Violations at 2510 Avenue P
Brooklyn, NY 11229 · BBL 3-06788-0001 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
The newest 50 of 141 DOB violations. The city keeps the complete history.
- Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2021 external low pressure inspection
Jun 30, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2022 external low pressure inspection
Apr 25, 2023
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 12, 2021
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 11, 2021
Dob violation - active - High pressure boiler boiler required
Violation issued - failure to file 2017 external high pressure boiler inspection
Mar 16, 2020
Dob violation - dismissed - High pressure boiler boiler required
Violation issued - failure to file 2017 external high pressure boiler inspection
Mar 16, 2020
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 27, 2019
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 27, 2019
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 27, 2019
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 27, 2019
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 27, 2019
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 26, 2018
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 26, 2018
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 26, 2018
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 26, 2018
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 28, 2017
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 28, 2017
Dob violation - active - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2016 inspection/test
Sep 15, 2017
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2015 inspection/test
Dec 1, 2016
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 6, 2016
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 6, 2016
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 19, 2014
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 19, 2014
Dob violation - active - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2013 inspection/test
Oct 31, 2014
Dob violation - active - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2012 inspection/test
Mar 31, 2014
Dob violation - active - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2012 inspection/test
Mar 31, 2014
Dob violation - active - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2012 inspection/test
Mar 31, 2014
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2012 inspection/test
Mar 31, 2014
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2012 inspection/test
Mar 31, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 15, 2013
Dob violation - active
ECB violations
The newest 50 of 160 ECB violations. The city keeps the complete history.
- Class - 2
Reissue: 35692109l-failure to maintain building in code-compliant manner. at staircase #16 and #15 water penetration leading to stairs, walls, and ceiling. remedy: comply with code.
Mar 12, 2026 · Penalty $3,125
Active - Class - 2
Reissue: 35682868n-failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public gym per bc 1006.1; 27-381. 3rd floor gym lights not working, emergency lights. remedy
Mar 12, 2026 · Penalty $3,125
Active - Class - 2
Reissue: 35692107h. failure to maintain building in code-compliant manner. roof level water rises after raiins. leaks through 5th floor classrooms. remedy: comply with code.
Mar 12, 2026 · Penalty $3,125
Active - Class - 2
Reissue: 35692108j. failure to maintain building in code-compliant manner. roof bulkhead has water penetration through door saddle. remedy: comply with code.
Mar 12, 2026 · Penalty $3,125
Active - Class - 1
Hazardous cease use boiler#4>brick set hp boiler has loose i beam+bricks right side+loose bricks@top steam drum+corroded flue@chimney base;correct all hazardous conditions immediately+call dob 212 6020580 to li
Dec 31, 2025 · Penalty $2,500
Active - Class - 2
Observed one oil fired weilmcalin 782 945000 btu boiler, missing the sight glass and the jacket coming apart. correct all violating conditions and submit a certificate of corrections
Aug 18, 2025 · Penalty $1,250
Active - Class - 2
Reissue #35682869p: failure to maintain building in code-compliant manner: observed @ staircase #16 and #15 water infiltration from rooftop bulkhead leads onto stairs, walls and ceiling. remedy: repair and/or r
Mar 14, 2025 · Penalty $3,125
Active - Class - 2
Reissue #35682865h: failure to maintain building in code-compliant manner: observed from rooftop, at bulkhead water rises continue penetrating through door/saddle which leads to landing, waters and ceiling. rem
Mar 14, 2025 · Penalty $3,125
Active - Class - 2
Reissue #35682866j; failure to maintain building in code-compliant manner: observed at roof level water level rise after rains cause leaks through roofig materials and onto 5th floors classroom(s). remedy: repa
Mar 14, 2025 · Penalty $3,125
Active - Class - 2
Reissue #35682867l; failure to maintain building in code-compliant manner: observed @ 5th floor classrooms #526 ceiling damage caused by water infiltration through from roof. remedy: repair and/or replace.
Mar 14, 2025 · Penalty $3,125
Active - Class - 1
Failure to maintain building in code compliant manner. class 2 items: service to the second floor currently disabled, restore service to the second floor. class 1 item: brake monitor switch missing a bolt, prov
Jul 19, 2024 · Penalty $1,250
Active - Class - 2
Rts class 2: failure to maintain building in code compliant manner. upon inspection, the device is found to be out of service. remedy: restore to service and call the dob elevator division at (212) 393-2144 for
Jul 19, 2024 · Penalty $625
Active - Class - 2
Failure to maintain building in code compliant manner. class 2 items: fire extinguisher expired, update. in car communication inoperative, repair. pit dirty, clean.
