1055 University Avenue

Bronx, NY 10452BBL 2-02527-0061Map

Owner of record: Highbridge Apartments Estates LLC

1055 University Avenue is an elevator apartment building built in 1927 in Bronx, 10452. It has 94 residential units across 6 floors. The owner of record is Highbridge Apartments Estates LLC. HPD has recorded 2,286 housing violations here, most recently on September 22, 2026. 22 of the 50 most recent violations are still open.

HPD violations
2,286
DOB violations
89
ECB violations
163
HPD complaints
7,870

What to know

Concern
6 open Class C

Immediately hazardous issues among recent violations are still open.

Watch
Last violation Sep 22, 2026

Date of the most recent HPD inspection that found a problem.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 2,286

  • A

    Paint with light colored paint to the satisfaction of this department all walls and the ceiling in the foyer located at apt 6f, 6th story, 2nd apartment from east at south , section ''northwest''

    Sep 22, 2026 · Apt 6F

    Open — Nov sent out
  • A

    Properly repair with similar material the broken or defective wood floor in the 4th room from east located at apt 6f, 6th story, 2nd apartment from east at south , section ''northwest''

    Sep 22, 2026 · Apt 6F

    Open — Nov sent out
  • A

    Paint with light colored paint to the satisfaction of this department all walls and the ceiling in the 4th room from east located at apt 6f, 6th story, 2nd apartment from east at south , section ''northwest''

    Sep 22, 2026 · Apt 6F

    Open — Nov sent out
  • B

    Repair the roof so that it will not leak above the ceiling in the 4th room from east located at apt 6f, 6th story, 2nd apartment from east at south , section ''northwest''

    Sep 22, 2026 · Apt 6F

    Open — Nov sent out
  • A

    Paint with light colored paint to the satisfaction of this department all walls and the ceiling in the private hallway located at apt 6f, 6th story, 2nd apartment from east at south , section ''northwest''

    Sep 22, 2026 · Apt 6F

    Open — Nov sent out
  • A

    Properly repair with similar material the broken or defective wood floor in the private hallway located at apt 6f, 6th story, 2nd apartment from east at south , section ''northwest''

    Sep 22, 2026 · Apt 6F

    Open — Nov sent out
  • A

    Refit door in the 1st room from east located at apt 6f, 6th story, 2nd apartment from east at south , section ''northwest''

    Sep 22, 2026 · Apt 6F

    Open — Nov sent out
  • A

    Properly repair with similar material the broken or defective wood floor in the 1st room from east located at apt 6f, 6th story, 2nd apartment from east at south , section ''northwest''

    Sep 22, 2026 · Apt 6F

    Open — Nov sent out
  • A

    Paint with light colored paint to the satisfaction of this department all walls and the ceiling in the 1st room from east located at apt 6f, 6th story, 2nd apartment from east at south , section ''northwest''

    Sep 22, 2026 · Apt 6F

    Open — Nov sent out
  • B

    Repair the roof so that it will not leak above the ceiling in the 1st room from east located at apt 6f, 6th story, 2nd apartment from east at south , section ''northwest''

    Sep 22, 2026 · Apt 6F

    Open — Nov sent out
Show 40 more ↓
  • C

    Abate the infestation consisting of mice in the entire apartment located at apt 6f, 6th story, 2nd apartment from east at south , section ''northwest''

    Sep 22, 2026 · Apt 6F

    Open — Notice of issuance sent to tenant
  • A

    Properly repair with similar material the broken or defective wood floor in the foyer located at apt 6f, 6th story, 2nd apartment from east at south , section ''northwest''

    Sep 22, 2026 · Apt 6F

    Open — Nov sent out
  • B

    Certify compliance with lead-based paint hazard control requirements during period of unit vacancy by submitting required supporting documentation and affidavits for apartment located at apt 4n, 4th story, 1st apartment from east at south , 1st section from east at south

    Mar 23, 2026 · Apt 4N

    Closed — Violation closed
  • B

    Certify compliance with lead-based paint hazard control requirements during period of unit vacancy by submitting required supporting documentation and affidavits for apartment located at apt 5d, 5th story, 2nd apartment from north at east , 2nd section from north at east

