roofy

2230 5 Avenue

Manhattan, NY 10037BBL 1-01733-0017Map

Owner of record: NYC Department Of Parks And Recreation

2230 5 Avenue is a school building built in 1956 in Manhattan, 10037. The owner of record is NYC Department Of Parks And Recreation. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
18
ECB violations
71
HPD complaints
11

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 18

  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 19, 2003

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
Show 8 more ↓
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 18, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 18, 1993

    Dob violation - dismissed

ECB violations · 71

  • Class - 2

    Reissue #35688984h date of issue: 09-09-24. exit door not self-closingproperly. at the time of inspection, at the time of inspection observed and noted at cellar level gym 3 emer. exit door are not self-closing

    Jul 30, 2025 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. at the time of inspection observed and noted at 2nd fl. stairway 'd' em

    Jul 30, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. at the time of inspection observed and noted at cellar room electrical room, unlawfulstorage elevator equipments, boxes, package. remedy: replace all from

    Jul 30, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted interior fpsc doors not working properly at 2nd fl stair f, 1st fl cafeteria(2 doors) ist fl stair e, main entrance smoke doors, exit #5 smoke door b

    Sep 9, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted at 2nd flfan room vertical crack in cmu wall approx. 7' in length. cellar watermain room vertical crack in cmu wall approx. 4', auditiorium stage rig

    Sep 9, 2024 · Penalty $625

    Resolve
  • Class - 2

    28-301.1. unlawful placement of furnishings, decorations or other objects at exits that obstruct access to, egress from or visibilty thereofper fdny 2008 code; fc 1027.4. noted at cellar level sprinkler room ex

    Sep 9, 2024 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner: use of prohibited door and/or hardware per bc 1008.1.8; 27-371(j). noted approx. 60% of classrooms and egress doors have illegal kickstops installed, at mu

    Sep 9, 2024 · Penalty $625

    Resolve
  • Class - 2

    Reissue #35652552j. failure to maintain building in code-compliant manner. noted chipping paint on wall at main entrance steps down by school safety desk. by rooms 244 and 242 bulging ceiling tiles across corri

    Sep 9, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted approx. 75% of emergency lights not working when tested throughou

    Sep 9, 2024 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self-closing. noted: exterior doors at exit #4 and #5 not self-closing. mentioned doors are reached/rub on saddle. remedy: repair/replace door.

    Sep 9, 2024 · Penalty $625

    Resolve
Show 40 more ↓
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:upon inspection observed at main entrance near school safety guard desk,stairs leading down to auditorium has peeling & chipping paint on the walls ne

    Jun 6, 2024 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self closing properly, at the time of inspection observed that at 2nd floor near stair "a" 2 exit doors, at 2nd fl near stair-'f' 1 exit door, at 2nd floor near rm-229 one corridor exit door, at 1

    Aug 2, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner illumination for exits, exit discharges and public corridors per bc 1006.1;27-381 at the time of inspection observed that at first floor lunch room no-8 eme

    Aug 2, 2023 · Penalty $625

    Resolve
  • Class - 2

    E&h door not self closing. noted: at basement gym & hallway double doors near gym door checks were in disrepair/non operational when tested.remedy: repair/replace door.

    May 20, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at basement level hallway double doors near gym indisrepair/racked. remedy: repair &/or replace.

    May 20, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at basement gas & electric meter rooms storage of various items & materials chairs,boxes,tools cleaning products etc. remedy: comply w/code.

