Violations at 171-05 137 Avenue

Queens, NY 11434 · BBL 4-12495-0166 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

22 DOB violations, newest first.

  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 11, 2019

    Dob violation - active
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 7, 2018

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 4, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 21, 2015

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 5, 2013

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2010 inspection/test

    Dec 13, 2011

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 8, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 15, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 2, 2007

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 15, 2005

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 8, 2004

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 21, 2003

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - active
  • Elevator elevatoroptional

    1

    Apr 25, 1991

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Jun 29, 1990

    Dob violation - dismissed

ECB violations

The newest 50 of 67 ECB violations. The city keeps the complete history.

  • Class - 1

    Failure to maintain building in code-compliant manner.noted:step crackat the corner of exposure#1 and #2 on the 3rd floor and a vertical crack at the corner of exposure#1 and exposure#3 on 3rd floor and at expo

    Jun 1, 2026 · Penalty $2,500

    Active
  • Class - 1

    Failure to maintain building in code-compliant manner.noted:loose decorative window panel at exposure#2 3rd floor observed upon inspection.rem:repair and/or replace.

    Jun 1, 2026 · Penalty $2,500

    Resolve
  • Class - 2

    Reissue on ecb#35724675j exit door not self closing.noted:emergency exterior exit door not self-closing properly due to binding,missing and or faulty hardware on exterior emergency exit#4(1)door 1st fl,exit 3 1

    Jun 1, 2026 · Penalty $1,562

    Active
  • Class - 2

    Reissue on ecb#35724676l failure to maintain building in code-compliant manner.noted:fire rated classroom and smoke doors not closing properly due to binding,missing and or faulty hardware on classrooms 353,346

    Jun 1, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue on ecb#35724677n failure to maintain building in code-compliant manner.noted:at gas meter room storage of combustible materials withlight bulbs,batteries,tables,chairs and steel parts observed upon insp

    Jun 1, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manenr. no fire stopping per bc 712.3; 27-345. noted: at electric meter room observed multiple areas missing fire stopping. remedy: provide/maintain fire stopping.

    Sep 25, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: at gas meter room, observed light bulbs storage, inside as storage, electric meter room has two table, 8 chairs inside the rm. remedy: remove materi

    Sep 25, 2025 · Penalty $1,250

    Active
  • Class - 2

    Re-issue #35677487n. failure to maintain building in code-compliant manner. noted: interior smoke doors do not self-close properly at "cafeteria exit 11", "door k", "l", at "stair h 2 doors", "stair l(a) door",

    Sep 25, 2025 · Penalty $3,125

    Active
  • Class - 2

    Re-issue #35677488p. exit door not self-closing. noted: at cellar "exit 3". 1st flr-"exit 11", exit 2". doors do not self-close properly. remedy: repair/replace door.

    Sep 25, 2025 · Penalty $1,562

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridor per bc 1006.1; 27-381. noted: at first floor, emergency exit lighting #12, at gym 3 lighting fo

    Jul 1, 2024 · Penalty $625

    Resolve
  • Class - 2

    Reissue #35676513n. failure to maintain building wall(s) or appurtenances. noted: at cellar leve, foundation wall has become porous allowingthe rain water into the oil tank room. remedy: maintain exterior wall.

    Jul 1, 2024 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue #35676514p. exit door not self-closing. noted: at cellar exit #3, exit #11, exit #2 doors donot self-close. remedy: repair/replace door.

    Jul 1, 2024 · Penalty $1,562

    Active
  • Class - 2

    Reissue #35676515r. failure to maintain building in code-compliant manner. noted: at cafeteria exit #11, door k, l, at stair "h" 2 doors, stair "l" a door, class room door 219, 244 do not close properly. remedy

    Jul 1, 2024 · Penalty $1,562

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: at auditorium right side of stage door slam too hard, at cafeteria exit #11, ddoor k,l, do not close properly. remedy: repair/replace door.

    Aug 10, 2023 · Penalty $625

    Active
  • Class - 2

    Exit door not self-closing. noted: at cellar exit #3, storage room, at first floor exit #11, exit doors are jammed needs excessive force to open. remedy: repair/replace door.

    Aug 10, 2023 · Penalty $625

    Active
  • Class - 2

    Reissue #35655453h failure to maintain building wall(s) or appurtenances. noted: foundation wall has become porous allowing the rain water in to the oil rank room. remedy: maintain exterior wall.

    Aug 10, 2023 · Penalty $3,125

    Resolve
  • Class - 2

    28-301.1 failure to provide ventilation to gasmeterrm per p115.6(1968code),fgc apdxe(e4)(2014code).noted:observed@cellar level-gasmeterrm has ventilation system installed incorrectly,not allowing fan to exhaust

    Jun 17, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    Exit door not selfclosing noted:observed@cellar level-boilerrm door for emergency exit@roof level-bulkhead/roof door for stwyd&e&stwyf&g,@2fl stwyh&i,@1fl kitchen emergency exit@1fl stwyf&g/exit4&3.these doors

    Jun 17, 2022 · Penalty $625

    Resolve
  • Class - 2

    Reissue35554014n failure to maintain bldg wall(s) or appurtenances.noted:observed@cellar level in oil tankrm,foundation wall has become porous allowing wter to enter rm&create several puddles thruout oil tankrm

    Jun 17, 2022 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue#35495219j failure to maintain bldg walls or appurtenances. cellar level in oil tank room foundation wall has become porous allowing the water to enter room. remedy: maintain exterior bldg wall.

    May 20, 2021 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue#35495220r failure to maintain bldg in code compliant manner. gas meter room is being used as storage room. remedy: repair &/or replace.

    May 20, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: gas meter room is being used as storage room w/metal shelving full of misc items &pile of chemical buckets. remedy: comply w/notice of violation.