    Mar 23, 2026 · Apt 5D

    Closed — Violation closed
  • B

    Certify compliance with lead-based paint hazard control requirements during period of unit vacancy by submitting required supporting documentation and affidavits for apartment located at apt 4k, 4th story, 2nd apartment from west at north , 1st section from east at south

    Mar 23, 2026 · Apt 4K

    Open — Nov sent out
  • C

    M/d law abate the nuisance consisting of hot water temperature exceeding over 130 degrees at all fixtures in the entire apartment located at apt 1r, 1st story, 1st apartment from east at south

    Feb 20, 2026 · Apt 1R

    Closed — Violation closed
  • C

    Correct failure to notify occupants and/or to investigate lead-based paint hazards.

    Jan 14, 2026 · Apt 1C

    Open — Nov sent out
  • C

    Correct failure to provide to the department within 45 days of demand all records required to be maintained by owner pursuant to local law 1 of 2004 related to lead-based paint notices, inspections and remediation/abatement activities.

    Jan 14, 2026 · Apt 1C

    Open — Nov sent out
  • A

    Properly repair or replace the broken or defective light fixture at the ceiling in the bathroom located at apt 6p, 6th story, 2nd apartment from west at north , section ''north''

    Sep 18, 2025 · Apt 6P

    Closed — Violation dismissed
  • C

    Abate the infestation consisting of roaches in the entire apartment located at apt 6p, 6th story, 2nd apartment from west at north , section ''north''

    Sep 18, 2025 · Apt 6P

    Open — Notice of issuance sent to tenant
  • A

    Paint with light colored paint to the satisfaction of this department all walls in the 5th room from east located at apt 6p, 6th story, 2nd apartment from west at north , section ''north''

    Sep 18, 2025 · Apt 6P

    Closed — Violation dismissed
  • A

    Repair the broken or defective plastered surfaces and paint in a uniform color the ceiling in the 5th room from east located at apt 6p, 6th story, 2nd apartment from west at north , section ''north''

    Sep 18, 2025 · Apt 6P

    Closed — Violation dismissed
  • B

    Repair the roof so that it will not leak above the ceiling in the 5th room from east located at apt 6p, 6th story, 2nd apartment from west at north , section ''north''

    Sep 18, 2025 · Apt 6P

    Open — Nov sent out
  • A

    Properly repair with similar material the broken or defective wood floor in the 5th room from east located at apt 6p, 6th story, 2nd apartment from west at north , section ''north''

    Sep 18, 2025 · Apt 6P

    Closed — Violation dismissed
  • A

    Properly repair with similar material the broken or defective wood floor in the 4th room from east located at apt 6p, 6th story, 2nd apartment from west at north , section ''north''

    Sep 18, 2025 · Apt 6P

    Closed — Violation dismissed
  • A

    Repair the leaky and/or defective faucets at sink in the kitchen located at apt 6p, 6th story, 2nd apartment from west at north , section ''north''

    Sep 18, 2025 · Apt 6P

    Closed — Violation dismissed
  • A

    Refit door in the bathroom located at apt 6p, 6th story, 2nd apartment from west at north , section ''north''

    Sep 18, 2025 · Apt 6P

    Closed — Violation dismissed
  • C

    Abate the infestation consisting of mice in the entire apartment located at apt 6p, 6th story, 2nd apartment from west at north , section ''north''

    Sep 18, 2025 · Apt 6P

    Open — Notice of issuance sent to tenant
  • A

    Properly repair with similar material the broken or defective porcelain enamel finish by method of reglazing at bathub in the bathroom located at apt 6p, 6th story, 2nd apartment from west at north , section ''north''

    Sep 18, 2025 · Apt 6P

    Closed — Violation dismissed
  • A

    Properly repair with similar material the broken or defective wood floor in the 1st room from east at south located at apt 6p, 6th story, 2nd apartment from west at north , section ''north''

    Sep 18, 2025 · Apt 6P

    Closed — Violation dismissed
  • A

    Paint with light colored paint to the satisfaction of this department all walls in the 1st room from east at south located at apt 6p, 6th story, 2nd apartment from west at north , section ''north''

