Violations at 238 Classon Avenue

Brooklyn, NY 11205 · BBL 3-01923-0001 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

28 DOB violations, newest first.

  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2018 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2018 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 30, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 30, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 3, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 3, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 9, 2017

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 30, 2013

    Dob violation - resolved
  • Failure to benchmark none

    Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4

    Jan 1, 2012

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 5, 2009

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 5, 2009

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 12, 2005

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 12, 2005

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Jan 19, 1989

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Jan 11, 1989

    Dob violation - active

ECB violations

33 ECB violations, newest first.

  • Class - 2

    Found fitzgibbons oil fired boilers active with defects at time of inspection. boiler refactory defective in chamber and chamber doors. correct all violating condition and submit a certificate of correction.

    Aug 14, 2024

    Resolve
  • Class - 3

    Corridor wall next to rm 303 has spalling plaster. remedy: repair wall.

    Apr 18, 2012

    Resolve
  • Class - 1

    Reissue #34919575x grates above area way from boiler room have excessive corrosion,grate supports are corroded through at several points leaving bolts supporting angle bracket detached. remedy: remove & replace

    Apr 18, 2012

    Resolve
  • Class - 2

    Reissue #34919574y. cmu walls in gym have vertical and step cracks at various locations. remedy: repair cracks.

    Apr 18, 2012

    Resolve
  • Class - 2

    Foundation wall in area way under (grates) at boiler room is cracked &spalling w/missing concrete in several areas exposing reinforcing steel. remedy: repair concrete wall.

    Apr 18, 2012

    Resolve
  • Class - 2

    Sec. 27-371(b). plexi vision panels installed on door to rooms 123 and215. remedy: install required glass panels.

    Apr 18, 2012

    Resolve
  • Class - 2

    Defective area grates @ cellar boiler room access to areaway,steel grate supports are rusted through @ several areas along the bldg side.rem:repair if feasible or replace

    Jul 5, 2011

    Resolve
  • Class - 2

    Defective cmu block @ gym,vertical cracks in cmu blockwall @ north,south & west walls.rem:repair masonry cmu block walls.

    Jul 5, 2011

    Resolve
  • Class - 3

    Reissue: 34692535h exterior foundation wall has become porous allowingwater to enter bldg in boiler room adj fdny box at cellar level. remedy: water proof the foundation wall.

    Mar 19, 2009

    Resolve
  • Class - 3

    Reissue 34569494r exterior foundation wall has become porous and allowing rain water to enter the building in the boiler room adjacent to the fdny box at cellar level. remedy: water proof foundation wall.

    Jul 15, 2008

    Resolve
  • Hazardous

    Reissue:34510150r no fire stopping applied at pipe penetration located at the boiler room on the north side at cellar level. remedy:provide fire stopping.

    May 1, 2007

    Resolve
  • Hazardous

    Reissue:34504916k:exterior foundation wall has become porous and allowing run water enter the bldg in the boiler room adjacent to the fdny box on cellar level. remedy:water foundation wall.

    May 1, 2007

    Resolve
  • Hazardous

    Reissue: 34475124m. exit doors not self closing (1)auditorium and stage doors rear east & west left han leaf(s). are racked (2)basement stair door 10/11 no closer. remedy: repair doors/replace missing closers.

    Jan 20, 2006

    Resolve
  • Hazardous

    Reissue:34475122z. failure to provide/maintain required fire-stopping within boiler room north & south end wall penetration above debris. remedy: provide/maintain required firestopping.

    Jan 20, 2006

    Resolve
  • Non-hazardous

    Water penetration into boiler room behind fdny box. remedy: water proof and seal areas along fdny box.