    May 20, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner illumination for exits,exit discharges & public corridors per bc 1006.1/27-381. noted: at(1st fl)cafeteria(basement)auditorium & gym emergency lights were non

    May 20, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at 1st fl cafeteria area entry/exit doors installed non shatter proof plexiglass in place of the required(tempered)shatter proof glass also w/some crack

    May 20, 2020 · Penalty $625

    Resolve
  • Class - 2

    Re-issue #35326548n.date of issue 04/11/2018. failure to maintain building in code compliant manner.illumination forexits,exit discharges & public corridors per bc 1006.1;27-381 at 2nd f

    Jun 5, 2019 · Penalty $3,125

    Resolve
  • Class - 2

    Exit door not self closing properly at 1st floor staircase "d".2(two) doors are not self closing at basement level,staircase "a",one door isnot self closing properly at the time of inspection when tested.rem:

    Jun 5, 2019 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: lack of emergency lights for exits, exit discharges and public corridor per bc 1006.1 noted: at cafeteria, gym and auditoirum, inoperative emergency li

    Apr 11, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at cafeteriaarea and at corridors at 2nd floor, missing ceiling tiles at various locations. rmdy: comply with code/install ceiling tiles.

    Apr 11, 2018

    Resolve
  • Class - 2

    Exit door not self closing. noted: interior foyer main entrance doors have defective in the top hinge and not operate properly. rmdy: complywith code repair or replace.

    Apr 11, 2018

    Resolve
  • Class - 2

    Re issue #35213778h failure to maintain bldg in code compliant manner: lack of emergency lighting for exits,exit discharges and public corridors per bc 1006.1;27-542.noted:existing emergency lights are not oper

    May 4, 2017

    Resolve
  • Class - 2

    Failure to maintian bldg in code compliant manner no fire stopping perbc712.3;27-345.rem:provide/maintain fire stopping.

    Sep 22, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner.lack of emergency lighting for exits,exit discharges &public corridors per bc1006.1 27-542:found many lights doesn't work properly like exit f,b, exits to stwy

    Sep 22, 2016

    Resolve
  • Class - 2

    Failure to maintain exit doors not self closing.found @basement level corridor smoke door near stwy"a",also stwy"c" dining room,from hall toboiler room, boiler room door.rem:repair or replace door.

    Sep 22, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner:provide required corridor w.per bc 101.62;27-369 found-blocking access to rooms #232,234 &r140 fan room b1 &b3-note room 232,234,r140.blocking access to electri

    Sep 22, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner-illumination for exits,exit discharges &public corridors per bc1006.1;27-381-observed-exuts high from inside library missing-2signs @auditorium doesnt work.rem:

    Sep 22, 2016

    Resolve
  • Class - 2

    Failure to maintain in code compliant manner. fail to provide wired vision panel as required per 27-371(b). at time of inspection i observed no wired glass on door at auditorium front left exit door.rmdy:comp

    Oct 15, 2015

    Resolve
  • Class - 2

    Reissue #35093176r exit door not self-closing. noted: basement level corridor smoke doors near stairway "a" are not closing. rmdy: repair/ replace doors.

    Oct 15, 2015

    Resolve
  • Class - 2

    27-371(b). re-issue # 35003046r. 1st floor stwy "e" plexi-vision panels installed. plexi-vision panels also installed at auditorium front left exit door. remedy: provide required glass panels.

    Mar 19, 2014

    Resolve
  • Class - 2

    Combustible material are hanging from numerous light fixtures at 2nd floor corridors. remedy: remove combustible material forthwith!

    Mar 19, 2014

    Resolve
  • Class - 2

    Basement level, gym ceiling tiles are loose. remedy: repair/replace ceiling tiles.

    Mar 19, 2014

    Resolve
  • Class - 2

    Basement level corridor smoke doors near stwy "a" are not closing. remedy: repair/replace doors.

    Mar 19, 2014

    Resolve
  • Class - 2

    Holes in wall of electrical room left of entrance door at pipe penetrations. remedy: provide/maintain fire stopping.

    Mar 19, 2014

    Resolve
  • Class - 2

    Sec. 27-371(b). plexi-vision panels installed on doors to rms 113,111,109,107,105,103 and on doors to stair e at 1st flr. remedy: provide required glass panels.

