Violations at 54 Osborne Street
Staten Island, NY 10312 · BBL 5-05336-0001 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
33 DOB violations, newest first.
- Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 16, 2021
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 25, 2017
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 23, 2014
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 30, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 17, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 25, 2011
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Vcat1-elevator annual inspection / test elevatorrequired
Oct 8, 2010
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 7, 2009
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 12, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 4, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 20, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 29, 2005
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 21, 2003
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Elevator elevatoroptional
1
Apr 7, 1992
Dob violation - dismissed - Elevator elevatoroptional
1
Jun 29, 1990
Dob violation - dismissed
ECB violations
30 ECB violations, newest first.
- Class - 1
Failure to maintain building in code compliant manner.noted:there are several classrooms and corridors with excessive amounts of combustiblematerials hanging from ceilings and light fixtures.cloths lines and el
Mar 30, 2026 · Penalty $2,500
Resolve - Class - 2
Failure to maintain building in code compliant manner.noted:the concrete slab/exit patio at exit#2 at exposure 2 is cracked,chipped,uneven and deteriorating.the uneven surface causes trip hazard for the heavy s
Mar 30, 2026 · Penalty $1,250
Active - Class - 2
Reissue:35691924n failure to maintain building in code compliant manner.noted:there are several glass panels and/or windows that have created glass and some with holes from what appears to be pellet guns or bb
Mar 30, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner, noted: there are several glass panels and windows that have cracks, some more severe than others. some have holes that appear to be from bb guns or the lik
Mar 26, 2025 · Penalty $1,250
Active - Class - 2
Failure to maintain bldg in code-compliant manner: no fire stopping per bc 712.3; 27-345. noted: at basement level, electric room, missing fire sopping on wall (hole apprx 5" x 24") rmdy: comply with code.
Oct 27, 2016 · Penalty $2,500
Resolve - Class - 2
Failure to maintain building in code-compliant manner. noted: at base ment level, boiler room area, vertical steps cracked masonry in the wall. rmdy: comply with code/repair the crack.
Oct 27, 2016
Resolve - Class - 2
Roll down gates. all roll down gates on 1st floor (3 total) do not have safety stops. remedy: install safety stops for roll down gates.
Apr 29, 2014
Resolve - Class - 2
Re-issue # 34981380n. rotted door jamb. at boiler room exit door, door jamb at bottom rusted & splitting. remedy: replace door jamb.
Apr 29, 2014
Resolve - Class - 2
Reissue 34981380n. door and jamb at boiler room exterior exit rotted @bottom. remedy: maintain bldg.
Jun 17, 2013
Resolve - Class - 1
Hinged grate over exit ladder from boiler room is obstructed by vertical window grate above preventing it from opening. rem: remove obstruction.
Jun 19, 2012
Resolve - Class - 2
Door jamb for boiler rm exit at area way is excessively corroded and base of door jamb is completely deteriorated at both sides rem; replace door jamb
Jun 19, 2012
Resolve - Class - 2
Exit door in boiler rm leading to area way has no exit sign rem: provide exit sign
Jun 19, 2012
Resolve - Class - 2
Support angles for grate over area way from boiler room are excessively corroded at right side angle is separating from wall rem: replace angle supports for grate
Jun 19, 2012
Resolve - Class - 2
Opening in walls of electric rm at pipe penetrations w/ no fire stopping rem: provide fire stopping
Jun 19, 2012
Resolve - Class - 2
Reissue 34871409k. missing fire suppression system at gas stove in kitchen. remedy: install ansul system.
Oct 17, 2011
Resolve - Class - 2
(r-055) at auditorium, stage left, steps; trip hazard present, (christmas style string of lights across stairs).
Aug 4, 2010
Resolve - Class - 2
(r-055) at kitchen, no fire suppression system installed @ gas range. remedy: install "ansul" fire suppression or remove equipment.
Aug 4, 2010
Resolve - Class - 2
(r-055) at ne corner of bldg, outside of basement exit - b -, horizontal, overhead fence member is not supported. remedy: secure overhead horizontal fence's pipe from falling.
Aug 4, 2010
Resolve - Class - 3
(r-055) reissued from 34793247x, issued 07.15.09. 400 sq ft of fabric hung in auditorium (pa = 500561171) w/no flame spread rating. remedy: apply coating to achieve flame-spread rating. or remove.
Aug 4, 2010
Resolve - Class - 3
> 400 ¬ of fabric hung in auditorium ( quilts & banners ) w/o a flame spread rating. remedy: achieve required flame spread rating or remove suspended fabrics
Jul 15, 2009
Resolve - Hazardous
Failure to maintain interior cellar gas meter room no fresh air vent. remedy: furnish and install fresh air vent.
Mar 18, 2008
Resolve - Hazardous
Reissue: 34576631j, failure to maintain - exterior the entire facade all sides mortar joints(detracted) and missing mortar reissue #34576632l the lintels @ all windows throughout building(detracted) & corroded
Mar 18, 2008
Resolve - Hazardous
Reissue 34513426m noted: the lintels @ all windows throughout bldg aredeteriorated & corroded. remedy: maintain/repair defective lintels.
Jul 12, 2007
Resolve - Hazardous
Reissue #34513427y noted: the entire facade all sides mortar joints deterioated & missing mortar. remedy: maintain exterior wall.
Jul 12, 2007
Resolve - Hazardous
Reissue #34465886j, 34282314m, & 342866472. failure to maintain exterior bldg wall, in that "entire" facade c "all" sides, show signs of deteriorated mortar joints. joints at numorus various locations are missi
Mar 16, 2006
Resolve - Hazardous
Failure to maintain exterior, in that the lintels at "all" windows, "all sides" through out bldg show signs of deterioration, being corroded& flaking. remedy: maintain exterior bldg/make all necessary repairs t
Mar 16, 2006
Resolve - Non-hazardous
Reissue #34286647z fail to maintain (ext). on north and east elevation, between 2nd floor and parapet several areas of missing mortar and missing caulking at expansion joints and brick joints. remedy: repair
Jan 5, 2005
Resolve - Non-hazardous
Failure to maintain (interior) at street termination of stairway 3, right side door of double exit doors is binding and does not open (due to recent and cement work). remedy: repair defect.
Jan 5, 2005
Resolve - Non-hazardous
* re - issue * failure to maintain. noted : small areas of missing / defective mortar joints at various parts of exterior wall ( most prominent at top portion of protruding windows ) remedy : maintain brickwork
Jan 7, 2002
Resolve - Non-hazardous
Failure to maintain.defect is:(1)the facade has loose and missing mortor joints the south side facade has some loose bricks.(2)there is no emergency lighting in the stairways (3) the roof counter flashing is
Apr 7, 2000
Resolve