350 West 88 Street
Manhattan, NY 10024BBL 1-01249-0054Map
Owner of record: 350 Realty Co
350 West 88 Street is a hotel built in 1910 in Manhattan, 10024. The owner of record is 350 Realty Co. HPD has recorded 15 housing violations here, most recently on October 18, 2026. 3 of the 15 most recent violations are still open. City tax records listed 29 rent-stabilized apartments here in 2024.
- HPD violations
- 15
- DOB violations
- 46
- ECB violations
- 34
- HPD complaints
- 28
What to know
No open immediately-hazardous violations among recent records.
Date of the most recent HPD inspection that found a problem.
No balance due on recent ECB violations.
Rent stabilization
Counts come from owners' rent-stabilization filings shown on NYC Department of Finance tax bills, as extracted by JustFix. They tell you a building has stabilized apartments, not which ones.
Think your apartment is stabilized? Request its rent history from HCR (free), then check your renewal with the renewal calculator.
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 15
- ANon-hazardous
Trace and repair the source and abate the visible mold condition... less than 10 sqft at ceiling in the 1st room from east located at b-room 322, 3rd story, 1st b-room from north at east , section ''east''
Oct 18, 2026 · Apt 322
Open — Notice of issuance sent to tenant - BHazardous
Properly repair the source and abate the evidence of a water leak at ceiling in the bathroom located at b-room 322, 3rd story, 1st b-room from north at east , section ''east''
Oct 18, 2026 · Apt 322
Open — Nov sent out - BHazardous
Repair the broken or defective plastered surfaces and paint in a uniform color at ceiling in the bathroom located at b-room 322, 3rd story, 1st b-room from north at east , section ''east''
Oct 18, 2026 · Apt 322
Open — Nov sent out - CImmediately hazardous
Remove device preventing door from being self-closing kick stand at vestibule door to public hall , 1st story
Oct 19, 2023
Closed — Violation closed - ANon-hazardous
Post and maintain a proper notice on wall of the entrance story in english and spanish on the availability of the agencys housing information guide. a sample notice can be found at www.nyc.gov/hpd. at public hall, 1st story
May 24, 2018
Closed — Violation closed - ANon-hazardous
Post a proper notice of smoke detector requirements, in a form approved by the commissioner, at or near the mail box improper sign at public hall, 1st story
May 24, 2018
Closed — Violation closed - ANon-hazardous
Post a proper notice of carbon monoxide detecting device requirements, in a form approved by the commissioner, in a common area of a class a multiple dwelling near inspection certificate or provide notice to tenants in a private dwelling. at public hall, 1st story
May 24, 2018
Closed — Violation closed - ANon-hazardous
Post, in a form approved by the commissioner, and maintain a notice in a common area of the building regarding the procedures that should be followed when a gas leak is suspected at public hall, 1st story
May 24, 2018
Closed — Violation closed - ANon-hazardous
Post and maintain a proper sign on wall of entrance story showing the registration number assigned by the department and the address of the building. at public hall, 1st story
May 24, 2018
Closed — Violation closed - ANon-hazardous
Post sign on wall of entrance story bearing name, address including apartment number if any, and telephone number of superintendent, janitor or housekeeper. at public hall, 1st story
May 24, 2018
Closed — Violation closed
Show 5 more ↓
- CImmediately hazardous
Post notice, in form approved by the department, stating the name and location of the person designated by the owner to have key to buildings heating system missing at public hall, 1st story
May 24, 2018
Closed — Violation closed - ANon-hazardous
§ 329, m/d law and dept. rules and regs. provide a completed certificate of inspection visits in a proper frame at or near mailboxes, bottom edge of frame between 48-62 inches above floor frame missing at public hall, 1st story
May 24, 2018
Closed — Violation closed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Oct 26, 2016
Closed — Violation dismissed - CImmediately hazardous
Provide hot water at all hot water fixtures at community bathroom at east , 1st story, section at east
Dec 11, 2012
Closed — Violation closed - BHazardous
§ 300, 301, 302, m/d law file plans and obtain a certificate of occupancy to legalize the following alteration or restore premises to prior legal condition community bathroom now converted to private bathroom for b room 412 now used as a class apt 4th story east sec.
