Violations at 125-20 Sutphin Boulevard
Queens, NY 11436 · BBL 4-12051-0001 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
14 DOB violations, newest first.
- Low pressure boiler boiler required
Violation issued-failure to file 2018 external low pressure inspection
Jun 20, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2018 external low pressure inspection
Jun 20, 2023
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 17, 2019
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 13, 2017
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 15, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 29, 2015
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 17, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 4, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 24, 2010
Dob violation - resolved - Facade facade optional
Ll10/80-local law 10/80 - facade facade optional
Jul 1, 1992
Dob violation - dismissed
ECB violations
45 ECB violations, newest first.
- Class - 2
Failure to maintain building in code-compliant manner.noted:missing chunks of concrete on riser steps and missing non slip diamond tread plates on exterior walkway steps observed coned off upon inspection.rem:r
May 26, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner.no firestopping per bc 712.3;27-345.noted:missing firestopping in gas meter room on one large section of cmu block above entrance approximately 2ft x 3ft ob
May 26, 2026 · Penalty $1,250
Active - Class - 2
Reissued on ecb#35725403k failure to maintain building in code-compliant manner.noted:fire rated classrooms and smoke doors not self-closingdue to binding,missing and or faulty hardware on classrooms 501,502,30
May 26, 2026 · Penalty $3,125
Active - Class - 2
Reissue on ecb#35725405y failure to maintain building in code-compliant manner.noted:at kitchen with commercial gas stove without an ansul or a fire suppression system observed upon inspection.rem:repair and/or
May 26, 2026 · Penalty $3,125
Active - Class - 2
Reissue on ecb#35725404m failure to provide ventilation to gas meter room per p115.6(1968 code);fsc appendix e(e4)(2014 code).noted:at cellar level at gas meter room remains without ventilation or fresh air int
May 26, 2026 · Penalty $3,125
Active - Class - 2
Reissue #35692576k date of issue: 10-24-2025. exit door not self-closing properly. at the time of inspection observed and noted at 1st floorexit-6 outside one exit door, at 1st floor cafeteria two exit doors, n
Sep 26, 2025 · Penalty $625
Resolve - Class - 2
Reissue #35692556n date of issue: 10-14-2024. failure to maintain building in code-compliant manner. noted and observed at kitchen has a commercial gas stove in that place without an ansul system. remedy: repai
Sep 26, 2025 · Penalty $3,125
Active - Class - 2
28-301.1. reissue #35692557p date of issue: 10-24-2024. failure to provide ventilation to gas meter room per p115.6(1968 code) fgc appendix e(e4)(2014 code) . at the time of inspection observed and noted at cel
Sep 26, 2025 · Penalty $3,125
Active - Class - 2
Reissue #35692558r date of issue: 10-24-2024. failure to maintain building in code-compliant manner. at the time of inspection observed and noted, defective hardware on interior fpsc doors missing door closure
Sep 26, 2025 · Penalty $3,125
Active - Class - 2
Federal boiler has #3 king valve leaking water onto oil burner+vac system pump+float switch both leaking water+oil shutoff valve is missing@top of oil tank;correct violation+submit certificate of correction
Aug 27, 2025 · Penalty $1,250
Active - Class - 2
Exit door not self-closing. noetd: exterior door at exit #6, rubs or saddle and jamb preventing it from closing properly. remedy: repair/replace door.
Oct 24, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. emeregency lights defective/not working when tested at 1st fl stair 4,
Oct 24, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner. noted: interiorfpsc doors missing closures or rached at rm #303b, 303c, 313c, 313e, 313g, 309 smoke door, 309b, 309c, 200x, 203a, 203c. mentioned doors ar
Oct 24, 2024 · Penalty $625
Active - Class - 2
28-301.1 reissue #35663487x. failure to provide ventilation to gas meter room per p115.6(1968 code), fgc appendix e(e4)(2014 code). noted atcellar level gasmeter room, no fresh air ventilation provided. remedy:
Oct 24, 2024 · Penalty $3,125
Active - Class - 2
Reissue #35663488h. failure to maintain building in code-compliant manner. noted: kitchen has a commercial gas stove in place without an ansul system. remedy: repair/replace. provide ansul system.
Oct 24, 2024 · Penalty $1,562
Active - Class - 2
Reissue: 35655436x failure to maintain building in code-compliant manner. commercial gas stove in place without an ansul system. remedy: repair and/or replace
Aug 15, 2023 · Penalty $1,562
Active - Class - 2
Reissue: 35655437h miscellaneous violations cellar level gas meter room no fresh air intake vent. remedy: comply with code
Aug 15, 2023 · Penalty $3,125
Active - Class - 2
Reissue: 35655438j failure to maintain building wall(s) or appurtenances. roof level on parapet wall coping stones have cracks and chipping on them about 15 stones with crack 9 have been replaced last year. als
Aug 15, 2023 · Penalty $3,125
Resolve - Class - 2
Failure to maintain building wall(s)or appurtenances.noted:observed atseveral locations of parapet wall,the coping stones(approx.7 pieces/stores)have several cracks and are chipping away on the inside of the wa
Jun 9, 2022 · Penalty $1,250
Resolve - Class - 2
28-301.1 reissue#35561262h failure to provide ventilation to gas meterroom per p115.6(1968 code),fgc appendix e(e4)(2014 code).noted:observed at basement level-gas meter room does not have mechanical or natural
Jun 9, 2022 · Penalty $3,125
Active - Class - 2
Reissue#35561264l failure to maintain building in code-compliant manner.noted:observed in 1st flr kitchen,commercial gas stove in place without a ansul system.rem:repair and/or replace,install ansul system.
