Violations at 204-08 203 Street
Queens, NY 11412 · BBL 4-10944-0301 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
20 DOB violations, newest first.
- Low pressure boiler boiler required
Violation issued-failure to file 2018 external low pressure inspection
Jun 20, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2018 external low pressure inspection
Jun 20, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2018 external low pressure inspection
Jun 20, 2023
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 1, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 31, 2005
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 7, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 28, 1993
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 28, 1993
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 28, 1993
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 28, 1993
Dob violation - dismissed
ECB violations
The newest 50 of 80 ECB violations. The city keeps the complete history.
- Class - 2
Exit door not self-closing.noted:on 1st floor inside auditorium behindstage,emergency exterior exit on the right does not self-close properly.rem:repair/replace door.
Jun 2, 2026 · Penalty $625
Active - Class - 3
@boiler room water feed line to boilers+vac system is missing the back flow preventer;correct violation+submit certificate of correction
Aug 18, 2025 · Penalty $500
Active - Class - 2
Failure to maintain building in code-compliant manner. noted: at 1 floor stage ceiling at window cracks and hole in bricks, cellar gas room pipe leaking puddling of ater and repair in floor. remedy: repair and/
Oct 21, 2024 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner. noted: at kitchen entrance exterior walkway concrete flooring indisrepair exposed rebar, main entrance spalling at ceiling. remedy: repair and/or replace.
Oct 21, 2024 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner. noted: at 3 floor room 303, corridor by 318, 2fl. 201, 245, 247, corridor by 203, 1fl. kitchen entrance doors are not closing correctly. remedy: repair and
Oct 21, 2024 · Penalty $625
Active - Class - 2
Reissue #35672322m. failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: at 2 floor girls locker room, exit 6 by stai
Oct 21, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner. noted: at 2nd floor, electrical room #212, illegal storage of misc. items. remedy: remove illegal storage from electrical room.
Jun 7, 2023 · Penalty $625
Resolve - Class - 2
Reissue #35654920n failure to maintain building in code-compliant manner. noted: at cafeteria kitchen, 10 burner commercial gas stove do not have ansul system. remedy: provide ansul system to gas stove.
Jun 7, 2023 · Penalty $1,562
Resolve - Class - 2
Reissue #35654921p exit door not self-closing. noted: at cafeteria, kitchen rear door, at first floor exit #5, one door and stairway "a" bulkhead door that lead to the roof do not close properly. remedy: repair
Jun 7, 2023 · Penalty $1,562
Resolve - Class - 2
Reissue #35658001k failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: defective emergency exit lighting observed at
Jun 7, 2023 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building in code-compliant manner:illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:observed existing emergency lights located at(1st flr)exit#3 by rm#133
May 31, 2022 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner:use of prohibited door and/or hardware per bc 1008.1.8;27-371(j).noted:observed throughout the enitire building,numerous illegal kick stops installed at var
May 31, 2022 · Penalty $625
Resolve - Class - 2
Exit door not self-closing.noted:observed at(1st flr)kitchen,the 2nd means of egress door aka loading dock,exit door is not closing properlyalso observed at(1st flr)stwy e/exit#5 door is not closing properly wh
May 31, 2022 · Penalty $625
Resolve - Class - 2
Reissued#35561049z failure to maintain building in code-compliant manner.noted:observed(1 flr)cafeteria,kitchen has a 10 burner commercial grade gas stone in place with no fire(ansui)suppression system.rem:repa
May 31, 2022 · Penalty $1,562
Resolve - Class - 2
Reissued#35577100l failure to provide ventilation to gas meter room per p115.6(1968 code),fgc appendix e(e4)(2014 code).noted:observed at cellar level-gas meter room has no fresh-on-ventilation provided during
May 31, 2022 · Penalty $3,125
Resolve - Class - 2
Boiler over 8 feet high ,ladder & platform required ,2 low water cut offs 1 tapping
Jul 16, 2021 · Penalty $625
Resolve - Class - 2
Boiler over 8 feet high ladder & platform required,2-low water cut offs 1 tapping
Jul 16, 2021 · Penalty $625
Resolve - Class - 2
Boiler over 8 foot high ladder & platform required,2 low water cut offs 1 tapping need valve on oil suction line b/4 anti syphon ,gas water heater flue into same brick chimney with draft inducer
Jul 16, 2021 · Penalty $625
Active - Class - 2
Reissued#35495568h failure to provide ventilation to gas meter room. noted: observed at cellar,gas meter room has no fresh air ventilation provided as per 115.6(1968 code),fgc appendix e(e4)(2014 code)
May 20, 2021 · Penalty $4,687
Resolve - Class - 2
Reissued#35495569j noted: observed at kitchen,a 10 burner gas commercial stove w/no fire supression system in place. remedy: repair &/or replace.
May 20, 2021 · Penalty $1,562
Resolve - Class - 2
Failure to maintain building in code compliant manner noted at kitchen 10 burner commericial gas stove do not have ansul system provide ansul system to gas stove
May 19, 2020 · Penalty $625
Resolve - Class - 2
Reissue#35434522n failure to maintain building in code complaint amnner noted at gas meter room no fresh air ventilation provide comply with notice of violation
May 19, 2020 · Penalty $625
Resolve - Class - 2
Exit door not self closing. noted: at the 1st floor exit 3 stair c by room 126, exit 7, stair g by room 147 and gymnasium by room 160, exit doors not working properly. rmdy: repair/replace door.
