Violations at 194 Jefferson Boulevard
Staten Island, NY 10312 · BBL 5-06262-0012 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
33 DOB violations, newest first.
- Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2015 inspection report
Feb 24, 2017
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2015 inspection report
Feb 24, 2017
Dob violation - dismissed - Low pressure boiler boiler required
Lblvio-low pressure boiler boiler required
Dec 31, 2009
Dob violation - dismissed - Low pressure boiler boiler required
Lblvio-low pressure boiler boiler required
Dec 31, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Construction other optional
C-construction other optional
Mar 12, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed
ECB violations
The newest 50 of 67 ECB violations. The city keeps the complete history.
- Class - 2
Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors-per bc 1006.1; 27-381. noted: there were several emergency lights, scattered around the school
Mar 25, 2025 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code compliant manner.illumination forexits,exit discharges and public corridors per bc1006.1;27-381.noted at time of inspection,the emergency lights in the gym were not operatio
Jan 25, 2023 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in codecompliant manner.observed@toi pavement/slab outside&near exita&b needs to be corrected.its sinking&backpitched toward bldg that may be causing some of the leaking of water into b
Feb 16, 2022 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in codecompliant manner.observed@toi entry stairs@exit1&3 in need of serious repair.treads are sinking&out of level.mortar joints open in need of repointing.delay will equal further dam
Feb 16, 2022 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in codecompliant manner.observed@toi bsmt level has water penetration@several locations.most concerning is electricmeterrm&gasmeterrm are included.w/moderate to heavy rain,water will po
Feb 16, 2022 · Penalty $625
Resolve - Class - 2
Reissue ecb #35452241x failure to maintain building in code compliant manner note: at 1st floor exit #4 stairway (c) &(d) exit door left side is rusted and loose at bottom repair and replace
Jul 2, 2020 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building in code complaint manner use of prohibited door and or hardware per bc 1008.1.8;27-371(j) note the following doors hav eillegal kids stops :242,219,218,217,200,203,204,209,210,211,2
Sep 3, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner note at 1st floor exit #4 stairway c&d eixt door left side jam is rusted and loose at bottom repair and or replace
Sep 3, 2019
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. noted: foundation wall has become porous, allowing the rainwater into boiler room along side jefferson blvd and ionia avenue.rmdy: waterproof the foundation
Oct 27, 2016
Resolve - Class - 2
Failure to maintain bldg wall(s) or appurtenances.noted: first floor at exit 2, spalling plaser at ceiling due to roof leak. rmdy: make necessary repairs.
Oct 27, 2016
Resolve - Class - 2
Spalling plaster. at room 217, library plaster wall at rear of room spalling & deteriorating next to heaters. remedy: repair wall.
Apr 23, 2014
Resolve - Class - 2
Failure to maintain bldg wall(s)or appurtenances.@ exit 1,outside stairs,left side,grab bar missing.rem:replace grab bar.
Mar 5, 2014
Resolve - Class - 2
Failure to maintain bldg in code compliant manner.interior @ boiler room,concrete wall spalling & cracked.rem:repair concrete wall
Mar 5, 2014
Resolve - Class - 3
Re issue ecb #34987874k failure to maintain bldg pipe from roof drain leaking into boiler room.rem:repair/replace pipe.
Mar 5, 2014
Resolve - Class - 2
Re-issue ecb 35023151r failure to maintain bldg.@ first fl.exit 384,doors do no close properly.rem:repair doors.
Mar 5, 2014
Resolve - Class - 2
Reissue 34987298l. at first flr exit 3/4 defective, won't properly close. remedy: maintain bldg.
Jun 13, 2013
Resolve - Class - 3
Reissue 34987299n. damaged plaster walls & ceiling @ bulkhead, stair c. remedy: maintain bldg.
Jun 13, 2013
Resolve - Class - 3
Reissue 34987874k. roof drain pipe leaking into boiler room in area ofoil tank room. remedy: maintain bldg.
Jun 13, 2013
Resolve - Class - 2
At 2nd flr, stair c, door closer defective, door won't self-close. remedy: maintain bldg.
Jun 13, 2013
Resolve - Class - 2
Sec. 27-766. reissue 34986704n. no fresh air vent in gas meter room. remedy: provide ventilation.
Jun 13, 2013
Resolve - Class - 3
Pipe from roof drain leaking in boiler room. remedy: repair/replace pipe.
Aug 10, 2012
Resolve - Class - 3
Damaged plaster walls & ceiling at bulkhead of stair c. remedy: repairdamaged plaster.
Aug 10, 2012
Resolve - Class - 2
Door at exit 1 from auditorium is racked preventing it from closing properly. remedy: repair/replace door.
Aug 10, 2012
Resolve - Class - 2
Reissue 34927400y failure to maintain no fresh air vent in gas meter rm rem: provide ventilation
Jun 27, 2012
Resolve - Class - 2
Failure to maintain no fresh air ventilation gas meter room rem: provide ventilation
Oct 6, 2011
Resolve - Class - 3
Failure to maintain lower window sashes wont remain open rms 127 & 259rem: maintain bldg
Oct 6, 2011
Resolve - Class - 2
R844 @ boiler room,northwest corner,concrete foundation wall has delaminated ~ 20. remedy:repair foundation wall.___________________________
Aug 3, 2010
Resolve - Class - 2
R-844 @ bulkhead, roof leak. remedy: waterproof leaking bulkhead.
