Violations at 58 Summit Street
Staten Island, NY 10307 · BBL 5-07898-0001 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
10 DOB violations, newest first.
- Low pressure boiler boiler required
Lblvio-low pressure boiler boiler required
Dec 31, 2009
Dob violation - dismissed - Low pressure boiler boiler required
Lblvio-low pressure boiler boiler required
Dec 31, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed
ECB violations
The newest 50 of 94 ECB violations. The city keeps the complete history.
- Class - 2
Failure to maintain building in code-compliant manner.noted:in room#7(upper level)the roof above is leaking when rain falls.damage to walls and ceiling at the corner of the room against the outside wall.rem:rep
Apr 21, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code compliant manner.noted:there is alook in the roof area above the exit doors at exit#6 which is damagingthe walls and ceiling from water damage.rem:repair/replace fix leak,re
Apr 21, 2026 · Penalty $1,250
Active - Class - 2
Reissue#35691954y failure to maintain building in code-compliant manner.noted:there is very obvious water damage on walls and ceiling in thelibrary.mostly the upper section of the wall near the exit sign.rem:re
Apr 21, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code compliant manner.noted:there are 2 exhaust fans mounted on the roof that are not working.these 2 exhaust fans provide the ventilation for the bathrooms on the 2nd and 3rd fl
Apr 21, 2026 · Penalty $1,250
Active - Class - 2
Reissue#35691955x failure to maintain building in code-compliant manner.noted:the doors at rm#109 need to do replaced.very old and beyond repair.cracked,split,broken to the extent they cannot be used.don't open
Apr 21, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: there were several emergency lights scattered through the buildi
Apr 9, 2025 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: there were several emergency lights scattered through the school
Apr 9, 2025 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner. noted: the doors at rm #109 need to be replaced. they are very old and beyond repair.normal operation is impossible, can't open or close. remedy: repair/re
Apr 9, 2025 · Penalty $1,250
Active - Class - 2
Re-issue #35674606n. failure to maintain building in code-compliant manner. noted: water damage is very obvious in the library. mostly the upper wall near exit sign gets worse with each rains. remedy: repair/re
Apr 9, 2025 · Penalty $3,125
Active - Class - 2
Re-issue #35674605l. failure to maintain building in code-compliant manner. noted: outside exit #3, the courtyard fence bottom has concrete coping that is cracked, chipped and damaged at the fence post bottoms.
Apr 9, 2025 · Penalty $3,125
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted:in the library,rm#4,there is water damage at the upper wall(left of exit sign)with each rain the damage gets worse.source of this leak needs to be foa
Mar 26, 2024 · Penalty $625
Active - Class - 2
Failure to maintain building in code compliant manner.note:at the courtyard outside exit 3 the concrete coping at fence bottom cracked,broken and missing sections.the charm link fence is not tied to the bottom
Mar 26, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner.noted at the courtyard outside exit 3 the chainlink fence is loose at the bottom on the summit street side.the fencing needs to be re-tied to the posts to p
Feb 27, 2023 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner.reissue#35560820z.no fire stopping per bc712.3;27-345.observed at toi the electric meter room has pipe penetrations through the walls in need of fire stoppi
Feb 24, 2022 · Penalty $3,125
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: no fire stopping per bc 712.3;27-345. note at cellar level in electrical room no fire stopping around pipes penetrating thru the walls. remedy: provide & maint
Feb 23, 2021 · Penalty $3,125
Resolve - Class - 2
Reissue#35500918m failure to maintain bldg walls or appurtenance. noteexterior fire escape metal stair are not covered w/roof or canopy as per code 27-376c. remedy: maintain bldg exterior provide roof.
Feb 23, 2021 · Penalty $3,125
Resolve - Class - 2
Failure to maintain building in code and complaint manner. noted cafeteria ceiling water pentration visible repair and or replace
Jun 26, 2020 · Penalty $625
Resolve - Class - 2
Exit door not self closing noted gym exit door not self close repair and or replace
Jun 26, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain building wall (s) or appuretannces re issu ecb #35448042l noted at exit 10 and other exterior steel stair sets one not covered with roof or canopy and are exposed to the elements both steel
Jun 26, 2020 · Penalty $3,125
Resolve - Class - 2
Reissue#35341945m issued 7/30/18;failure to maintain building wall(s)or appurtenances at exit 10,3rd floor steel stair five escape are not covered with canopy or roof at 2nd location steel stair fire escape are
Sep 11, 2019
Resolve - Class - 2
Reissued#35241946y issued 07/30/2018 exit door not self closing,3 story building several doors throughout the building does not close property or operating in class rooms,and corridors.rem:repair/replace door.
Sep 11, 2019
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. noted: the exit corridor door coming from auditorium & leading to the exit passageway just outside classroom#2(annex),swings the wrong way. rem:repair/replace/
Jul 30, 2018
Resolve - Class - 2
Exit door not self closing. noted: several doors throughout facility not operating correctly &/or not operating @ all. including several classroom doors & namely exterior exit#10 leading to steel exterior stair
Jul 30, 2018
Resolve - Class - 2
Reissue# 35216972p. failure to maintain bldg wall(s) or appurtenances. 2 exterior steel stair sets are not covered w/ roof or canopy. exposed to elements. rem: maintain bldg appurtenances/provide roof.