    Sep 18, 2025 · Apt 6P

    Closed — Violation dismissed
  • A

    Repair the broken or defective plastered surfaces and paint in a uniform color the ceiling in the 1st room from east at south located at apt 6p, 6th story, 2nd apartment from west at north , section ''north''

    Sep 18, 2025 · Apt 6P

    Closed — Violation dismissed
  • B

    Repair the roof so that it will not leak above the ceiling in the 1st room from east at south located at apt 6p, 6th story, 2nd apartment from west at north , section ''north''

    Sep 18, 2025 · Apt 6P

    Open — Nov sent out
  • A

    Refit door in the 1st room from east at north located at apt 6p, 6th story, 2nd apartment from west at north , section ''north''

    Sep 18, 2025 · Apt 6P

    Closed — Violation dismissed
  • A

    Properly repair with similar material the broken or defective wood floor in the 1st room from east at north located at apt 6p, 6th story, 2nd apartment from west at north , section ''north''

    Sep 18, 2025 · Apt 6P

    Closed — Violation dismissed
  • A

    Paint with light colored paint to the satisfaction of this department all walls in the 1st room from east at north located at apt 6p, 6th story, 2nd apartment from west at north , section ''north''

    Sep 18, 2025 · Apt 6P

    Closed — Violation dismissed
  • A

    Repair the broken or defective plastered surfaces and paint in a uniform color the ceiling in the 1st room from east at north located at apt 6p, 6th story, 2nd apartment from west at north , section ''north''

    Sep 18, 2025 · Apt 6P

    Closed — Violation dismissed
  • B

    Repair the roof so that it will not leak above the ceiling in the 1st room from east at north located at apt 6p, 6th story, 2nd apartment from west at north , section ''north''

    Sep 18, 2025 · Apt 6P

    Open — Nov sent out
  • A

    Properly repair or replace the broken or defective wood door in the 5th room from east located at apt 6p, 6th story, 2nd apartment from west at north , section ''north''

    Sep 18, 2025 · Apt 6P

    Closed — Violation dismissed
  • C

    Abate the infestation consisting of roaches in the entire apartment located at apt 1a, 1st story, 1st apartment from west at north

    Jul 17, 2025 · Apt 1A

    Closed — Violation dismissed
  • C

    Provide hot water at all hot water fixtures in the kitchen located at apt 3m, 3rd story, 2nd apartment from west at north

    Jul 11, 2025 · Apt 3M

    Closed — Violation dismissed
  • B

    Fire egress defective. remove obstructing bars or unlawful gates from at least 1 window or provide approved type gate .. in the kitchen located at apt 1a, 1st story, 1st apartment from west at north

    May 3, 2025 · Apt 1A

    Open — Not complied with
  • A

    Paint with light colored paint to the satisfaction of this department at east wall at public hall, 1st story

    Jan 3, 2024

    Closed — Violation closed
  • C

    Properly repair with similar material the broken or defective unkeyed fire retardent material at east wall (next to vestibule door) at public hall, 1st story

    Jan 3, 2024

    Closed — Violation dismissed
  • C

    Replace or repair the self-closing doors that is missing or defective frame at vestibule door leading to public hall , 1st story

    Jan 3, 2024

    Closed — Violation closed
  • A

    Paint with light colored paint to the satisfaction of this department the north wall in the private hallway located at apt 3l, 3rd story, 1st apartment from north at east , section at south

    Dec 15, 2023 · Apt 3L

    Closed — Violation dismissed
  • A

    Paint with light colored paint to the satisfaction of this department the west wall, 1st window frame from north at east wall in the 2nd room from north located at apt 3l, 3rd story, 1st apartment from north at east , section at south

    Dec 15, 2023 · Apt 3L

    Closed — Violation dismissed
  • A

    Paint metal in accordance with dept. regulation the 1st riser from east at south wall in the bathroom located at apt 3l, 3rd story, 1st apartment from north at east , section at south

    Dec 15, 2023 · Apt 3L

    Closed — Violation dismissed
  • A

    Paint with light colored paint to the satisfaction of this department the 1st door from south at west wall in the 1st room from north at west located at apt 3l, 3rd story, 1st apartment from north at east , section at south

