Violations at 300 Wild Avenue
Staten Island, NY 10314 · BBL 5-02647-0013 · Back to the property
HPD housing violations
6 HPD violations, newest first.
- ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Apr 17, 2024
Closed — Violation dismissed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Nov 27, 2023
Closed — Violation dismissed - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Mar 31, 2023
Closed — Violation dismissed - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Mar 10, 2022
Closed — Violation dismissed - ANon-hazardous
File annual bedbug report in accordance with hpd rule as described on the back of this notice of violation or as described on hpds website, www.nyc.gov\hpd, search bed bugs.
Apr 20, 2021
Closed — Violation dismissed - IInformation / order
And is therefore subject to civil penalties, prohibited from certifying violations, and denied the right to recover possession of premises for nonpayment of rent until a valid registration statement is filed.
Dec 11, 2017
Closed — Violation dismissed
DOB building violations
18 DOB violations, newest first.
- Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
May 2, 2024
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Feb 22, 2024
Dob violation - dismissed - Failure to post energy grade/score none
Failure to display energy efficiency score and energy efficiency grade as per adcode sec. 28-309.12.3
Dec 1, 2023
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Nov 2, 2023
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Aug 2, 2023
Dob violation - dismissed - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
May 2, 2023
Dob violation - dismissed - Failure to post energy grade/score none
Failure to display energy efficiency score and energy efficiency grade as per adcode sec. 28-309.12.3
Dec 1, 2021
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 6, 2021
Dob violation - resolved - Failure to benchmark none
Failure to file benchmarking report of energy use as per ad. code sec. 28-309.4
Jun 2, 2021
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 5, 2020
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2016 inspection/test
Sep 15, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 18, 2014
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 5, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 21, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 21, 2012
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 13, 2010
Dob violation - resolved
ECB violations
22 ECB violations, newest first.
- Class - 2
Replace or secure gibs where needed (2.11.11.5.7.)> maintnenance log not up to date (8.6.1.4.). oil and water mixture in pit (2.2.2.4.). cab handrail missing.
Aug 25, 2026 · Penalty $625
Active - Class - 2
Failure to comply with the commissioner's order to file a certificate of correction with the department of buildings. no certificate of correction on file for vio#39122119x as of 4/13/2026., file a certificate
Apr 13, 2026 · Penalty $6,250
Active - Class - 2
Failure to comply with the commissioner's order to file a certificate of correction with the department of buildings. no certificate of correction on file for vio#39122120n as of 4/13/2026., file a certificate
Apr 13, 2026 · Penalty $6,250
Active - Class - 2
Failure to comply with the commissioner's order to file a certificate of correction with the department of buildings. no certificate of correction on file for vio#39122117m as of 4/13/2026., file a certificate
Apr 13, 2026 · Penalty $6,250
Active - Class - 2
Failure to comply with the commissioner's order to file a certificate of correction with the department of buildings. no certificate of correction on file for vio#39122098x as of 4/13/2026., file a certificate
Apr 13, 2026 · Penalty $6,250
Active - Class - 1
Unlawful acts. failure to comply with commissioner's order. for work without a permit for vio#39143435k no permit on file as of 4/13/2026., comply with commissioner's order
Apr 13, 2026 · Penalty $12,500
Active - Class - 2
Work does not conform to approved construction documents and/or approved amendments. at time of inspection, observed the 5th floor do not conform to nb job app #500842109. noted 19 additional guest rooms on the
May 22, 2025 · Penalty $1,280
Active - Class - 2
No certificate of correction on file for class 1 electrical violation 39122120n issued for unpermitted wiring devices, circuit breakers installed to various receptacles without permits. conditions repaired unde
Apr 1, 2025 · Penalty $1,250
Active - Class - 2
No certificate of correction on file for class 1 electrical violation 39122119x issued for unapproved use of electrical equipment. conditions have been fixed under approved job #s01115437, file a certificate of
Apr 1, 2025 · Penalty $1,250
Active - Class - 1
Work without a permit; violation #39122117m issued for flex gas line installed to supply gas to hvac system on roof. flex line has since been removed and replaced with appropriate gas lines. no permits on file
Apr 1, 2025 · Penalty $2,500
Active - Class - 2
No certificate of correction on file for class 1 electrical violation 39122115z issued for electrical wiring not installed as per code. wiring has been fixed under approved job #s01115437., file a certificate o
Apr 1, 2025 · Penalty $1,250
Active - Class - 2
No certificate of correction on file for class 1 violation 39122098x issued for missing fire stopping throughout public corridors. summons found in vio, civil penalty unpaid., file a certificate of correction
Apr 1, 2025 · Penalty $1,250
Active - Class - 2
No certificate of correction on file for class 1 violation 39122117m issued for gas connection to hvac system not installed as per code. gas connection has been fixed without permit., file a certificate of corr
Apr 1, 2025 · Penalty $1,250
Active - Class - 2
Observed painted sprinkler caps as well as 2 sprinkler heads with paint on them. as per 102.3 maintenance. installations, both existing and new, and parts thereof shall be maintained in proper operating conditi
Sep 6, 2024 · Penalty $310
Resolve - Class - 2
Observed gas pipe to hvac unit on roof not being supported correctly. as per 308.3 of the plumbing code and anchors shall be attached to the building construction in an approved manner., repair and/or replace
Sep 6, 2024 · Penalty $310
Resolve - Class - 1
I observed in the cellar electrical room the installation of branch circuit wiring, devices, circuit breakers to various receptacles, and laundry equipment. no permit in dob records covers this work., obtain pe
Aug 15, 2024 · Penalty $800
Active - Class - 1
I observed in the 5th and 4th floor mechanical room, and the cellar pantry room, defective gfci outlets in use. this is an immediate shock and safety hazard., comply with ec; provide gfci protection as required
Aug 15, 2024 · Penalty $1,600
Active - Class - 1
I observed on the roof the gas service supplied to the hvac unit connected with flex. as per the fgc 411.1the connection shall be of rigid piping and fittings only, semi rigid (flexible piping is not permitted)
Aug 15, 2024 · Penalty $2,500
Active - Class - 2
I observed in the laundry room the equipment disconnect made inaccessible due to the equipment and the piping. all electrical equipment shall be accessible for normal and emergency repairs. photos taken., provi
Aug 15, 2024 · Penalty $250
Resolve - Class - 1
I observed in the elevator motor room the unpermitted of a flexible cord as permanent wiring plugged in to a receptacle outlet and terminated in a disconnect switch. this an immediate shock and fire hazard. pho
Aug 15, 2024 · Penalty $1,600
Active - Class - 1
I observed in the water meter room the improper installation of the water meter jumper, the conductor was wrapped around the various components of the water main. the conductor shall be installed so that it pro
Aug 15, 2024 · Penalty $4,800
Resolve - Class - 1
Multiple holes, large section of fire-stop removed from ceilings and walls, and illegal plastic access panels installed in ceiling corridors and all mechanical rooms located throughout building. removing fire-s
Aug 15, 2024 · Penalty $2,500
Active