Aug 3, 2010
Resolve - Class - 2
(r-036) re-issue from 34793214j,07/14/2009.defects in parapet wall:1-@2nd fl roof near main entry.@ least side 40' rfom south wall seam of cap stone has opened 1/1/2" to 2" on all cantelevered parapet section
Jul 27, 2010
Resolve - Class - 2
Cap stone on parapet shifted leaving a 3" gap @ one end. location: ne corner. (drumcoole & jefferson). remedy: reposition/secure & point alljoints.
Jul 14, 2009
Resolve - Class - 2
Re-issue of 34639378k/34607707x by hillen 2277/ by menler 1810. water penetration through wall. location: boiler room - cellar - west & south wall. remedy:make all necessary repairs to prevent water penetration
Jul 14, 2009
Resolve - Class - 2
Fuel & gas appendix e.3.3. storage present in gas meter room & electrical switch room. ie. blueprints, plexiglass, cardboard desk, mini-fridge, file cabinet, milk crates w/files. no firestopping @ sleeve above
Jul 14, 2009
Resolve - Class - 2
300 to 400 sq ft of standing water present in crawl-space. strong odorof mold or mildew. location: crawl-space, through access door, in front of boiler room stairs. source of water not determined. remedy:
Jul 14, 2009
Resolve - Class - 2
Defects in parapet wall. locations & descriptions. 1) on 2nd sty roof near main entrance @ east side 40' from south wall - seam of capsules has opened to 1 1/2" 2) all cantelevered parapet sections. (approx 25)
Jul 14, 2009
Resolve - Hazardous
Failure to maintain - interior 1st flr exit 4 plaster ceiling spallingdue to water penetration through roof/ceiling. remedy: stop water penetration/repair plaster.
Mar 18, 2008
Resolve - Hazardous
Reissue: #34607707x cellar - boiler room west and south wall water penatration through wall reissue #34607708h 1st flr exit 4 - water penatration trough roof/wall in vestibule. remedy: make all necessary repair
Mar 18, 2008
Resolve - Hazardous
Exit door not self closing 1st flr stairway b - exit doors - center jamp(ramp) not attached to flr doors do not close properly. remedy: repair/replace doors.
Mar 18, 2008
Resolve - Hazardous
Failure to maintain - interior there is an "active" leak in a pipe within the boiler room causing a bathroom to be in operable. this leak is over electrical conduit in the boiler room and a hole approx. 2'x 2'
Mar 18, 2008
Resolve - Non-hazardous
Failure to provide/maintain fir stopping where required hole in cinderblock wall in the boiler room was made last year to repair a water leak. the leak is still active and 2'x 2' hole still exist this hole is a
Mar 18, 2008
Resolve - Hazardous
Water penetration through roof into vestibule for exit 4 @ the 1fl.remedy:stop water penetration & make all necessary repairs.
Sep 19, 2007
Resolve - Hazardous
Water penetration through exterior wall into bathroom rm#308,boiler rmwest & south walls.remedy:stop water penetration & make all necessary repairs.
Sep 19, 2007
Resolve - Hazardous
Reissue # 34513429h an active leak within the boiler room is causing abthrm to be inoperable. remedy: maintain/repair leak.
Jul 13, 2007
Resolve - Hazardous
Reissue # 34513428x a hole in cinder block wall in boiler room still exsist after water repair leak still exists & 2'x2' hole remains. remedy: provide & maintain fire stop.
Jul 13, 2007
Resolve - Hazardous
Failure to maintain bldg, in that there is an "active" leak in a pipe within the boiler room causing a bathroom to be inoperable. this leak is over electrical conduit in the boiler room and causing a hole appro
Mar 16, 2006
Resolve - Hazardous
Failure to provide/maintain fire stopping where required. noted: a hole in the cinderblock wall in the boiler room was made last year to repair a water leak. the leak is still active and a 2' x 2' hole still ex
Mar 16, 2006
Resolve - Hazardous
6a 6)rear saftey valve relieves @ 19 psi not 15 psi 95 necessary
Apr 14, 2004
Resolve - Non-hazardous
Failure to maintain. noted: 8 foot section of steel i beam heavily rusted/ deteriorated at south/east (jefferson blvd) side of boiler room. remedy: repair/replace i beam and maintain.
Jan 11, 2002
Resolve - Non-hazardous
Failrue to maintain. noted ; 3 or 4 crank - operated windows in gymnasium not working - broken parts. remedy : repair / maintain windows in gym
Jan 7, 2002
Resolve - Non-hazardous
* re- issue * failrue to maintain. noed : missing / defective mortar joints - loose concrete blocks below window in gymnasium ( interior ) remedy : repairs mortar joints / concrete blocks
Jan 7, 2002
Resolve - Non-hazardous
Failure to maintain. noted ; plaster damaged / deteriorated at corner of ceiling - boys bathroom ( rm. 270 ) remedy : maintain ceilings / plaster
Jan 7, 2002
Resolve