    Dec 15, 2023 · Apt 3L

    Closed — Violation dismissed
  • C

    Certify compliance with lead-based paint hazard control requirements during period of unit vacancy by performing activities necessary to abate presumed lead-based paint from required window and/or door friction surfaces for apartment and make floors smooth and cleanable, presumed lead paint in an apartment with a child under six located at apt 3l, 3rd story, 1st apartment from north at east , section at south

    Dec 15, 2023 · Apt 3L

    Open — Lead docs submitted, acceptable

DOB building violations · 89

  • Construction other optional

    Emergency work order due to imminent hazardous conditino on exposures #3 & 4 south & west elev, sagging corroding metals, loose bricks & mortar joints. crack & step cracks @ multiple locations, broken window panes. immediately install sidewalk shed @ exp1,3&4 to protect public from hazard facade.retain professional to superv installation, repair

    Jul 8, 2025

    Dob violation - active
  • Construction other optional

    Partial vacate order due to multiple hazardous condtions such as crack and bulging masonry brivk pushing of window lintels. deteriorating win -dow lintels @ multiple locations. these conditions have made the cour tyard @ exp 4, n.elev, unable to be occupied. remedy: vacate entire courtyard 2 exp 4, n.elev, to be used in emergencied only

    Feb 11, 2025

    Dob violation - active
  • Failure to post energy grade/score none

    Failure to display energy efficiency score and energy efficiency grade as per adcode sec. 28-309.12.3

    Dec 1, 2024

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Oct 4, 2023

    Dob violation - active
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    May 11, 2022

    Dob violation - dismissed
  • Failure to post energy grade/score none

    Failure to display energy efficiency score and energy efficiency grade as per adcode sec. 28-309.12.3

    Apr 29, 2021

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 4, 2017

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 4, 2017

    Dob violation - resolved
Show 40 more ↓
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Jun 28, 2017

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Jun 28, 2017

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Jun 28, 2017

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2015 inspection/test

    Dec 1, 2016

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2015 inspection/test

    Dec 1, 2016

    Dob violation - dismissed
  • Residential elevator periodic inspection/test elevatorrequired

    Failure to perform category 5 inspection

    Jun 1, 2016

    Dob violation - dismissed
  • Residential elevator periodic inspection/test elevatorrequired

    Failure to perform category 5 inspection

    Jun 1, 2016

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Jul 1, 2015

    Dob violation - dismissed
  • Fail to certify class 1 none

    Failure to certify correction on immediately hazardous (class 1) ecb violation

    Jul 1, 2015

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 5, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 5, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 6, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 6, 2014

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2012 inspection/test

    Mar 31, 2014

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2012 inspection/test

    Mar 31, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 21, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 21, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 12, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 12, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 3, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 3, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 15, 2010

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 15, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 15, 2010

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 15, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 13, 2009

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 13, 2009

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 10, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 10, 2008

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 28, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 28, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 26, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 26, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 25, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 25, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 25, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 25, 2007

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 29, 2006

    Dob violation - resolved

ECB violations · 163

  • Class - 2

    Class 2: 1) maintenance program missing as per asme a17.1/csa b44 8.6. remedy: provide required program. 2) maintenance log book missing as per asme a17.1/csa b44 8.6.1.4. remedy: provide log book. 3) category

    May 26, 2026

    Resolve
  • Class - 2

    Class 2: 1) insufficient illumination in the motor room; light levels below acceptable working conditions as per asme a17.1/csa b44. remedy: restore adequate lighting. 2) machine oil leak observed. remedy: iden

    May 26, 2026

    Resolve
  • Class - 2

    Found federal fst -175 dual fuel boiler with exposed wiring, discharge pipe missing on coil relief valve, safety relief valves defective labels not legible and body drains missing, (need to be replaced)

    May 26, 2026

    Resolve
  • Class - 2

    Failure to properly secure/support electrical metallic tubing (emt). observed in the lobby on the a/b side of building emt pipes are not secured and not supported correctly. ec 358.30 nec sec. (a) must comply w

    May 26, 2026 · Penalty $500

    Active
  • Class - 1

    Electrical work without a permit. observed in basement exit signs / emergency lights installed thru out with new bx cables. also on in lobby new quad receptacles installed along with 1/2 inch emt conduit. 27-30

