roofy

100 Luten Avenue

Staten Island, NY 10309BBL 5-06613-0001Map

Owner of record: NYC Department Of Education

100 Luten Avenue is a school building built in 1972 in Staten Island, 10309. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
63
ECB violations
103
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 63

  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - active
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 3, 2018

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 3, 2018

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - active
Show 40 more ↓
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 11, 2017

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 11, 2017

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 28, 2016

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 31, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 31, 2014

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 1, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 1, 2013

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2011 inspection/test

    Oct 1, 2012

    Dob violation - active
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2010 cat 1 insp/tst

    Aug 15, 2012

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 22, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 22, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 22, 2012

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 22, 2012

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 27, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 27, 2011

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Vcat1-elevator annual inspection / test elevatorrequired

    Oct 8, 2010

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 2, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 16, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 11, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 11, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 27, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 27, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 27, 2005

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 27, 2005

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 9, 2004

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 9, 2004

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 21, 2003

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 22, 1997

    Vp*-violation unserved ecb- dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 22, 1997

    Vp*-violation unserved ecb- dismissed

ECB violations · 103

  • Class - 2

    Reissue#35691916n exit door not self closing.noted:there were several exit doors scattered through the school that were not operating/closing properly.rem:repair/replace self closing exit doors.

    Apr 9, 2026 · Penalty $1,562

    Active
  • Class - 2

    Failure to maintain building in code compliant manner.noted:the parking lot at exposure 3 is riddled with pot holes,cracks,missing asphalt and uneven surfaces.also affects the loading dock.rem:repair/replace.

    Apr 9, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissue#35691917p failure to maintain building in code compliant manner.noted:the ongoing problem remains the same at te contrally located courtyard.pavement is cracked,broken up,falling apart and uneven which

    Apr 9, 2026 · Penalty $3,125

    Active
  • Class - 2

    Re-issue #35674602x. exit door not self-closing. noted: at t. o. i. there were several exit door scattered throughout the school that self-closing and/or not operating properly. remedy: repair/replace doors.

    Mar 25, 2025 · Penalty $1,562

    Active
  • Class - 2

    Re-issue #35674603h. failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors perbc 1006.1; 27-381. noted: at t. o. i. there were several emergency lig

    Mar 25, 2025 · Penalty $3,125

    Active
  • Class - 2

    Re-issue #35674601y. failure to maintain building in code-compliant manner. noted: the centrally located courtyard remains for years in verybad condition. its cracked, broken, uneven, and falling apart. this is

    Mar 25, 2025 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code compliant manner:illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:several emergency lights were not operational when tested at t.o.i.rem

    Mar 22, 2024 · Penalty $625

    Active
  • Class - 2

    Reissue#35665347n failure to maintain building in code compliant manner.the courtyard at central area of facility has major cracks and uneven surfaces and broken creating unsafe tripping and falling hazard.rem:

    Mar 22, 2024 · Penalty $1,562

    Active
  • Class - 2

    Reissue#35665348p exit doors not self closing.several exit doors scattered through the building are not operating and/or self closing properly.rem:repair/replace all faculty doors.

    Mar 22, 2024 · Penalty $1,562

    Active
  • Class - 2

    Re-issue#35636523k failure to maintain in code compliant manner.noted:the ongoing problem concerting the surface of the courtyard continues the asphalt and concrete surfaces are cracled and uneven,not level tha

    Feb 6, 2023 · Penalty $1,562

    Active
Show 40 more ↓
  • Class - 2

    Re-issue#35636524m exit doors not self-closing.noted:at several locations throughout the entire school approx.17 doors in total especially at exit 7 and exit 9.rem:repair/replace doors and hardware.

    Feb 6, 2023 · Penalty $1,562

    Active
  • Class - 2

    Failure to maintain building in code compliant manner:illumination for exits,out discharges and public corridors per bc 1006.1;27-381.observed at t.o.i.there were several emergency lights throughout the facilit

    Feb 17, 2022 · Penalty $625

    Resolve
  • Class - 2

    Re-issue 35555830x failure to maintain building in code compliant manner.observed at t.o.i.there is water penetration at the basement level in the o-1 tank rm.water enters and ponds whenever it rains.rem:repair

    Feb 17, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Re-issue#35555829z failure to maintain building in code compliant manner observed at t.o.i. the surface of the court yard at center front building is in serious disrepair.the concrete and asphalt surfaces are c

    Feb 17, 2022 · Penalty $1,562

    Active
  • Class - 2

    Re-issue#35555828r exit doors not self-closing observed at t.o.i.thereare several doors through-out the entire facility that do not self-close.approximately 17 doors,notably at exits 9 and 7.rem:repair/replace.