Jul 3, 2003
Closed — Violation closed
DOB building violations · 46
- No report and / or late filing (facade) facade required
Failed to file fisp cycle 9a technical report by 02/21/2022
Feb 22, 2022
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Aug 2, 2020
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
May 2, 2020
Dob violation - dismissed - Facade safety program facade required
Fisp-facade safety program facade required
Jan 25, 2017
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 7, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 7, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 9, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 9, 2013
Dob violation - resolved - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2011 inspection report
Mar 1, 2013
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 10, 2012
Dob violation - resolved
Show 36 more ↓
- Elevator elevatorrequired
E-elevator elevatorrequired
Jul 6, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 2, 2011
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 1, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 1, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 1, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 24, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 24, 2009
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 24, 2009
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 5, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 5, 2008
Dob violation - resolved - Construction other optional
C-construction other optional
Jul 26, 2008
Dob violation - dismissed - Emergency power none
Ll2604e-emergency power none
Mar 31, 2008
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 18, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 18, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 6, 2004
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 6, 2004
Dob violation - resolved - Elevator elevatorrequired
1p8716
Oct 4, 2000
Dob violation - resolved - Facade facade optional
Ll10/80-local law 10/80 - facade facade optional
Mar 27, 2000
Dob violation - dismissed - Elevator elevatorrequired
1p8716
Oct 5, 1999
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 20, 1999
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 13, 1997
Dob violation - active - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 13, 1997
Dob violation - dismissed - Construction other optional
C-construction other optional
Dec 4, 1996
Dob violation - dismissed - Construction other optional
C-construction other optional
Dec 4, 1996
Dob violation - dismissed - Construction other optional
C-construction other optional
Dec 4, 1996
Dob violation - dismissed - Construction other optional
C-construction other optional
Dec 2, 1996
Dob violation - dismissed - Construction other optional
C-construction other optional
Dec 2, 1996
Dob violation - dismissed - Construction other optional
C-construction other optional
Dec 2, 1996
Dob violation - dismissed - Construction other optional
C-construction other optional
Nov 21, 1996
Dob violation - dismissed - Construction other optional
C-construction other optional
Nov 21, 1996
Dob violation - dismissed - Construction other optional
C-construction other optional
Nov 21, 1996
Dob violation - dismissed - Landmark none
Landmk-landmark none
Sep 13, 1996
Dob violation - dismissed - Landmark none
Landmk-landmark none
Sep 13, 1996
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 1, 1994
Dob violation - dismissed - Elevator elevatorrequired
Device #1p8716
Jan 29, 1991
Vp*-violation unserved ecb- dismissed - Elevator elevatorrequired
#54t-post name of maintenenace company
Mar 6, 1990
Dob violation - resolved
ECB violations · 34
- Class - 1
Observed on the 8th floor upright sprinkler heads not installed correctly. sprinkler heads throughout the building are obstructed. toilets seats are not open ended. basement a standpipe valve is broken and spri
Jan 15, 2026 · Penalty $2,530
Resolve - Class - 1
Failure to maintain building in code-compliant manner: no fire stopping per bc 712.3 (2014 code); 27-345; bc 711.2.4 (2022 code. observd hole penetrations located in electrical rooms and in the corridor by the
Sep 26, 2024 · Penalty $2,500
Resolve - Class - 2
Failure to maintain building in code-compliant manner. black gate leading to street defective. also observed no self closing door at boiler room (location basement level)., repair and/or replace
Sep 26, 2024
Resolve - Class - 2
Exit door not self-closing. observed non self closing doors on roof and basement level. potential fire hazard, repair/replace door
Sep 26, 2024
Resolve - Class - 1
I observed the installation of conduits, subfeeder, branch circuit wiring, electrical panel, breakers, junction boxes, and devices, in the main electric room and the employee break room. no permit on file cover
Sep 17, 2024 · Penalty $800
Resolve - Class - 2
I observed in the employee break area and the boiler room the failure to install/ provide gfci protection as required in mechanical rooms and within 6 ft of a sink. photos taken., install gfc1 protection; provi
Sep 17, 2024 · Penalty $1,200
Resolve - Class - 1
I observed a new electrical panel, sub-feeders, and conduit from the mdp for the installation of branch circuit wiring, junction boxes and devices to a new employee break area. this work was performed by unknow
Sep 17, 2024 · Penalty $4,800
Resolve - Class - 2
Failure to maintain exterior building facade and appurtenances. noted:observed there are spalling concrete at exp 1(n. elev) at parapet level. also observed there is a cracked stone and water table at exp 2(e.
