Violations at 62 Travis Avenue
Staten Island, NY 10314 · BBL 5-02364-0001 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
32 DOB violations, newest first.
- Low pressure boiler boiler required
Violation issued-failure to file 2020 external low pressure inspection
Jun 30, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2020 external low pressure inspection
Jun 30, 2023
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 21, 2021
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 16, 2020
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 15, 2018
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 2, 2009
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 17, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 30, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 13, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 27, 2005
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 3, 2004
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 21, 2003
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Elevator elevatoroptional
1
Apr 7, 1992
Dob violation - dismissed - Elevator elevatoroptional
1
Jun 29, 1990
Dob violation - dismissed
ECB violations
The newest 50 of 78 ECB violations. The city keeps the complete history.
- Class - 2
Failure to maintain building in code-compliant manner. noted: observedat t. o. i., the wrought iron fence near the corner of travis abe and ferndale ave, has been damaged by auto collision. fence is temperally
Mar 3, 2026 · Penalty $1,250
Active - Class - 2
Re-issue #35692222n. failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors perbc 1006.1; 27-381. several emergency lights were not operational when
Mar 3, 2026 · Penalty $3,125
Active - Class - 2
Re-issue #35692224r. failure to maintain building in code-compliant manner. noted: the walls at exit #10, adjacent to the exit doors, have tiles that are bulging and cracking creating a safety hazard. tiles are
Mar 3, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:at t.o.i.observed at exit#10,adjacent to the exit doors,the tile blocks on the wall are seriously bulging,cracking at joints a appear to be falling ap
Mar 6, 2025 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:at t.o.i. there were several exterior exit doors that need attention not fittingproperly,not closing need adjusting.rem:repair/replace exterior doors.
Mar 6, 2025 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted at t.o.i. there were several emergency lights scattered throughout the school that were not operational when tested.rem:repair/replace emergency light
Mar 6, 2025 · Penalty $1,250
Active - Class - 2
Reissue#35679090y altered changed building occupied without a valid cofo as per 28-118.3.1-28-118.3.2.at time of inspection,the cofo has notbeen updated or renewed.rem:obtain valid cofo.
Mar 6, 2025 · Penalty $3,125
Active - Class - 2
Re-issue #35672279x. altered/changed building occupied without a validcertificate of occupancy as per sj 28-118.3.1-sj 28-118.3.2. at t. o. i. the c of o has not been updated and/or re-issued to date. remedy: o
Sep 17, 2024 · Penalty $3,125
Active - Class - 2
Re-issue #35655181n altered/changed building occupied without a validcertificate of occupancy as per 28-118.3.1 28-118.3.2 remedy: obtain a valid certificate of occupancy
May 31, 2023 · Penalty $3,125
Active - Class - 2
Re-issue#35655182p failure to maintain building in code compliant manner: illumination for exits, exit discharges, and public corridors per bc 1006.1; 27-381. note: at t.o.i there were several emergency lights
May 31, 2023 · Penalty $1,562
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner;illumination for exits,exit discharges & public corridors per bc1006.1.1,27-381.observed at t.o.i. there were several emergency light fixtures,located through
May 24, 2022 · Penalty $625
Resolve - Class - 2
Re-issue #35561419r altered changed bldg occupied w/out a valid c of oobserved at t.o.i.,the temp c of o #070916 that expired 7/14/88 has not been renewed &/or updated.remedy:obtain a valid c of o
May 24, 2022 · Penalty $3,125
Active - Class - 2
Reissue35495776m alter changed bldg occupied w/o valid c/o observed@toi temp c/o70916 expired as of 7/14/88.no new c/o on file.obtain valid c/o.
Jun 28, 2021 · Penalty $3,125
Active - Class - 2
Altered changed bldg occupied w/o a valid cert of occupancy. noted: attime of inspection,temp c of o#70916 is expired as of 7/14/88. no renewal on file. reissue#35422323m. remedy: obtain valid c of o.
May 29, 2020 · Penalty $3,125
Active - Class - 2
Re-issue # 35321761j altered/changed building occupied w/o a valid certificate of occupancy note: c of o #70916 expired 7/14/88.no updated c of o on file. remedy: obtain a valid certificate of occupanc
Jul 11, 2019
Active - Class - 2
Failure to maintain bldg in code compliant manner. service equipment boiler. noted: at cellar level, boiler room boilers #1 and 3 observed leaking. also at cellar level, both pumps leaking excessive water leav
Mar 5, 2018
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. noted: at 4th floor level, holding room 416h, damaged door booster, door not self closing. rmdy: repair/replace damaged hardware.
Mar 5, 2018
Resolve - Class - 2
Reissue of nov #35252710n altered changed building occupied w/o a valid certificate of occupancy. cofo #70916 expired 7/14/88. rmdy: obtain valid certificate of occupancy.
Mar 5, 2018
Active - Class - 2
28-301.1 reissue of nov#35252709x failure to provide ventilation to gas meter room per p115.6 (1968 code) fgc appen e (e4) (2014 code) noted: at cellar level gas meter room lack ventilation, via fresh air or
Mar 5, 2018
Resolve - Class - 2
Re-issue ##35120409j altered/changed bldg occupied w.o a valid c of o tco #70916 expired 7/14/88.rem:comply w.summons.
Apr 26, 2017
Active - Class - 2
28-301.1 reissue #35195470p failure to provide ventilation to gas meter room per p115.6 (1968 code)fgc appendix e(e4)2014 code.gas meter room @basement lacks &fresh air vent.rem:comply w.summons.