    Feb 17, 2022 · Penalty $1,562

    Active
  • Class - 2

    Reissue35502129z failure to maintain bldg walls&appurtenances note@front courtyd concrete&asphalt deteriorated in several areas causing tripping hazards.also sidewalks thruout entire school area in disrepair wh

    Apr 15, 2021 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain bldg in codecompliant manner note in cafeteriaa gas stove not hardpipe to supply.gasline is blue flex pipe.repair &/or replace.

    Apr 15, 2021 · Penalty $625

    Resolve
  • Class - 2

    Reissue35502130x exit door not selfclosing note exit doors9&7&staricasea&total of 17doors not selfclosing.repair &/or replace doors.

    Apr 15, 2021 · Penalty $1,562

    Active
  • Class - 2

    Emergency signs@elevator call station missing defective or noncompliant w/sec requirements note@elevatora 2&3fl emergency signs missing.install signs.

    Apr 15, 2021 · Penalty $625

    Resolve
  • Class - 2

    Reissue35502128r failure to maintain bldg in codecompliant manner note@bsmt level in oilrm water penetration thru fl causing puddling on fl water about3" on fl.repair &/or replace.

    Apr 15, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue ecb #35442549n failure to maintain building wall (s) or appurtenances noted at front court yard concreted asphalt are detriorated and cracks in several area tripping hazards is sidewalk in various locat

    Jun 30, 2020 · Penalty $3,125

    Active
  • Class - 2

    Reissue ecb #35448025j failure to maintain building in code compliant manner noted ta oil tank room in cellar level leak at foundation wall allowed water in to floor at oil tank room repair and or replace

    Jun 30, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue ecb #35442548k exit door not self closing noted exit #9 and 7 facing athlete field not close properly also by stair case (a) exit door not self close exit (17) door is not self closed repair and or rep

    Jun 30, 2020 · Penalty $1,562

    Active
  • Class - 2

    Exit door not self closing.at time of inspection and observed at exit #9 & 7 facing athlete fields not close property due to sadle uplifts and hinges several(7)reissued (#35341943z)issued on 7/27/2018)rem:repai

    Aug 26, 2019

    Active
  • Class - 2

    Failure to maintain building in code compliant manner.at the time of inspection and observed at oil tank room in cellar level leak at foundation wall allowed water into floor @ oil tank room.(reissue #35341941

    Aug 26, 2019

    Resolve
  • Class - 2

    Failure to maintain building wall or appurtenances.at the time of inspection and observed at front court-yard concreted asphalt are deteriorated and cracks in several area tripping hazards in sidewalks in vario

    Aug 26, 2019

    Active
  • Class - 2

    Failure to maintain. reissue# 35270614m, leak @ foundation/slab allowing water into oil tank room. rem: repair/replace.

    Jul 27, 2018

    Resolve
  • Class - 2

    Exit door not self closing. note: several doors throughout entire facility. not operating correctly or not operating at all. noteably @ exit# 9 & 7. rem: repair/replace door.

    Jul 27, 2018

    Active
  • Class - 2

    Reissue# 35270611r. failure to maintain bldg walls or appurtenances.failure to maintain bldg wall(s) or appurtenances. asphalt @ parking lot & courtyard area has cracks @ various locations causing tripping haza

    Jul 27, 2018

    Active
  • Class - 2

    Failure to maintain bldg. note: there is water ponding on the gym floor @ the corner located by the exit#7 to exterior. the water comes from a roof leak above that same area. rem: replace/repair/fix leak.

    Jul 27, 2018

    Resolve
  • Class - 2

    Exit door not self closing. noted: exit#4 all 4 door are defective dont self closing. remedy: repair/replace door.