Sep 6, 2024 · Penalty $620
Resolve - Class - 1
Observed in the gas meter room adjacent from the electrical meter room located in the basement/cellar no fire stopping or missing fire stopping missing from full height partition wall., provide/maintain fire st
Aug 20, 2024 · Penalty $625
Resolve - Class - 2
Observed in the gas meter room located in the room adjacent from the electrical room no ventilation noted. as per e 4 of the fuel gas code an opening to the outside air in the wall of such room or space, provid
Aug 20, 2024
Resolve
Show 24 more ↓
- Class - 1
Failure to maintain exterior building facade and appurtenances. notes:hazardous conditions observed (1)at exposure #1(north) cracked watertable and stones at northeast corner (2)defective stucco/masonry at para
Jul 31, 2024 · Penalty $2,500
Resolve - Class - 1
Unlawful acts.failure to comply with commissioner's order.note:at the time of inspection observed respondent failure to comply with previousviolation#35674548y dated 12/19/2023,which requires repair damage faca
Mar 21, 2024 · Penalty $2,500
Resolve - Class - 1
Failure to maintain exterior building facade and appurtenances. noted at time of inspection east elevation exposure #2 cracked masonry stone at facade and water table. north elevation exposure #1 (west 88 stree
Dec 19, 2023 · Penalty $6,250
Resolve - Class - 2
Removal of safety measures/sidewalk shed without departments approval note at time of inspection building facade was still esignated as unsafe the amended facade report (trg) received on 6-20-19 has not been ac
Jun 24, 2019 · Penalty $625
Resolve - Class - 2
Failure to maintain exterior building facade and appurtenance. roof level observe coping stone on gas elevations spalled joint /loose at roof parapet wall on east elevation. remedy: maintain exterior
May 24, 2019
Resolve - Class - 2
Failure to file acceptable amended cycle 8a report indicating correction of unsafe conditions described in initial facades report required by 28-302.5 for control#804022. remedy: file acceptable report
Aug 1, 2018 · Penalty $1,250
Resolve - Class - 1
28-301.failure to maintain bldg in code compliant manner.defects noted1hole in ceiling where gas dryer exhaust duct penetrates sheetrock at public laundry room area(2)use of flexible pipping connection for gas
Mar 12, 2014 · Penalty $400
Resolve - Class - 1
28-301.1 failure to maintain in code compliant manner.exhaust discharge must be no closer than 10'from building opening as per rs 2-2.1.4 & mc 401.5.2.note:(1)exhaust outlet for 4-commercial gas dryers terminat
Mar 12, 2014 · Penalty $400
Resolve - Class - 2
05l10,52j01. 05- zone restrictor. 52- hoist cables too long.
May 24, 2013
Resolve - Class - 1
Failure to maintain bldg wall or appurtenances.defects noted:rubble/brick fence located at rear of premises exposure #2 missing stones abovebedrock footing.remedy:repair defects.
Jul 26, 2008
Resolve - Non-hazardous
Failure to maintain exterior building walls. noted at north elevation 8 floor spalling and cracked stucco, at east and west elevations 8 flsbrick masonry bulged, cracked and displaced with steel window lintels
Apr 28, 2000 · Penalty $350
Resolve - Non-hazardous
Failure to file a report of compliance with local law 16/84 certifying to the installation of required fire protection systems.remedy:file report.
Feb 22, 2000
Resolve - Non-hazardous
Failure to provide "3"stair and elevator i.d. signs throughout all fls. in both wings.remedy:provide signage as per local law 16/84.
Feb 22, 2000
Resolve - Non-hazardous
Eork without a permit work noted metal studs and sheet rock partition erected in 5 story north west section b rm 505 for installed bathrm also metal studs and sheet rock partition erected in 3 sty south east s
Aug 9, 1999 · Penalty $500
Resolve - Non-hazardous
Work without a permit work noted 6 sty north west section rms b03 converted to bathrm metal stud an dsheetrock walls erected in b07 for bathrm stop all work remedy obtian a permit or restore to prior legal cond
Aug 2, 1999 · Penalty $500
Resolve - Non-hazardous
Failure to provide acess to sro room on all floors at time of inspect-ion to determine ompliance with approved which indiccated no lavatoresconstructed in rooms.only rooms 16,+ 18/20 with lav approval.location:
Sep 16, 1996
Resolve - Non-hazardous
Work without a permit work noted bathrooms installed in the following 1sty rooms 120 118 116 117 119 123 remedy: obtain a permit or restore to prior legal condition: stop all work.