    May 26, 2026 · Penalty $2,500

    Active
  • Class - 1

    Failure to properly group/label disconnects. observed in the basement that the two main house 400 amp service switches was painted and not labeled also one 200 amp disconnect is not labeled ec 230.72(a). nec 11

    May 26, 2026 · Penalty $1,000

    Active
  • Class - 2

    Failure to certify corrections 39073449k, file a certificate of correction

    May 14, 2026 · Penalty $1,250

    Active
  • Class - 1

    Failure to maintain building walls and appurtenances. as noted at the time of inspection i observed on exposure #1 east elevation: loose bricks at 2nd floor brick eye brow. crack and step cracks 1st floor spand

    Jul 8, 2025 · Penalty $5,000

    Active
  • Class - 1

    Failure to maintain building in code-compliant manner. observed fire escapes obstructed by garden fences and handrail. located at exposure 1 and 4. emergency exit access inadequate. potential fire hazard., repa

    May 29, 2025 · Penalty $2,500

    Resolve
  • Class - 2

    I found a fedral fst175 steam boiler with barometric damper broken/ spill switch broken/mechanical fan on all the time/safety valve body drain missing/correct all violating condition/submit certificate of corre

    May 29, 2025 · Penalty $6,250

    Active
Show 40 more ↓
  • Class - 2

    Class 2 items: provide labeling for main line disconnect. category 1 test tag missing. repair basement and first floor hoistway door to fully close. provide access to overhead door. (inoperative) need to be rep

    May 27, 2025 · Penalty $625

    Active
  • Class - 2

    Class items: in-car communication inoperative. provide labeling for main line disconnect. fire extinguisher in machine room expired.

    May 27, 2025 · Penalty $3,125

    Active
  • Class - 1

    Failure to provide unobstructed exit passageway. note: at time of inspection i observed objects on fire escapes multi loc. at exp #1 east, #3 west impeding emergency exit passageways. remedy: remove all objects

    Feb 10, 2025 · Penalty $1,250

    Resolve
  • Class - 1

    Failure to maintain bldg exterior facade and appurtenances. note: at time of inspection, i observed exp #1 east-cracked brick by first floorlevel at both north/south facing walls.-exp #2 south-broken window gla

    Feb 10, 2025 · Penalty $2,500

    Active
  • Class - 2

    Failure to comply with the commissioners order contained in summons/violation# 39073449k issued on 10/31/2022 and to file a certificate of correction pursuant to 28-201.1 and 1rcny 102-01. failure to maintain i

    Jun 3, 2024 · Penalty $1,250

    Active
  • Class - 2

    Observed active water leak on overhead hot water piping located in the boiler room in the basement/cellar. as per 102.3 maintenance. installations, both existing and new, and parts thereof shall be maintained i

    Feb 2, 2024 · Penalty $310

    Resolve
  • Class - 1

    Unlawful acts: failure to comply with commissioner's orders as per ecb# 39073449k issued on 10/31/2022 and file a certificate of correction as pursuant to 28-201.1 and 1rcny 102-01., comply with commissioner's

    Jan 2, 2024 · Penalty $2,500

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. maintenance log not filled out, perform routine maintenance and update the maintenance log. car door gibs worn, replace.

    Dec 28, 2023 · Penalty $312

    Resolve
  • Class - 2

    At the time of my inspection, i observed in the basement. open defective wiring are in used, defective fluorescent lights are not secured, splice box in the elevator is not covered, armored cables are not prope

    May 25, 2023 · Penalty $2,000

    Resolve
  • Class - 2

    I observed in the apt 1d in office #3 the installation of a plastic covering over energized conductors. as noted in ecb #39055421j issued on 02/02/2022 the following violating condition remains in effect. a c o

    Nov 4, 2022 · Penalty $1,250

    Resolve
  • Class - 1

    I observed in the basement elevator disconnect switches the improper fusing of the conductors i noted 100 amp fuses installed with the conductors of a lesser ampacity. the conductors must be fused at the ampaci

    Nov 4, 2022 · Penalty $4,800

    Resolve
  • Class - 2

    Observed active water leak in the boiler room located in cellar. as per pc 102.3 maintenance. installations, both existing and new, and parts thereof shall be maintained in proper operating condition in accorda