Jul 19, 2024 · Penalty $625
Active - Class - 2
Reissue #35655163j. failure to maintain building in code-compliant manner. noted: at stairs 15 and 16 there are signs of water penetration from bulkhead and roof that is causing damage to the ceiling and walls
Jun 27, 2024 · Penalty $1,562
Active - Class - 2
Reissue #35672064z. failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public gymnasium per bc 1006.1; 27-381. noted: on the third floor gymnasium eight lights, t
Jun 27, 2024 · Penalty $1,562
Active - Class - 2
Reissue #35672061n. failure to maintain building in code-compliant manner. noted: on the fifth floor in room 526 the ceiling is damage, due to leak on the roof. remedy: repair and/or replace.
Jun 27, 2024 · Penalty $1,562
Active - Class - 2
Reissue #35672062p. failure to maintain building in code-compliant manner. noted: at roof level there are leaks at various locations. remedy: repair and/or replace.
Jun 27, 2024 · Penalty $1,562
Active - Class - 2
Reissue #35672063r. failure to maintain building in code-compliant manner. noted: observed at roof top bulkhead, water is penetrating through doors, and is gettiing corridors, stairs, and ceiling walls damage.
Jun 27, 2024 · Penalty $1,562
Active - Class - 2
Reissue 35560956h failure to maintain building in code-compliant manner.illumination for exits,exit discharges & public corridors per bc1006.1;27-386.emg light not working when tested 3fl gym 2 sets not working
Mar 14, 2023 · Penalty $1,562
Resolve - Class - 2
Reissue 35655160y failure to maintain building in code-compliant manner.rooftop bulkhead water infiltrated thru doors water getting stairs & corridors damage to ceiling & walls.remedy:repair and/or replace.
Mar 14, 2023 · Penalty $1,562
Active - Class - 2
Reissue 35655161x failure to maintain building in code-compliant manner.roof level several area leaks from parapet walls deteriorated conditions on walls.remedy:repair and/or replace
Mar 14, 2023 · Penalty $1,562
Active - Class - 2
Reissue 35655162h failure to maintain building in code compliant manner. 5th fl rm 526 ceiling damaged/spalling caused by water leak.remedy:repair and/or replace.
Mar 14, 2023 · Penalty $1,562
Active - Class - 2
Reissue35560951z(4/29/21) failure to maintain bldg in codecompliant manner@stairs15&16 water infiltrated from bulkhead&roof caused spalling/deteriorated on walls&ceiling 5-3fls.repair &or replace
May 6, 2022 · Penalty $1,562
Active - Class - 2
Reissue35560952k(4/29/21) failure to maintain bldg in codecompliant manner.@rm526@5fl,ceiling damaged/deteriorated/spalling caused by leak from roof.repair &or replace
May 6, 2022 · Penalty $1,562
Active - Class - 2
Reissue35560953m(4/29/21) failure to maintain bldg in codecompliant manner:@roof level in several area leaks from parapet weep holes into bldg.caused deteriorated conditions on walls&ceiling.repair &or replace
May 6, 2022 · Penalty $1,562
Active - Class - 2
Reissue35560955x(4/29/21) failure to maintain bldg in codecompliant manner:@rooftop bulkhead water infiltrated thru door/doorjamb onto stairs&corridors doors.caused damage to ceiling&walls.repair &or replace
May 6, 2022 · Penalty $1,562
Active - Class - 2
Failure to maintain bldg in codecompliant manner,illumination for exits,exit discharges&public corridors per bc1006.27.381.@3fl gym1 4place each place 3lights,@3fl gym2,4place each place 3lights&2fl gym 2place
Apr 29, 2021 · Penalty $625
Resolve - Class - 2
Reissue35422589j doi5.13.21 failure to maintain bldg in codecompliant manner note@roof level,bulkhead water penetration around doorjamb causing damage to interior walls.repair &/or replace.
Apr 29, 2021 · Penalty $1,562
Active - Class - 2
Reissue352603230h doi5.11.17 failure to maintain bldg in codecompliantmanner.noted@bsmt in swimming pool area,cracks on wall@various locations.make necessary repairs.
Apr 29, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue35422588h doi5.13.21 failure to maintain bldg in codecompliant manner note@roof level roof leaks in various areas&various roo leaks from parapet weep holes.repair &/or replace.