Jul 30, 2018
Resolve - Class - 2
Exit door not self-closing. noted: at bulkhead staircase (a) and at 3rd floor, room 306 and at old bldg rm 30, the doors have defective in the hinges, closer and frames. rmdy:comply w/code/repair the doors.
Oct 31, 2016
Resolve - Class - 2
Reissue #35085996m failure to maintain building in code compliant manner. noted: cracked spalling plaster walls and ceiling at the following locations. at bulkhead staircase a and b, at 2nd floor, library room
Oct 31, 2016
Resolve - Class - 2
Reissue #35127718p failure to maintain building wall(s) or appurten ances. noted: there are two exterior stairs made of steel that are not covered and are exposed to the elements. rmdy: comply with code.
Oct 31, 2016
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner: no fire stopping per bc 712.3; 27-345. noted: at basement level, electric room, missing fire stopping on walls. rmdy: comply with code/provide fire stopping.
Oct 31, 2016
Resolve - Class - 2
Failure to maintain building wall(s) or appurtenances exterior steel stairs. there are 2 exterior stairs made of steel that are not covered and are exposed to the elements. rmdy: comply with nov.
Mar 30, 2015
Resolve - Class - 2
Failure to maintain bldg wall(s) & appurtenances: exterior. -facade leaks allowing water penetration into classrooms. -cracked bricks & loose mortar throughout exterior of bldg in various areas. remedy: repair
Mar 10, 2014
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner: interior. in old bldg, rooms 3,4 & 7 -spalling & cracked walls & ceiling from water penetration. remedy: repair walls & ceiling.
Mar 10, 2014
Resolve - Class - 2
Failure to maintain bldg wall(s) & appurtenances: exterior. small roof above auditorium leaks allowing water penetration onto auditorium ceiling. remedy: repair roof.
Mar 10, 2014
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner: interior. -1st fl auditorium, spalling & cracked ceiling & walls. -2nd fl library & mdf room, spalling & cracked ceiling & walls. -stairway a, cracked & spalli
Mar 10, 2014
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner: interior. at basement, kitchen area room b 109 -hole in ceiling by ceiling light, kitchen storage room -holes in ceiling. remedy: repair holes.
Mar 10, 2014
Resolve - Class - 2
Re-issue # 34798849x,35023069h. failure to maintain bldg: exterior. no roof protection for fire escape stairs. 27-376(c). remedy: provide roof for fire escape stairs.
Mar 10, 2014
Resolve - Class - 2
Re-issue # 34927406p. failure to maintain bldg: interior. throughout bldg in various classrooms, cracked & spalling walls & ceilings due to water penetration from exterior. remedy: repair walls & ceilings.
Mar 10, 2014
Resolve - Class - 2
Re-issue # 34995679p. failure to maintain bldg: exterior. water penetrating from facade of bldg throughout bldg. remedy: repair facade.
Mar 10, 2014
Resolve - Class - 2
Standing water observed at various location throughout basement. remedy: maintain bldg.
Jun 12, 2013
Resolve - Class - 2
Sec. 27-376(c). reissue 34995681y no roof provided over exterior metalexit stairs. remedy: provide roof.
Jun 12, 2013
Resolve - Class - 2
At rear aisle of auditorium - partial construction to rear exits due to free standing artwork in aisle. remedy: remove obstruction - keep egress aisles clear.
Jun 12, 2013
Resolve - Class - 2
Reissue 34995679p. water penetration through exterior walls at variouslocations throughout bldg. remedy: maintain bldg.
Jun 12, 2013
Resolve - Class - 2
Reissue 34995680m cracked, spalling plaster walls and ceilings. in various rooms throughout bldg. remedy: maintain bldg
Jun 12, 2013
Resolve - Class - 2
Sec. 27-371(b). reissue 34995682x. plexi-vision panels installed on f.p.s.c. doors throughout bldg. remedy: use code compliant hardware.
Jun 12, 2013
Resolve - Class - 2
Sec. 27-371(b). plexi-vision panels installed on doors throughout bldg. remedy: provide required glass panels.
Jun 19, 2012
Resolve - Class - 2
Sec. 27-361(c). reissue 34927407r. no roof provided over exterior exitstair as required by 27-376(c). remedy: provide roof over stair.
Jun 19, 2012
Resolve - Class - 2
Reissue 34927406p. cracked spalling plaster walls and ceilings in various rooms throughout bldg. remedy: repair walls & ceilings.
Jun 19, 2012
Resolve - Class - 2
Water penetrating through exterior walls at various locations through out bldg. remedy: provide water proofing to exterior walls.
Jun 19, 2012
Resolve - Class - 2
27-376c failure to maintain no roof provided over two exterior fire stairs as required by 27-376 reissue 34798849x 34847521k rem: maintain bldg
Oct 12, 2011
Resolve - Class - 3
Failure to maintain observed spalling cracked plaster on exterior wall rms 101 103 209
Oct 12, 2011
Resolve - Class - 2
Roof ridge (parallel to summit st) of 1878 bldg presents 2 points of deflection (visible from st) remedy: provide engineers report & recommendations as to the conidtion of roof ridge
Jun 17, 2010
Resolve