    Jun 20, 2017

    Resolve
  • Class - 2

    Reissued#35216450h failure to maintain bldg walls or appurtenances. noted: asphalt parking in courtyard area has cracks at various locations creating hazards(tripping). remedy: maintain asphalt parking/make nec

    Jun 20, 2017

    Active
  • Class - 2

    Failure to maintain bldg in code compliant manner: lack of emergency lighting for exits,exits discharges & public corridors per bc 1006.1;27-542. observed 2 lights at gym ab,2 lights at gym d,& 2 lights at audi

    Jun 20, 2017

    Resolve
  • Class - 2

    Reissue#35216451j failure to maintain bldg in code complaint manner. noted: ceiling leak at exit 15 ground level,gym & cafeteria hallway,due to roof drain leak. remedy: repair &/or replace.

    Jun 20, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at oil tank room leak at foundation wall,or summint at floor. remedy: repair leak/comply w/commioner order.

    Jun 20, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner. noted: ceiling leakat exit 15 at ground level, gym area and cafeteria hallway due to roofdrain leak.

    Oct 28, 2016

    Resolve
  • Class - 2

    Reissue #35094460z failure to maintain building wall(s) or appurten ances. noted: asphalt paving in courtyard area has cracks at various locations creating tripping hazard. rmdy: make necessary repairs.

    Oct 28, 2016

    Active
  • Class - 2

    Reissue #35094462m failure to maintain in code-compliant manner. noted: no fire protection pass through opening between kitchen and cafeteria missing. rmdy: provide fire protection.

    Oct 28, 2016

    Resolve
  • Class - 2

    Re-issue # 34995996z. cross corridor doors. 4 cross corridor doors near room a305 completely removed & missing. remedy: install cross corridor doors.

    May 2, 2014

    Resolve
  • Class - 2

    Re-issue # 34995995r. court yard. asphalt in court yard uneven & pitted in various areas. area of flagpole has broken & deteriorating concrete. remedy: repair areas of court yard & flagpole area.

    May 2, 2014

    Active
  • Class - 2

    Re-issue # 34798808j. no fire protection. pass through opening between kitchen & cafeteria missing. remedy: provide fire protection.

    May 2, 2014

    Resolve
  • Class - 2

    Reissue: 34995996z four cross corridor doors missing near room a305.rmdy: maintain building.

    Jul 2, 2013

    Resolve
  • Class - 2

    Reissue: 34995995r asphalt paving in courtyard severely uneven, pitted, causing trip hazrds. rmdy: maintain building.

    Jul 2, 2013

    Active
  • Class - 2

    Reissue 34870930r. at cellar (d-wing) d-tunnel approx 3" of standing water. remedy: repair defects remove water.

    Jul 3, 2012

    Resolve
  • Class - 2

    Door racked preventing them from closing properly at stage right side,3rd flr corridor adjacent to rm 305 and are corridor door missing adjacent to rm 305. remedy: repair/replace doors.

    Jul 3, 2012

    Resolve
  • Class - 2

    Asphault paving in courtyard has cracks & is heaving in various locations causing several tripping hazards. remedy: repair/replace paving.

    Jul 3, 2012

    Active
  • Class - 2

    Failure to maintain. observed: water penetration into boys & girls gymfrom roof into folding divider closets standing water observed in closets, spreading onto gym flrs. also water entering fan room from roof

    Oct 14, 2011

    Resolve
  • Class - 2

    Failure to maintain. observed: no protection at pass through window from kitchen to pa cafeteria from fire. reissue 34870927x. remedy: provide protection.

    Oct 14, 2011

    Resolve
  • Class - 2

    Work w/o permit:@ auditorium above stage left 2 stage right, repaired removed/replaced (2)cinderblock in-fill walls(approx. 24ft long by8ft high) location currently under vacate #19/11 due to a total failure &

    May 20, 2011

    Resolve
  • Class - 1

    Failure to maintain bldg in code-compliant manner. noted: at the time of my inspection i observed at the roof area 2 block walls have collapsed the larger wall approx 10'- 12' high was the interior wall had

    Apr 6, 2011

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1972
Floors
4
Residential units
—
Building area
411,000 ft²
Lot area
807,545 ft²
Zoning
R3X
Community board
503
Council district
51
Block / lot
6613 / 1
Assessed value
$55,157,400
Landmark / historic district
No

Questions about 100 Luten Avenue

Who owns 100 Luten Avenue?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 100 Luten Avenue have violations?

NYC HPD has no housing violations on record for this property.

Is 100 Luten Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 100 Luten Avenue built?

City records list 1972 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.