Apr 29, 2021 · Penalty $1,562
Active - Class - 2
Reissue35422591z doi5.13.19 failure to maintain bldg in codecompliant manner note:@5fl 526 ceiling damage due to roof leak.repair &/or replace.
Apr 29, 2021 · Penalty $1,562
Active - Class - 2
Reissue35422593m doi5.13.19 failure to maintain bldg in codecompliant manner note in stairway15&16 water penetration from roof leak causing damage to ceiling&wall.repair &/or replace.
Apr 29, 2021 · Penalty $1,562
Active - Class - 2
Reissue35490872j doi5.5.20 exit door not selfclosing properly.1fl exit3&4,3fl exit1&2 5fl exit1&2,7&8,3fl exit5&6,1.3fl gym near exitl&k 1exit door not selfclosing properly@time of insp.repair/replace door.
Apr 29, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue#35422590r failure to maintain bldg in a code compliant manner.noted: observed on the 1st fl stairway #5&6 handrail is broken. remedyrepair &/or replace.
May 5, 2020 · Penalty $1,562
Resolve - Class - 2
Reissue#35422595x failure to maintain bldg in code compliant manner: illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. noted: observed on the 2nd 3rd fl gymnasium. also on the 1st
May 5, 2020 · Penalty $1,562
Resolve - Class - 2
Reissue#35422594y exit door not self closing. noted: on the 1st fl ecxit#3 & 4,3rd fl exit 1 & 2,also on the 3rd fl exit 4 & 6,on the 5th flnext to room 506 & 507,all these door were not opening & closing prope
May 5, 2020 · Penalty $1,562
Resolve - Class - 2
Work after hours w/o variance permit contrary to 28-105.12.5. at the time of my inspection work performed under job#(302573533) was ongoing at auditorium balcony w/ the installation of temporary guardrails. mos
Jun 4, 2019 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code compliant manner illumination forexits,exit discharges and public corridors per bc 1006.1;27-381. note at 2nd fl gym emergency lights and exit light not lite. remedy:repair
May 13, 2019
Resolve - Class - 2
Exit door not self closing. note the following door not closing: 5th floor exit 1 + 2, 7 + 8 3rd floor exit 1 + 2 and 1st floor exit 3 + 4. remedy: repair or replace door
May 13, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner.note in stairway15&16,water penetration from roof leak causing damage to ceiling and wall.rem:repair and/or replace.
May 13, 2019
Active - Class - 2
Failure to maintain building in code compliant manner.note at 4th floor corridor outside room 410,hole in wall.rem:repair and/or replace.
May 13, 2019
Resolve - Class - 2
Failure to maintain bld.in code compliant manner.note:at 5th floor 526ceiling damage due to roof leak.rem:repair or replace.
May 13, 2019
Active - Class - 2
Failure to maintain bld. in code compliant manner.note at 1st floor stairway 5&6 handrail broken pulling away from wall.rem:repair or replace.
May 13, 2019
Resolve - Class - 2
Failure to maintain bld.incode compliant manner.note at roof level,bulkhead water penetration around door jam causing damage to interior walls.rem:repair and/or replace.
May 13, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner. note at roof level roof leaks in various area and various roofs leaks from parapet weep holes. remedy: repair and or replace
May 13, 2019
Active - Class - 2
28-301.1 reissued 35325617n unlawful display of artwork in corridors greater than 20% per fdny 2008 code 803.3.2. note artwork displayed in corridors throughout entire building greater than 20%. remedy:remove a
May 13, 2019
Resolve - Class - 2
Reissue of nov#35260324p sectuib 28-301.1 unlawful display of artwork in corridors greater than 20% per fdny 2008 code: fc803.3.2. noted: artwork displayed in corridors throughout the bldg is greater than 20%
Apr 2, 2018
Resolve - Class - 2
As per fgc 411.1 appliances shall be connected to the supply piping system by rigid metallic pipe and fittings 411.1.3 where appliances are equipped with casters and subject to periodic movement, appliance
Apr 2, 2018
Resolve - Class - 2
Appliances shall be connected to the gas piping system by rigid metallic piping and fittings as per 411.1.3, where appliances are equipped with casters, and subject to periodic movement, appliances shall be co
Apr 2, 2018
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. provide required corridor width per bc 1016.2;27-369. noted: at cellar corridor,storage of chairs,tables,boxes. remedy: provide proper corridor width.
May 11, 2017
Resolve