    Nov 4, 2022

    Resolve
  • Class - 1

    I observed in the basement room marked water meter the conduit supplying power to the meter, apt 1d office #3, basement above the elevator and along the basement ceiling open junction boxes energized and expose

    Nov 4, 2022 · Penalty $1,600

    Resolve
  • Class - 2

    Observed piping throughout basement either supported incorrectly or not at all. as per pc 308.4hangers and anchors shall be attached to the building construction in an approved manner., repair and/or replace

    Nov 4, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    I observed in the elevator motor room failure to properly terminate cable raceways in the circuit breaker panel and the junction box underneath also noted in apt 1d office #3 the improper termination of the rac

    Nov 4, 2022 · Penalty $600

    Resolve
  • Class - 2

    Observed: at staircase a&c, several opening due pipe penetration through fireproof walls, also, cellar level, utilities rooms, corridors & storage rooms several opening due ceiling damages and pipe penetraction

    Oct 31, 2022

    Resolve
  • Class - 2

    Observed:-at exposure #3, outside area to emergency exit cracked retaining wall,also, floor slab and retaining wall are dilated/separated by approximately 1.5 inches., maintain exterior building wall

    Oct 31, 2022

    Resolve
  • Class - 2

    Observed. at bub cellar level, boiler room, metal structure (beams, columns and deck) is being installed to create a mezzanine space. also, at sub cellar level, offices with cubicles were created, accessed by a

    Oct 31, 2022 · Penalty $1,250

    Resolve
  • Class - 1

    Door zone restrictor not working tampered with disabled(cu). top of car fan not working.

    Oct 31, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    Observed: -at exposure #3, first fl, windows split/broken wood frame, windows are being covered by sheets of flammable material (wood)., repair and/or replace

    Oct 31, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Observed: at cellar level, corridors, common areas, utility rooms. emergency lighting is required to illuminate and identify hallways, stairwells and exits to facilitate a safe / orderly evacuation. also, there

    Oct 31, 2022 · Penalty $1,250

    Active
  • Class - 2

    Observed: at cellar level, exposure # 2,3,4 exit doors do not close properly when inspected, exposure # 3 exterior exit gates do not work properly & difficult to open., repair/replace door

    Oct 31, 2022 · Penalty $312

    Resolve
  • Class - 2

    In car phone not working.

    Oct 31, 2022 · Penalty $312

    Resolve
  • Class - 2

    At roof level, waterproofing cover membrane has expansion/peeling joints in different locations, damage that can cause water damage inside the building., repair and/or replace

    Oct 31, 2022

    Resolve
  • Class - 2

    Observed: -at b&c buildings, from second fl to roof, stair case a&c walls cracked, opening (pipes penetration) and detachment of mortar/ paint in different areas also, at exposure #1 (right side facade) steps c

    Oct 31, 2022

    Resolve
  • Class - 2

    Observed: at first floor lobby, ceiling damages, at cellar level, corridors, electrical room, storage rooms, walls/ceiling damages with openings, missing/detachment plasterboard, also, exposed ceiling/walls woo

    Oct 31, 2022

    Resolve
  • Class - 2

    Observed: at cellar level, water meter rooms, storage of material, debris, wooden stairs, garbage, construction equipment without proper housekeeping and maintenance., repair and/or replace

    Oct 31, 2022

    Resolve
  • Class - 1

    At exp # 2,3, 4, fire scape stairs, cellar level exit corridors & exp #1,2,3 exit passageway, are being obstructed by materials, garbage bags, mattresses, cardboard boxes and other elements that obstruct the ex

    Oct 31, 2022 · Penalty $1,250

    Active
  • Class - 1

    I observed in the basement room opposite the meter bank a to j inside the sheetrock column the improper termination and splicing of conductors in an exposed junction box. the connections were arcing and causing

    Feb 2, 2022 · Penalty $400

    Resolve
  • Class - 2

    I observed on the 1st floor in office #3 of apt 1d the improper termination of a raceway supplying power to the overhead light from the hall way fixture. as the wires are pinched under the light without effecti

