Violations at 229-02 137 Avenue
Queens, NY 11413 · BBL 4-13170-0012 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
15 DOB violations, newest first.
- Failure to submit eer none
Failure to submit an eer per ad. code sec. 28-308.4 in 2020
Jun 20, 2021
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 1, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed
ECB violations
The newest 50 of 89 ECB violations. The city keeps the complete history.
- Class - 2
Reissue#35692596h failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:exit lights corridor 2nd fl and exit door 6#33 and
Feb 12, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:upon inspection no firestopping as per bc 712.3;27-345 in number use locations throughout boiler room.rem:provide/maintain firestopping.
Feb 12, 2026 · Penalty $1,250
Active - Class - 2
Reissue#35692597j failure to maintain building in code-compliant manner.noted:spalling/crumbling plaster at 3rd fl staircase 10-11.rem:repair and/or replace.
Feb 12, 2026 · Penalty $1,250
Active - Class - 2
Reissue#35692598l failure to maintain building in code-compliant manner.noted:upon inspection heavily corroded coal chute hatch space by sprinkler room.rem:repair and/or replace.
Feb 12, 2026 · Penalty $3,125
Active - Class - 2
Reissue#35692599n failure to maintain building walls or appurtenances.noted:upon inspection at exposure 3 rear vertical cracks and spalling at decorative corner exp 3 and 4 corner including inner courtyard corn
Feb 12, 2026 · Penalty $6,250
Active - Class - 2
Failure to maintain building walls or appurtenances.noted:at exp#3(rear)vertical cracks & spalling at decorative corner stores.locations include exp#2 & 3 corner,exp#3 & 4 corner,including inner courtyard corne
Feb 13, 2025 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. noted at cellarlevel by sprinkler central valve, the coal chute hatch is heavily corroded with holes through the surface allowing water into the cellar. re
Feb 13, 2025 · Penalty $625
Active - Class - 2
Reissue #35676498y. failure to maintain building in code-compliant manner. noted spalling/crumbling plaster at 3rd floor staircase 10-11 andclassroom #302, due to ceiling/roof leak. remedy: repair and/or replac
Feb 13, 2025 · Penalty $1,562
Active - Class - 2
Reissue #35676497m. failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted emergency lights at 2nd fl exit 6a, #33 and 3
Feb 13, 2025 · Penalty $1,562
Active - Class - 2
Failure to maintain building in code-compliant manner. noted: class room #320 missing door closer. remedy: repair/replace door.
Mar 1, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-complaint manner: no fire stopping per bc712.3; 27-345. noted: at cellar electrical room, hole around the conduit with no fire stopping. remedy: provide/maintain fire stoppi
Mar 1, 2024 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner. noted: defective garbage disposal at cellar allowing the rain water from roof into the cellar. remedy: make necessary repairs.
Mar 1, 2024 · Penalty $625
Resolve - Class - 2
Failure to miantain building in code-compliant manner. noted: foundation wall at cellar at 137 avenue side, foundation wall by exit #13 has become porous allowing the rain water in to the cellar. remedy: mainta
Mar 1, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-complaint manner. noted: spallingplaster at stair case 10, 11, room 302, 313 due to ceiling leak/roof leak. remedy: make necessary repairs.
Mar 1, 2024 · Penalty $625
Active - Class - 2
Reissue #35665277r. failure to minatin building in code-compliant manner. illumination for exits, exit discharges and public-corridor per bc1006.1; 27-381. noted: the following emergency exit lighting found ino
Mar 1, 2024 · Penalty $1,562
Active - Class - 2
Failure to miantain building in code-compliant manner. noted: at 1st floor, at custodian's office door, marble casing approx. 6"x3' missing.remedy: make necessary repairs.
Mar 1, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner.at 1st floor outside of auditorium custodian office marble casing approx 6'x3' collapsed form door causing floors.rem:repair/replace marble casing.
Feb 2, 2023 · Penalty $625
Resolve - Class - 2
Reissue#35644481l(3/23/2022)failure to maintain building in code-compliant manner:illumination exits at 2nd floor exit 6a 1st floor cellar by boiler room by exit 13 rear column,lunch room area,gym.rem:remove/re
Feb 2, 2023 · Penalty $1,562
Active - Class - 2
Reissue#35546580h failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridor per bc 1006.1 27-381.noted:at 2nd floor emergency light #28(exit a6,at 1st floo
Mar 23, 2022 · Penalty $1,562
Active - Class - 2
Failure to maintain bldg in code compliant manner illumination for exit discharges & public corridors per bc 1006.1;27-381. at cellar level lunch room 1 place there are 2 lights 1 light(emergency exit light)exi
Feb 5, 2021 · Penalty $625
Active - Class - 2
Exit door not self closing. noted: the following exit doors are not working properly;exit by 356,gymnasium by 351,auditorium stage left doorexterior exit by stair e & f,cafeteria exit 2 & 5 by 157. remedy: repa
Feb 3, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. illumination for eits,exits discharges & public corridors per bc 1006.1;27-381. noted: the emergency lights #30 by 301 & cafeteria #13 &(10 w are all inoperati
Feb 3, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. noted: the handrailat the main entrance to the bldg is loose & is shaking when used. remedy: repair &/or replace.
Feb 3, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. noted: at the cellar level by exit 13'column near ceiling has a large hole,approx 1'x2'. remedy: repair &/or replace.