Apr 26, 2017
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner. reissue edb 35120408h. no fresh air vent in gas meter room. at basement in gas meter roomthere is no fresh air vent. rmdy: comply with nov
Aug 12, 2016
Resolve - Class - 2
Reissue.ecb 35093406n.no c of o.public school operating w/o a current valid c of o.rem:obtain c of o.
Feb 19, 2015
Active - Class - 2
Re-issue.ecb 35093407p.no fresh air vent.in bsmt gas meter room & fan room,there is no fresh air ven.rem:provide fresh air vents.
Feb 19, 2015
Resolve - Class - 2
Re-issue.ecb 35093411h.step cracks on facade.@ the corner of merry mount ave & ferdale ct just below parapet,there are steps cracks on facade wall.rem:repiar section of exterior facade wall.
Feb 19, 2015
Resolve - Class - 2
Failure to maintain bldg wall(s)or appurtenances:exterior.corner of 1 story part of bldg,just below parapet wall in parking lot between merrymount ave & ferndale ct.side above sign that reads"no parking firelan
Mar 19, 2014
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner:interior.@ 1st fl roll down gates in main lobby,infront of room 135,167 & 151 has no safety stop in case an unauthorized person tries to roll gates down ir amal
Mar 19, 2014
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner;interior.@ 2nd fl infront of room 219 i:hallway ceiling tiles approx 2'x4' falling & in disrepair.rem:repair ceiling tiles.
Mar 19, 2014
Resolve - Class - 2
27-misc.,28-misc,bc-misc.miscellaneous violations.reissue ecb #35018334n.@ bsmt in gas meter room & fan room b15-no fresh air ventilation.rem:provide fresh air ventilation.
Mar 19, 2014
Resolve - Class - 2
Reissue ecb #35018332j.altered or changed bldg.altered or changed bldgoccupied w/o valid cert of occupancy.temporary c of o #70916 expired 07/14/88.rem:obtain valid c of o.
Mar 19, 2014
Active - Class - 2
Sec. 27-766. no fresh air ventilation gas meter room. remedy: maintainbldg.
May 20, 2013
Resolve - Class - 2
Electric room b11 used for storage of snow blower, oil tank room used for storage of power washer, spreader and school equipment/supplies. remedy: discontinue illegal use.
May 20, 2013
Resolve - Class - 2
Reissue 34986717m. tco #70916 expd 7.14.88. remedy: obtain valid c/o.
May 20, 2013
Active - Class - 2
Reissue 34987283z. at various locations throughout school, defective f.p.s.c. doors, either racked and/or defective closer. cross corridor door by 134 missing. remedy: maintain bldg.
May 20, 2013
Resolve - Class - 2
At rooms 220,319 and at stair b 2nd flr door area racked, at exit 8 door drags corridor door adjacent to room 126 is missing and glass panelin door at exit b 1st flr is cracked. remedy: repair/replace doors.
Aug 1, 2012
Resolve - Class - 2
Reissue 34908787y. bldg occupied as school w/o a valid c/o. tco 70916 expired 7.14.88. remedy: obtain a valid c/o.
Aug 1, 2012
Active - Class - 2
At the exterior. facade has become porous @ the 1st floor level through various areas w/water penetration present in classroom throughout. remedy: restore weather proof integrity to exterior facade.
Apr 19, 2011
Resolve - Class - 2
Re-issue #34847507y,92l,57l,93x & 57y (2004) building occupied as school nb #1041/72 w/o a valid c of o. tco #70916 expired on 7/14/88. remedy: obtain a valid c of o.
Apr 19, 2011
Active - Class - 2
No backup power to emergency lighting 2- emergency light pack @ bsmt near boiler room & stair remedy: repair/ replace battery packs
Jun 16, 2010
Resolve - Class - 2
No wire glass present @ fire rated doors or corridor walls. locations 319j opposite 319f 220h 167 remedy: maintain required fire rating of corridor doors & walls install wire glass where required
Jun 16, 2010
Resolve - Class - 2
@ 4th fl roof bulkhead # 8 door can not be opened remedy: repair or replace door
Jun 16, 2010
Resolve - Class - 2
@ north east bulkhead 4th fl parapet 2' section of tin coping is torn loose adjacent section is defective & can not provide protection from the elements remedy: repair coping
Jun 16, 2010
Resolve - Class - 2
@ 2nd story roof top of bulkhead access ladder 2 anchors have broken free of masonry wall remedy: secure access ladder to wall
Jun 16, 2010
Resolve - Class - 2
@ boiler room combustion - air louvres not working - actuator arms disconnected remedy: provide working combustion - air louvres
Jun 16, 2010
Resolve - Class - 2
Fire stopping not provided locations: @ gas meter room : pipe penetration @ boiler meter room : pipe penetrations remedy: provide required fire stopping
Jun 16, 2010
Resolve - Class - 2
@ auditorium under several seats exposed wire covers missing from condiletts locations include but not limited to: aa centre, left, z left, q left, m left, remedy: provide wire covering recommend an installatio
Jun 16, 2010
Resolve - Class - 2
Reissue from 34798810z, issued 7/1/2009 gas meter room used as storage (furniture, cleaning equip, supplies, etc) remedy: empty gas meter room of all stored items
Jun 16, 2010
Resolve - Class - 2
In boiler room near boiler # 3 water penetrating through fl. constant condition pallets on fl to keep workers dry. remedy: prevent water penetration through fl.
Jun 16, 2010
Resolve - Class - 2
Re-issue from: 34586857l, 34708092l, 34798809l, 34421557y, 34466393x nb 1041172, tco expired 7/14/1988 remedy: obtain final sign off & c of o
Jun 16, 2010
Active - Class - 2
Exposed wire. covers missing from condiletts. locations: auditorium; aa centre left, z left, q left, m left. remedy: install covers
Jul 1, 2009
Resolve