    Jan 24, 2013

    Resolve
  • Class - 2

    3rd floor stwy 'b' & 'a' doors racked. corridor smoke doors near room 323 hot closing. 2nd floor stwy 'd' & 'c' are racked. 1st floor stwy 'a'& 'b' & 'c' doors are racked. vestibule door at exit #5 doors racked

    Jun 27, 2011

    Resolve
  • Class - 2

    Electrical room @ basement level is being used for storage of chairs, rugs and a cabinet. remedy: remove storage from electrical room

    Apr 22, 2010

    Resolve
  • Class - 2

    2nd fl stwy "b" and basement stwy "b" door not closing. remedy: repairreplace doors

    Apr 22, 2010

    Resolve
  • Class - 2

    Reissue: 34792757l holes above door of electrical room @ basement level. remedy: provide maintain fire stopping

    Apr 22, 2010

    Resolve
  • Class - 2

    Electrical room at bsmt lvl is being used for storage of boxs floor cleaning equipment buckets ect rem: remove storage items from room

    Jun 18, 2009

    Resolve
  • Class - 2

    Holes above door of electrical room at bsmt lvl rem: provide maintain fire stopping

    Jun 18, 2009

    Resolve
  • Class - 2

    Sec bc1017.1 27-369 cafeteria exit door new ktcn is partially blocked w/ milk chest rem: remove obstruction

    Jun 18, 2009

    Resolve
  • Class - 2

    Concrete slab above exit doors d at west side of premises is spalling rem: repair replace spalling concrete

    Jun 18, 2009

    Resolve
  • Class - 2

    2nd fl stwy d g and corridor smoke doors near room 211 not closing 1st fl stwy e doors not closing exit doors d not closing and hard to open vestibule doors at exit d also not closing rem: repair replace doors

    Jun 18, 2009

    Resolve
  • Class - 2

    All roof access doors locked from inside w/ sliding latch locking mechanisms rem: remove illegal hardware

    Jun 18, 2009

    Resolve
  • Hazardous

    Exterior brick is missing mortar located at the rear of the school on the 1st level causing water to enter the bldg creating interior damages. remedy: replace missing mortar.

    Jul 19, 2007

    Resolve
  • Hazardous

    Foundation wall has become porous & allowing rain water into the bldg causing interior damages in the boiler room on the cellar level. remedy: water proof foundation wall.

    Jul 19, 2007

    Resolve
  • Non-hazardous

    Cease use.50/51/.preferred f.t.s.m boiler,lp steam.50-major corrosion & wastage of the ground-level flue gas outlet breeching on the referenced boiler.potentiar for flue gas emission into the boiler room

    Jan 3, 2007

    Resolve

Complaints

  • Unsanitary condition

    Garbage/recycling storage

    Jun 4, 2023 · Apt BLDG

    Close
  • Flooring/stairs

    Floor

    Nov 22, 2022 · Apt 44

    Close
  • Paint/plaster

    Wall

    Nov 22, 2022 · Apt 44

    Close
  • Unsanitary condition

    Pests

    Oct 22, 2022 · Apt 11S

    Close
  • Unsanitary condition

    Mold

    Jun 1, 2022 · Apt 2K

    Close
  • Heat/hot water

    Entire building

    Mar 19, 2021 · Apt 10L

    Close
  • Heat/hot water

    Apartment only

    Jan 31, 2019 · Apt C9H

    Close
  • Plumbing

    Water supply

    Nov 15, 2008 · Apt 32

    Close
  • Plumbing

    Water supply

    Jun 3, 2008 · Apt 5S

    Close
  • Plumbing

    Water supply

    Jun 3, 2008 · Apt 5S

    Close
Show 1 more ↓
  • Heating

    Heat related

    Jan 28, 2005 · Apt 5B

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1956
Floors
2
Residential units
—
Building area
100,200 ft²
Lot area
104,411 ft²
Zoning
R7-2
Community board
110
Council district
9
Block / lot
1733 / 17
Assessed value
$6,554,700
Landmark / historic district
No

Questions about 2230 5 Avenue

Who owns 2230 5 Avenue?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Parks And Recreation.

Does 2230 5 Avenue have violations?

NYC HPD has no housing violations on record for this property.

Is 2230 5 Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 2230 5 Avenue built?

City records list 1956 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.