Apr 25, 1996 · Penalty $350
Resolve - Non-hazardous
Work without a permit work noted complete bathrooms installed in 7sty room 715,6sty room 615,5sty room 519 rooms 619 and 623 combined.room 621 elivn ivated room 521 eliminated.remedy obtain permit and restore t
Feb 5, 1996 · Penalty $350
Resolve - Non-hazardous
Failure to provide approved plans at premises at time of inspection. location:rooms 319,615,619 and 715.remedy:provide approved plans.
Jan 26, 1996
Resolve - Non-hazardous
Work without a permit.expired permit.work noted:interior removation from first thru-out 8flr.permit#100849352.issued 08-19-94 and expired.location:hall ways.remedy:renew permit.
Jan 26, 1996
Resolve - Non-hazardous
Failure to provide approved plans at premises at time of inspection noted construction work on the 8th,5th,3rd&2nd floors.remedy provide approved plans.
Jun 7, 1995 · Penalty $250
Resolve - Non-hazardous
Work does not conform to approved plans: non-conforming work noted: under act#2 100849352 interior renovation of #18 line floors 1 thru 8 interior demolished and new windos installed, new sheet rock ceiling--
Dec 14, 1994 · Penalty $250
Resolve - Non-hazardous
46l
Oct 24, 1991 · Penalty $185
Resolve - Non-hazardous
46l
Jan 29, 1991
Resolve
Complaints
- Unsanitary condition
Sewage
Oct 13, 2026 · Apt 322
Close - Flooring/stairs
Floor
Oct 13, 2026 · Apt 322
Close - Electric
Outlet/switch
Oct 10, 2026 · Apt 322
Close - Electric
Lighting
Oct 10, 2026 · Apt 322
Close - Water leak
Heavy flow
Oct 9, 2026 · Apt 322
Close - Heat/hot water
Entire building
Feb 9, 2026 · Apt BLDG
Close - Heat/hot water
Entire building
Oct 23, 2023 · Apt BLDG
Close - Heat/hot water
Apartment only
Oct 19, 2023 · Apt 102NIG
Close - Heat/hot water
Apartment only
Oct 16, 2023 · Apt 102
Close - Heat/hot water
Entire building
Mar 4, 2016 · Apt 713
Close
Show 18 more ↓
- Heat/hot water
Entire building
Feb 18, 2016 · Apt 417
Close - Heat/hot water
Entire building
Feb 17, 2016 · Apt BLDG
Close - Heat/hot water
Entire building
Feb 15, 2016 · Apt BLDG
Close - Heat/hot water
Entire building
Feb 14, 2016 · Apt 815
Close - Heat/hot water
Entire building
Feb 13, 2016 · Apt 407
Close - Heat/hot water
Entire building
Oct 17, 2015 · Apt 613
Close - General
Windows
Jan 10, 2014 · Apt 322
Close - General
Windows
Jan 10, 2014 · Apt 322
Close - Heating
Heat related
Dec 10, 2012 · Apt 1FL
Close - Heating
Heat related
Nov 28, 2012 · Apt BLDG
Close - Nonconst
Vermin
Sep 11, 2012 · Apt 204
Close - Heating
Heat related
Sep 7, 2009 · Apt 102
Close - Heating
Heat related
Oct 13, 2006 · Apt 422
Close - Heating
Heat related
Oct 17, 2004 · Apt 422
Close - Plumbing
Basin/sink
May 4, 2004 · Apt 106
Close - Plumbing
Basin/sink
Apr 30, 2004 · Apt 106
Close - Heating
Heat related
Jan 15, 2004 · Apt 417
Close - Heating
Heat related
May 6, 2003 · Apt 422
Close
Sales history
No recorded sales in our data
Building details
- Building type
- Hotel (HH)
- Year built
- 1910
- Floors
- 8
- Residential units
- —
- Building area
- 48,327 ft²
- Lot area
- 7,553 ft²
- Zoning
- R8
- Community board
- 107
- Council district
- 6
- Block / lot
- 1249 / 54
- Assessed value
- $11,089,800
- Landmark / historic district
- Riverside-West End Historic District
HPD registration #103360, last renewed Jun 23, 2026.
Questions about 350 West 88 Street
Who owns 350 West 88 Street?
The owner of record in NYC Department of City Planning PLUTO data is 350 Realty Co.
Does 350 West 88 Street have violations?
Yes. NYC HPD has recorded 15 housing violations at this property.
Is 350 West 88 Street rent stabilized?
NYC Department of Finance tax bills listed 29 rent-stabilized units here in 2024. To confirm a specific apartment, request its rent history from NYS Homes and Community Renewal.
When was 350 West 88 Street built?
City records list 1910 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.