    May 27, 2020 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35341810p failure to maintain bldg walls or appurtenances. noted: at cellar level,at oil tank room,foundation wall has become porous allowing the rain water into the oil tank room. remedy: water roof

    May 27, 2020 · Penalty $3,125

    Resolve
  • Class - 2

    National us boiler. correct violating conditions and submit a certificate of correction.

    Oct 2, 2019

    Resolve
  • Class - 2

    National us boiler. correct violating conditions and submit a certificate of correction.

    Oct 2, 2019

    Resolve
  • Class - 2

    Reissue#353418122. exit door not self-closing,3rd floor doorway dt corridor 000 by room 342 not closing

    Jun 28, 2019 · Penalty $1,562

    Resolve
  • Class - 1

    2x10,5x10,42n9,68m7-2x10)repair phone system in the cab. 5x10)repair door zone restrictor immediately (safety hazard). 42n9)remove jumper from fuse & replace fuse. 68m7)provide maintenance log & mcp in mr.

    Dec 14, 2018

    Resolve
  • Class - 2

    Exit door not self closing:note @3rd fl door way d & corridor door by room 342 not closing.rem:repair or replace door.

    Jun 20, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner use of prohibited door & or hardware per bc 1008.1.8;27-371(j) note kids stops in stalled on varoius door.rem:provide legal hardware.

    Jun 20, 2018

    Resolve
  • Class - 2

    Reissue #35272201n failure to maintain bldg walls or appurtenance note:@cellar level in fuel oile room foundation walls have become porous allowing water penetration flooding room.rem:maintain exterior bldg wal

    Jun 20, 2018

    Resolve
  • Class - 1

    Cease use. 5d10,16m7. (5d)repair car door zone restrictor. restrictor has been modified & rendered inoperable. (16m)provide fire gibbs on 2nd flr door.

    Jul 13, 2017

    Resolve
  • Class - 2

    Reissue #35195245z. failure to maintain building wall(s) or appurtenances. noted: on tank room foundation wall has become porous allowing water penetration to room. rem: maintain building wall(s) or appurtenanc

    Jul 13, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. no fire stopping per bc 712.3;27-345. noted: observed at cellar level in gas meter room no fire stopping w/pipes & members (pre leading) through the walls & ce

    Nov 30, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg walls or appurtenances. reissue #35147564j issued on 10/1/15. noted: observed at cellar level in fuel oil tank room. the foundation wall has become porous allowing water to enter w/stan

    Nov 30, 2016

    Resolve
  • Class - 2

    Fail maintain bldg in compliant manner:lack emergency light for exits.note:@auditorium, inoperative emergency lighting w/battery back-up over exit doors. 2 of 3 sets of lights were found inoperative.rem:comply

    Oct 1, 2015

    Resolve
  • Class - 2

    Fail maintain bldg in compliant manner:lack emergency light for exits.note:@1st fl cafeteria, inoperative emergency lighting over all exit doors. rem:comply w/code.

    Oct 1, 2015

    Resolve
  • Class - 2

    27-766 reissue #35094964m fail to provide fresh air inlet per 27-766. note:@cellar gas meter room, no fresh air inlet provided per 27-766 rem:comply w/code

    Oct 1, 2015

    Resolve
  • Class - 2

    Reissue #35094965y fail to maintain building wall(s) or appt.@cellar fuel oil tank room,the foundation wall has become porous allowing water to enter w/standing water to 2" deep. rem:comply w/nov

    Oct 1, 2015

    Resolve
  • Class - 2

    Defective doors noted @3 floor corridor door, 3 flr stair f. remedy: repair/replace doors.

    Jul 3, 2014

    Resolve
  • Class - 2

    Reissue 35028326m. loose flashing @roof edge throughout building n/w corner,above exit 5 & 6 partially detached from facade. remedy: repair loose areas.

    Jul 3, 2014

    Resolve
  • Class - 2

    Reissue 35028327y. water penetration oil tank room cellar level. ponding noted. remedy: seal penetrations.

    Jul 3, 2014

    Resolve
  • Class - 2

    27-766. reissue 35028328x. missing f.a.i in gas meter room. remedy: provide f.a.i.

    Jul 3, 2014

    Resolve
  • Class - 1

    Spalling concrete above exits 3 & 4 w/evident signs of further falling debris. remedy: secure loose debris, provide protection.

    Jul 3, 2014

    Resolve
  • Class - 2

    27-766 reissue 34987213n gas meter room lacking fresh air ventilation at cellar level. rmdy: provide fresh air intake.

    Jul 2, 2013

    Resolve
  • Class - 2

    Foundation wall has become porous and allowing rain water into cellar level causing interior damage at oil tank room. rmdy: maintain water proofing.

    Jul 2, 2013

    Resolve
  • Class - 2

    Reissue 34987215r the metal edge cap of the roof is not fully attached to the building located adjacent to the shopping plaza. rmdy: correct condition.

    Jul 2, 2013

    Resolve
  • Class - 2

    The metal edge cap of the roof is not fully attached to the building located adjacent to the shopping plaza. remedy: re-attach metal edge cap.

    Jul 20, 2012

    Resolve
  • Class - 2

    The foundation wall has become porous & allowing rain water into cellar level causing interior damages at the oil tank room. remedy: water proof foundation wall.

    Jul 20, 2012

    Resolve
  • Class - 2

    Sec. 27-766 reissue: 34926257x the gas meter room is lacking fresh airventilation at the cellar level. remedy: provide fresh air ventilation.

    Jul 20, 2012

    Resolve
  • Class - 2

    Reissue: 34840557k. the gas meter room is lacking fresh air ventilation at the cellar level. remedy: provide/maintain fresh-air ventilation.

    Sep 2, 2011

    Resolve