    Jan 20, 2006

    Resolve
  • Hazardous

    Defective hinge at exit #9 1st fl., exit 10 at 3rd and 2nd floor, defective hinge rod (vertical) at auditorium main entrance door left side adjacent to school main entry/exit doors. door #10, 11 at basement is

    Jan 20, 2006

    Resolve
  • Non-hazardous

    Noted : exit doors not self - closing : (1) auditorium stage and rear east & west left hand leafs are paked (2) basement stair door 10/11 remains in open position remedy : repair / replace doors / hardware as r

    Apr 20, 2005

    Resolve
  • Non-hazardous

    Noted : basement exit passafge / corridor required width decreased by obstructions charis, tables, computer equipment, band equipment, bookcases, desk, etc... remedy : remove obstructions, maintain passages cl

    Apr 20, 2005

    Resolve
  • Non-hazardous

    Noted : failure to provide maintain required fire - stopping within boiler room north & south end wall penetrations above doors remedy : provide / maintain required fire - stopping

    Apr 20, 2005

    Resolve
  • Non-hazardous

    Noted : exit doors required width decreased by obstructions : (1) 1st floor exit # 6 left hand leaf not openable - reducing exit by 1/3 (2) 1st floor exit # 8 left hand leaf not readily openable - reducing exit

    Apr 20, 2005

    Resolve
  • Non-hazardous

    "reissue" (34394317y).failure to maintain.defect is glazed back wall above auditorium entrance door is cracked.remedy:repair glazed block wall.

    Jun 30, 2004

    Resolve
  • Non-hazardous

    "reissue" (34394316m).failure to use panic hardware where required by law.note:auditorium occupancy #416 and no panic hardware install on stage east side exit door.remedy:provide panic hardware.

    Jun 30, 2004

    Resolve
  • Non-hazardous

    "reissue" failure to maintan. defects are: rear yard east (classon ave-side) paved- surface have numerous cracks. remedy: repair pavedsurface.

    Apr 16, 2003

    Resolve
  • Hazardous

    Failure to maintain. defects are: cracked and loose glazed blocks above auditorium entrance doors. remedy: repair glazed block wall.

    Apr 16, 2003

    Resolve
  • Non-hazardous

    Failure to use panic hardware where required by law. note. auditorium occupancy # 416 and no panic hardware install on stage east side exit door. remedy: provide panic hardware.

    Apr 16, 2003

    Resolve
  • Non-hazardous

    Failure to maintain. defect noted- concrete pavement is cracked at thru-fare from classon ave to dekalb ave(adj, to parks dept. fence)remedy: make all repairs.

    Apr 23, 2002

    Resolve
  • Non-hazardous

    Failure to maintain. defect are: concrete pavement is cracked at thru-fare from classon ave to dekalb ave (adj to parks dept fence). remedy: make all necessary repairs.

    Feb 23, 2002

    Resolve
  • Hazardous

    Failure to maintain defects exit door total obstruction. location: exit 8 adjacent lafayette 1st fl exits 546 1st fl. remedy: make safe reove obstruction.

    Jun 26, 2001

    Resolve
  • Non-hazardous

    Failure to maintain defects, damaged flooring exterior surface concrete cracked. location, thrufare from classon to parks dept fence due dekald. remedy: do repairs.

    Jun 26, 2001

    Resolve
  • Non-hazardous

    Failure to maintain.defects.cracked plaster ceilings.location rms 209,109,105,auditorium stage ceiling entire.remedy:do repairs

    Jun 26, 2001

    Resolve
  • Non-hazardous

    Failure to provide emegency light fixture within corridor and stairs(3location(on fl 1-3 including vestibule on first fl.failure to provide emegency power fr light fixture within corridos and stairs(3)on floor

    May 17, 2001

    Resolve
  • Non-hazardous

    No permit posted, sidewalk shed. noted: 1) no permit for sidewalk shedavailable at time of inspection. remedy: make permit available.

    Apr 5, 1999

    Resolve
  • Hazardous

    Failure to maintain building. noted: 1) no emergency lighting through-out school hazard. 2) flaf pole decayed & replace. 3) playfield need resurfacing. remedy: maintain building & remove hazards.

    Apr 5, 1999

    Resolve