2

    Sec 27-361: failure to maintain egress clear and unobsructed. noted: exit a security desk obstructed exit doors by 50%. exit b obstructed bygym equipment and file cabinets. rem: maintain bldg. remove obstructio

    May 7, 2010

    Resolve
  • Class - 3

    Re 34712392p 70% classroom door checks missing 1sty bldg rem: install door checks

    Feb 18, 2009

    Resolve
  • Class - 2

    Reissue: 34586319y fifty percent of classroom doors is missing door closers on the 1st flr level. remedy: install door closers.

    Oct 3, 2008

    Resolve
  • Class - 2

    Reissue: 345686318m gas meter room has no ventilation as required located adjacent to the custodian office. 1st flr level. remedy: provide ventilation (fresh air).

    Aug 13, 2008

    Resolve
  • Non-hazardous

    Reissue:34400806n.gas meter room has no ventilation as required on 1stlevel.remedy:provide ventilation (fresh air).

    Aug 13, 2007

    Resolve
  • Non-hazardous

    Several interior doors are missing.door checks located all on the 1fl remedy:install door checks.

    Aug 13, 2007

    Resolve
  • Non-hazardous

    Meter room inside of custodian's office 151 has no ventilation as required. remedy: provide / maintain vent.

    May 17, 2006

    Resolve
  • Non-hazardous

    Panic hardware inoperative.noted:first floor exit c vestibule door hasa broken panic bar.remedy:repair/replace panic hardware.

    Apr 29, 2005

    Resolve
  • Non-hazardous

    Failure to maintain.defect noted:perimeter fence at play yard on ireland street side fabric has a hole approximately 2 feet wide x 4 feet high.remedy:maintain fence.repair/replace fabric.

    Apr 29, 2005

    Resolve
  • Non-hazardous

    Failure to maintain defect is: tile floor wraping, cracked at various location in cafeteria and in corridors leading into main entrance to cafeteria. remedy: repair or replace.

    Jan 17, 2002

    Resolve
  • Hazardous

    Failure to maintian building tiel floor is warpping, cracked anf defective in rooom p causing trip hazardous remedy : replace tile floor immediately

    Jan 17, 2002

    Resolve
  • Non-hazardous

    Failure to maintian. notd; vinyal fl tiles water logged and bulging in rooms d,f,g,k,o, m, n , o. eastern south corridor next to exit 3 and cafeteria. remedy: repair immediately.

    Jan 4, 2001

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1930
Floors
1
Residential units
—
Building area
32,207 ft²
Lot area
40,380 ft²
Zoning
M1-1
Community board
404
Council district
30
Block / lot
2451 / 21
Assessed value
$2,337,300
Landmark / historic district
No

Questions about 76-05 51 Avenue

Who owns 76-05 51 Avenue?

The owner of record in NYC Department of City Planning PLUTO data is Twin Music INC.

Does 76-05 51 Avenue have violations?

NYC HPD has no housing violations on record for this property.

Is 76-05 51 Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 76-05 51 Avenue built?

City records list 1930 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.