    Feb 2, 2022 · Penalty $600

    Resolve
  • Class - 1

    I observed in the basement above the electric meters the installation of recessed lighting with the use of lamp wiring inside of a sheetrock ceiling. also noted in a storage/breakroom a 4 circuit panel with imp

    Feb 2, 2022 · Penalty $800

    Resolve
  • Class - 1

    97x10-entire device inoperative remedy:restore service

    Jan 7, 2020 · Penalty $312

    Resolve
  • Class - 2

    32h10,40m7,37m7. 32h10-too much play in carshoes; 40m7-no access to machine room missing keys; 37m7-no access to overhead missing keys. incomplete inspection call the super he was not on the premises. super

    Apr 10, 2019 · Penalty $625

    Resolve
  • Class - 2

    32h10,37m7,40m7,70m7. 32h10-too much play in car shoes; 37m7-no access to overhead missing keys; 40m7-no access to machine room missing keys. 70m7-no access to pit missing keys for car station. key switch

    Apr 10, 2019 · Penalty $625

    Resolve
  • Class - 2

    39x10,09i10,05j01,05k10,10h11,043d06,42i10,70o02,1m07. 39-fan not working; 09-car floor damaged/repair; 05-cab door banging on shaft wall; 05k-cab door rusted /repair; 10-replace cab door gibbs; 03-handrail

    Nov 14, 2018 · Penalty $312

    Resolve
  • Class - 2

    39x10,11m07,34e10,05k10,10h11,56y13,70o02. 39-fan not working;11-provide missing screws on car station; 34-banging goining down to basement; 05-cab door rusted; 10-replace cab door gibbs; 56-seal oil leak; 70

    Nov 14, 2018 · Penalty $310

    Resolve
  • Class - 2

    06i11,26b11,67b10,08v01,16t07,60q03,68m07,68m07,70o02,80b07,26d06. 06-car door is rusted and damage, replace door; 26-replace scape match switch for manual reset type 67-reprogram phone, 08-elevator not level

    Sep 28, 2018 · Penalty $625

    Resolve
  • Class - 1

    (c/u)5.a.10,5.b.1,59.bb.5,68.m.7,68.m.7-(5,a,10)door zone restrictor not working wired incorrectly.car door in the closed position plunger stay down and car door in the open position plunget pop up.(5,b,1)car d

    Sep 26, 2018 · Penalty $1,250

    Resolve
  • Class - 1

    (c/u)5.a.10,(c/u)44.b.10,59.bb.5,68.m.7,68.m.7,(c/u)78.l.10-(5,a,10)door zone restrictor not working taken a part.(44,b,10)loud screaming noise coming from maine overhead sheave.(59.bb.5)brake tag expired.(68,m

    Sep 26, 2018 · Penalty $1,250

    Resolve
  • Class - 2

    05e01,32i10,97v01,100m07,40p16. 05e01-car door is rubbing adjust; 32i10-car guideshoes slightly damage repair; 97v01-elevator is not leveling to certain floors adjust as needed; 100m07-in case of fire use stai

    Aug 8, 2018 · Penalty $310

    Resolve

Complaints

  • Unsanitary condition

    Mold

    Sep 15, 2026 · Apt 6F

    Close
  • Flooring/stairs

    Floor

    Sep 15, 2026 · Apt 6F

    Close
  • Unsanitary condition

    Pests

    Sep 15, 2026 · Apt 6F

    Close
  • Paint/plaster

    Wall

    Sep 15, 2026 · Apt 6F

    Close
  • Water leak

    Slow leak

    Sep 15, 2026 · Apt 6F

    Close
  • Door/window

    Window frame

    Sep 15, 2026 · Apt 6F

    Close
  • Unsanitary condition

    Pests

    Sep 15, 2026 · Apt 6F

    Close
  • Heat/hot water

    Entire building

    Mar 13, 2026 · Apt 5G

    Close
  • Heat/hot water

    Entire building

    Feb 20, 2026 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Jan 23, 2026 · Apt BLDG

    Close
Show 40 more ↓
  • Heat/hot water

    Entire building

    Jan 22, 2026 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Jan 15, 2026 · Apt BLDG