Feb 3, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. noted: the following doors are not working properly;rooms 323 & 2000 behind auditorium. remedy: repair &/or replace.
Feb 3, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: use of prohibited door &/or hardware per bc 1008.1.8;27-371(j). noted: rooms 305,319a & the gymnasium room 351;all have kick down door holder installed.
Feb 3, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner noted at 1st flrcafeteria entry door and at auditorium entry door do not close properly due to hardware defects. rmdy: repair and/or replace.
Feb 11, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner lack of emergency lighting for exits. exit discharges and public corridors per bc 1006.1; 27-542. noted: at 1st floor cafeteria, 3 emergency exit lighting
Feb 11, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner. noted: at gas meter room, crack in the foundation wall apprx 1/2" w x 4' long. rmdy: repair and/or replace.
Feb 11, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner no fire stoppingper bc 712.3; 27-345. noted: at electrical room, holes with no fire stopping. rmdy: provide/maintian fire stopping.
Feb 11, 2019
Resolve - Class - 2
B254,32a,50a. federal boiler mdl #fst200: 50a-proving switch for motorized fresh air louver jumped out. rmdy: resolve violating conditions and submit certificate of correction.
Jan 2, 2019
Resolve - Class - 2
B254,32a,50a. federal boiler mdl fst200: 50a-proving switch for motorized fresh air louver is jumped out; rmdy: resolve violating conditions and submit certificate of correction.
Jan 2, 2019
Resolve - Class - 2
Reissue #35234638z failure to maintain bldg in code compliant manner:noted: exit 5,4 by cafeteria water coming in from sky light. rmdy: complly with nov.
Feb 7, 2018
Resolve - Class - 2
Work after hours contrary to 28-105.12.5;work other than monday to friday 7am to 6pm no variance permit on file.rem:obtain after hours variance permit.
Sep 12, 2017 · Penalty $830
Resolve - Class - 2
5,42,50a. b254-50a-honeywell auto mixing valve leaking. correct all violating conditions and submit the certificate of correction.
May 1, 2017
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. noted: @ 3rd flr room 319a, spalling plaster around plumbing pipe. rem: comply w/ nov.
Mar 3, 2017
Resolve - Class - 2
Reissue# 35177788x. exit door not self-closing. noted: @ 2c,3c,2e,2f exit 52 & 5 vestibule doors have defective door closers prevent doors to operate from self-closing. rem: comply w/ nov.
Mar 3, 2017
Resolve - Class - 2
Reissue# 35177789h. failure to maintain bldg in code compliant manner. noted: @ multipurpose room 2 main door do not operate properly on opening/closing. rem: comply w/ nov.
Mar 3, 2017
Resolve - Class - 2
Reissue# 35177792z. failure to maintain bldg in code compliant manner. noted: @ cafeteria @ exit 5, 4 water penetration from the roof around the sky light. rem: comply w/ nov.
Mar 3, 2017
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. noted: @ cafeteria @ exit 5 & 4 water penetration from the roof around the sky lights. rem: make necessary repairs to stop leak.
Apr 19, 2016
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: lack of emergency lighting per bc1006-1,27-542. noted: @ gym inoperable emergency lighting. rem: repair &/or replace lighting.
Apr 19, 2016
Resolve - Class - 2
Failure to maintain bldg code-compliant manner. failure to provide wired glass vision panels. noted: no wired glass vision panels @ following room# @ 2nd flr- room 223,222, & throughout the 3rd flr doors do not
Apr 19, 2016
Resolve - Class - 2
Reissue# 35107540z. failure to maintain bldg in code-compliant manner. noted: fire & smoke doors defective/not operating properly on closure/opening locations. multipurpose room (2)main doors, 1 to stair d & 1
Apr 19, 2016
Resolve - Class - 2
Reissue# 35128460l. exit door not self-closing. noted: @ 2c,3c,2e,2f exit 52 & 5 vestibule doors have broken &/or missing door closers. rem:repair/replace doors.
Apr 19, 2016
Resolve - Class - 2
Failure to maintain building code compliant: noed: at transportable unit t4, the entry floor is defective. the sub flooring is rottd and spongy. the minor repair is loose and not adequate.rmdy:comply w/code.
May 5, 2015
Resolve - Class - 2
Reissue: 35107541k failure to maintain building wall(s) or appurtenances. noted: at transportable units t2 and t4, the wood ramp is defective at both units w/holes, loose pcs, and rotten wood giving little supp
May 5, 2015
Resolve - Class - 2
27-369. excessive combustibles in corridors per 27-369. noted: at 3rd floor corridor adjacent to room 323, combustible artwork,cardboard anddecorations stored on top of lockers. rmdy: comply w/care,remove all
May 5, 2015
Resolve - Class - 2
Failure to maintain building code compliant: lack of emergency lighting per bc1006; 27-542 noted: inoperative emergency lighting for exit 5 in 1st flr multi-purpose room. rmdy: comply w/code.
May 5, 2015
Resolve - Class - 2
Reissue: 35107539l failure to maintain building wall(s) noted: at room 319a, the roof drain ara allows rain water penetration to ceiling.the ceiling has several repairs that keep getting west.rmdy
May 5, 2015
Resolve - Class - 2
Reissue #35107540z exit doors not self closing. noted: at 2c,3c,2e,2f exits 2 & 5 vestibule doors have broken and or missing door closer. remdy: comply w/code.
May 5, 2015
Resolve