Jun 10, 2019
Resolve - Class - 2
Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: at cafeteria in multiple areas, auditorium right exit pack m an
Jun 10, 2019
Resolve - Class - 2
Reissue 35331767j noted: at cellar level, gas meter room does not have ventilation, no fresh air. rmdy: comply with notice of violation
Jun 10, 2019
Resolve - Class - 2
Failure to maintain building walls or appurtenances. noted: at the roof level, at the parapet wall (204 st and 11 ave) flashing hanging fromthe side wall. rmdy: maintain exterior building wall.
Jun 10, 2019
Resolve - Class - 2
Exit door not self-closing, t the time of inspection observed at 1st floor exit #3 stair d doors #1 and 4, at exit 2 stair #a doors #4 arenot close properly. rmdy: repair and/or replace door.
Jun 20, 2018
Resolve - Class - 2
Reissue #35289665m (8/22/2017) failure to maintain building wall(s) orappurtenances. observed at exterior walls above exit 3, concrete spalling show rebars, bricks are cracked. rmdy: maintain exterior building
Jun 20, 2018
Resolve - Class - 2
Reissue #35271872j (7/10/17) miscellaneous violations. at cellar levelgas room have no ventilation/ failure to provide fresh air intake. rmdy: comply with code.
Jun 20, 2018
Resolve - Class - 2
Reissue #3521871h (07/10/2017) failure to maintain building in code compliant manner: at 1st floor corridor landing next to/adjacent cafe teria stairs is sinking and create a tripping hazard. rmdy: repair and
Jun 20, 2018
Resolve - Class - 2
Failure to maintain bldg walls(s)or appurtenances.noted:at ground fl 204 st &111 ave door entrance over the door the bricks are cracked.alson on 205st &111 ave above the doors the bricks are cracked.rem:mainta
Aug 22, 2017
Resolve - Class - 2
Failure to maintain bldg in code compliant manner.auditorium right wall 15'horizontal bulgin in plaster wal also auditorium left side wall 5'vertical crack in cmi blocl wall.rem:repair/replace
Jul 10, 2017
Resolve - Class - 1
Failure to maintain bldg walls or appurtenances.ground fl.204 st/111 ave-door entrance;over door concrete spalling 205st/111ave both doors-over doors cracked brick(vertical)2'also 10'vertical crack in brick 205
Jul 10, 2017
Resolve - Class - 2
Bc 28-301.1:re-issue#35216648ncellar gas room no ventilation/failure to provide fresh air.rem:comply w/code
Jul 10, 2017
Resolve - Class - 2
Re-issue #35216649p.failure to maintain bldg in code compliant manner stair(e)adjacent to cafeteria stair landing is sinking creating tripping hazard.rem:repair/replace
Jul 10, 2017
Resolve - Class - 2
Failure to maintain bldg code compliant.use of prohibited hardware perbc1008.1.8;27-371(j) noted @ smoke door adjacent to rooms 224,206,hook& eye installed prevents proper door operation.rem comply w/ code,remo
Jul 20, 2015
Resolve - Class - 2
Failure to maintain bldg code compliant.noted missing numerous (luire)glass vision panels @ exits a 3a,4a,2c,2e adjacent to room 309.rem comply w/ code,replace vision panels
Jul 20, 2015
Resolve - Class - 2
Failure to maintain bldg code compliant.noted @ 2nd fl stair a 1 of 4 doors & exit d 1 of 2 doors require excessive force to open,& exit 1 jams shut.rem comply w/ code
Jul 20, 2015
Resolve - Class - 2
Exit door not self closing.noted 2nd fl stair e door has broken door closer.rem comply w/ code
Jul 20, 2015
Resolve - Class - 2
27-766 reissue 35028002x failure to provide fresh air inlet per 27-76 6.noted cellar gas meter room has no fresh air inlet.rem comply w/ code
Jul 20, 2015
Resolve - Class - 2
Reissue 35028004j exit doors not self closing.noted @ 4th fl adjacent to room 418,the smoke doors have defective closers.rem comply w/ code
Jul 20, 2015
Resolve - Class - 2
Reissue#35099908k failure to maintain bldg code compliant.noted @ stair e adjacent to cafeteria,settling of stair platform w/ approx 1/2" sinking creating a trip condition.rem comply w/ code
Jul 20, 2015
Resolve - Class - 2
Re-issue # 35028003h. defective floor at stair "e" 1st floor trip hazard. remedy: repair floor.
Jun 17, 2014
Resolve - Class - 2
Re-issue # 35028004j. defective doors 4th fl corridor doors, stair a 3rd fl stair c, 2nd fl stair a,c, 1st fl exit e vestibule doors, doors dragging not closing properly. remedy: repair/replace doors.
Jun 17, 2014
Resolve - Class - 2
The ceiling plaster is spalling located. stair 'a' 4th fl level. remedy: repair &/or replace plaster.
Jul 18, 2013
Resolve - Class - 2
Reissue 34980928p corridor smoke doors are not self closing located on the 4th fl level by room 418. remedy: repair corridor smoke doors.
Jul 18, 2013
Resolve - Class - 2
Reissue 34980929r exit stair 'e' at cafeteria exit on the 1st fl level. the floor is sinking causing a tripping hazard. remedy: repair &/or replace floor.
Jul 18, 2013
Resolve - Class - 2
Reissue 34980930y the gas meter room is lacking fresh air ventilation at the cellar level. remedy: provide fresh air ventilation.
Jul 18, 2013
Resolve - Class - 2
The gas meter room is lacking fresh air ventilation at the lower lvl rem: provide maintain fresh air ventilation in gas meter rm
Jun 26, 2012
Resolve - Class - 2
Floor by stair e is sinking causing a tripping condition on the 1st floor at cafeteria exit rem: and/or replace floor
Jun 26, 2012
Resolve