    Close
  • Unsanitary condition

    Pests

    Dec 30, 2025 · Apt 1C

    Close
  • Unsanitary condition

    Pests

    Dec 30, 2025 · Apt 1C

    Close
  • Safety

    Carbon monoxide detector

    Dec 30, 2025 · Apt 1C

    Close
  • Safety

    Smoke detector

    Dec 30, 2025 · Apt 1C

    Close
  • Unsanitary condition

    Mold

    Dec 30, 2025 · Apt 1C

    Close
  • Electric

    Power outage

    Dec 28, 2025 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Dec 6, 2025 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Nov 30, 2025 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Nov 27, 2025 · Apt BLDG

    Close
  • Heat/hot water

    Entire building

    Nov 21, 2025 · Apt 5H

    Close
  • Door/window

    Window frame

    Sep 19, 2025 · Apt 6P

    Close
  • Electric

    No lighting

    Sep 19, 2025 · Apt 6P

    Close
  • Door/window

    Door

    Sep 19, 2025 · Apt 6P

    Close
  • Paint/plaster

    Ceiling

    Sep 19, 2025 · Apt 6P

    Close
  • Paint/plaster

    Ceiling

    Sep 19, 2025 · Apt 6P

    Close
  • Paint/plaster

    Ceiling

    Sep 9, 2025 · Apt 6P

    Close
  • Paint/plaster

    Wall

    Sep 9, 2025 · Apt 6P

    Close
  • Heat/hot water

    Entire building

    Jul 11, 2025 · Apt 3M

    Close
  • Heat/hot water

    Entire building

    May 26, 2025 · Apt 4G

    Close
  • Safety

    Window guard broken/missing

    Apr 30, 2025 · Apt 1A

    Close
  • Heat/hot water

    Entire building

    Dec 14, 2024 · Apt BLDG

    Close
  • Door/window

    Door

    Aug 26, 2024 · Apt 6E

    Close
  • Door/window

    Door

    Aug 26, 2024 · Apt 6E

    Close
  • Unsanitary condition

    Pests

    Jul 28, 2024 · Apt 2C

    Close
  • Door/window

    Door

    Jul 28, 2024 · Apt 2C

    Close
  • Electric

    Outlet/switch

    Jul 28, 2024 · Apt 2C

    Close
  • Unsanitary condition

    Sewage

    Jul 28, 2024 · Apt 2C

    Close
  • Plumbing

    Toilet

    Jul 28, 2024 · Apt 2C

    Close
  • Heat/hot water

    Apartment only

    Apr 14, 2024 · Apt 6H

    Close
  • Heat/hot water

    Entire building

    Mar 3, 2024 · Apt 4B

    Close
  • Heat/hot water

    Entire building

    Jan 1, 2024 · Apt 4B

    Close
  • Heat/hot water

    Entire building

    Dec 22, 2023 · Apt 4D

    Close
  • Heat/hot water

    Apartment only

    Dec 12, 2023 · Apt 3B

    Close
  • Heat/hot water

    Entire building

    Dec 7, 2023 · Apt 3L

    Close
  • Heat/hot water

    Entire building

    Dec 3, 2023 · Apt 5K

    Close
  • Heat/hot water

    Entire building

    Oct 11, 2023 · Apt BLDG

    Close
  • Unsanitary condition

    Pests

    Jun 7, 2023 · Apt 5D

    Close
  • Unsanitary condition

    Pests

    Jun 7, 2023 · Apt 4D

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
Elevator apartment building (D7)
Year built
1927
Floors
6
Residential units
94
Building area
89,457 ft²
Lot area
19,887 ft²
Zoning
R7-1
Community board
204
Council district
16
Block / lot
2527 / 61
Assessed value
$3,131,550
Landmark / historic district
No

HPD registration #202713, last renewed Jul 28, 2025.

Questions about 1055 University Avenue

Who owns 1055 University Avenue?

The owner of record in NYC Department of City Planning PLUTO data is Highbridge Apartments Estates LLC.

Does 1055 University Avenue have violations?

Yes. NYC HPD has recorded 2,286 housing violations at this property.

Is 1055 University Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 1055 University Avenue built?

City records list 1927 as the year it was built.

How many apartments are in 1055 University Avenue?

It has 94 residential units and 95 units in total.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.