Jun 9, 2022 · Penalty $1,562
Active - Class - 2
Reissue#35561265n failure to maintain building in code-compliant manner:illumination for exits,exit discharges & public corridors per bc 1006.1;27-381.noted:observed at 1st flr by stairway c emergency light box
Jun 9, 2022 · Penalty $1,562
Resolve - Class - 2
Missing bolts & dogs on front & rear doors on boiler,oil leak at burner,missing wiska switch for combustion air,vacuum pump leaking
Nov 17, 2021 · Penalty $625
Active - Class - 2
Missing bolts & dogs on front & rear doors of boiler,oil leak at burner,missing wiska switch for combustion air louver,vacuum pump leaking
Nov 17, 2021 · Penalty $625
Active - Class - 2
Sec. 28-301.1 unlawful display of artwork in corridors greater than 20% per fgdny 2008 code;fc 803.3.2. observed: at 2nd & 3rd floors on walls finished in wood in the corridor area there is excessive educationa
May 11, 2021 · Penalty $1,250
Resolve - Class - 2
Exit door not self closing. observed: at 1st fl level,exit#5 is not closing properly when inspected. remedy: repair/replace door.
May 11, 2021 · Penalty $625
Resolve - Class - 2
Reissue#35495213z failure to maintain bldg in code compliant manner: observed: at 3rd fl smoke door#309;2nd fl,smoke door staircase'b';1st fl main entrance,smoke door did not close properly when inspected.
May 11, 2021 · Penalty $1,562
Resolve - Class - 2
Failure to maintain bldg in code compliant manners illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. observed:existing emergency lights at 2nd fl;1st fl,light exit 2,light#6,stairc
May 11, 2021 · Penalty $625
Resolve - Class - 2
Violation reissue#35495212r failure to maintain bldg in code compliantmanner: observed: 1st fl kitchen area commercial gas stove w/o ansual system. remedy: repair &/or replace.
May 11, 2021 · Penalty $1,562
Active - Class - 2
Reissue#35495210n failure to maintain bldg in code compliant manner: no fire stopping per bc 712.3;27-345. observed: at basement level,electrical room,holes around the conduits w/o fire stopping. remedy: provid
May 11, 2021 · Penalty $3,125
Resolve - Class - 2
Sec. 28-301.1 reissue#35495211p failure to provide ventilation to gas meter room per p115.6(1968 code),f6c appendix e (e4)(2014 code)observed: at basement,gas meter room does not have mechanical or natural vent
May 11, 2021 · Penalty $3,125
Active - Class - 2
Failure to maintain bldg in code compliant manner. noted: at 2nd fl staircase'b',one door do not close properly due to hardware problem. remedy: repair/replace door.
May 26, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. noted: at kitchen area,commercial gas stove w/no ansul system. remedy: provide ansul system to commercial gas stove.
May 26, 2020 · Penalty $625
Active - Class - 2
Sec. 28-301.1 ressie#35433665x failure to provide ventilation to gas meter room per ph5.5(1968 code);fgc appendix e(e4)2014 code. noted: at gas meter room no fresh air ventilation provided. remedy: comply with
May 26, 2020 · Penalty $3,125
Active - Class - 2
Reissue#35433666h failure to maintain bldg in code compliant manner. no fire stopping per bc 712.3;27-345. noted: at electrical room,holes around the conduits w/no fire stopping. remedy: provide/maintain fire
May 26, 2020 · Penalty $3,125
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. no fire stopping per bc 712.3/27-345. noted: at cellar electric meter room fire stopping missing/none w/opninings/holes in walls throughout in various location
Jun 20, 2019
Resolve - Class - 2
Sec. 28-301.1 failure to provide ventilation to gas meter room per 115.6 fgc appendix e(e4)noted: at cellar gas meter room w/no fresh air intake/ventilation system. remedy: comply w/notice of violation.
Jun 20, 2019
Active - Class - 2
59bb5,68m7,39m7,37t7,67x10,80m7-59bb5)brake maintenance tag expired. 68m7)maintenance control program missing. 39m7)crosby missing on spin out on top of car. 37t7)overhead door is unlabeled. 67x1)outside commun
Oct 20, 2017
Resolve - Class - 2
Bc3307.6.5 failure to maintain sidewalk shed as required by code.notedsidewalk shed erected as per job#402892553 along exp1 has inoperable 4bulbs rendering affected area visibly dark creating potential risk rem
Jan 8, 2016 · Penalty $400
Active - Class - 2
Reissue 35028670l failure to provide fresh air inlet per 27-766.noted @ cellar gas meter room,no fresh air inlet.rem comply w/ nov
Jul 30, 2015
Active - Class - 2
27-766 - reissue 34981448k no fresh air intake at cellar gas meter room. rmdy: provide fresh air intake.
Jul 29, 2013
Active - Class - 2
27-766 reissue #34921937r no fresh air inlet at cellar gas meter room no fresh air inlet rem: fresh air inlet rem: provide fresh air inlet
Jun 27, 2012
Active - Class - 2
The gas meter room is lacking fresh air ventilation in the cellar level. remedy: provide/maintain fresh air ventilation.
Jul 29, 2011
Active - Class - 2
Exteror concrete coping stone is cracked & spalling located at the roof level. remedy: repair &/or replace coping stones.
Jul 29, 2011
Resolve - Class - 2
No fire stopping applied in the gas meter room (c-5) at cellar level. remedy: provide/maintain fire stopping in gas meter room.
Mar 5, 2010
Resolve