Violations at 191-02 90 Avenue

Queens, NY 11423 · BBL 4-10447-0007 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

39 DOB violations, newest first.

  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 22, 2021

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 22, 2021

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 22, 2021

    Dob violation - resolved
  • Elevator elevatorrequired

    Cease use

    Oct 22, 2021

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 21, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 21, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 21, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 21, 2020

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 15, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 20, 2008

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 24, 2007

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Elevator elevatorrequired

    4p10133

    Dec 3, 2001

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 20, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 7, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 7, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 7, 1994

    Dob violation - dismissed

ECB violations

The newest 50 of 73 ECB violations. The city keeps the complete history.

  • Class - 2

    Re-issue #35725555j. altered/changed building occupied without a validcertificate of occupancy as per 28-118.3.1-28-119.3.2. noted: c of o #402889718 expired 5/28/2023, no updated c of o is on record. remedy: o

    May 29, 2026 · Penalty $3,125

    Active
  • Class - 2

    Re-issue #35725556l. failure to maintain building in code-compliant manner. noted: fpsc interior interior doors do not self-close properly at 3rd floor-staircase "f". 2nd flr-staircase "d", "e". classroom doors

    May 29, 2026 · Penalty $3,125

    Active
  • Class - 2

    Re-issue #35725557n. failure to maintain building in code-compliant manner. noted: at vestibule entrance area, there is sheetrock missing off walls. remedy: repair and/or replace.

    May 29, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner: roof membrane is lapping over the pavers. risk trapping water, moss growing along edges where paper over caps pavers. remedy: comply with code.

    Sep 26, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner: at the new building there is a strong mold, moss, water penetration, smell. also smell is in custodian office. remedy: comply with code.

    Sep 26, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue: 35692491l-failure to maintain building in code-compliant manner: entrance #9 vestibule area missing sheetrock, floor is a tripping hazard. remedy: comply with code.

    Sep 26, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue: 35692493p-failure to maintain building in code-compliant manner: 3rd floor 329, 1fl corridor 123, 125, doors not closing properly. remedy: comply with code.

    Sep 26, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue: 35692494r-altered/changed building. occupied with valid certification of occupancy as per 28-118.1; 28-118.3.2. noted: temp cert ofoccupancy temp c of o #4028897. remedy: comply with code.

    Sep 26, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue: 35692496k-exit door not self-closing. exit doors at 3rd fl stair e, f, 2nd fl.(s) stair d, e, f by exit 11, stair c exit 8, 7, 9. remedy: comply with code.

    Sep 26, 2025 · Penalty $1,562

    Resolve
  • Class - 2

    Exit door not self-closing. noted: at 3 floor smoke stair e, f, 2fl.(s) stair d, e, f, 1fl.(s) stair b by exit 11, stair c, exit 8, at exit 7, 8, 9 doors are not closing correctly. remedy: repair/replace door.

    Oct 17, 2024 · Penalty $625

    Resolve
  • Class - 2

    Reissue #35672313k. noted: at new building roof top numerous paving stones crack level and broken at various locations. remedy: repair and/or replace.

    Oct 17, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue #35672314m. altered/change building occupied without valid certificate of occupancy as per 28-118.1; 28-118.3.2. noted: temporary certificate of occupancy issued by building dept #4028897.8t022 expired

    Oct 17, 2024 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: at 3 floor room 329, 1fl. corridor by 123 and 125 doors are not closing correctly. remedy: repair and/or replace.

    Oct 17, 2024 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: at playground various crack throughout flooring area. remedy: repair and/or replace.

    Oct 17, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: at exit 9 vestibule area missing sheetrock walls and flooring trip hazard. remedy: repair and/or replace.

    Oct 17, 2024 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1-27-381. noted: at exit 7, stair a, room by 125 exit signs, exit 7, 8 stair c by

    Oct 17, 2024 · Penalty $625

    Resolve
  • Class - 2

    Vitalic seal leaking in the pit.

    Jul 12, 2024 · Penalty $625

    Resolve
  • Class - 2

    Provide keys for inspection missing.

    Jul 12, 2024 · Penalty $625

    Resolve
  • Class - 1

    No door lock monitoring installed on this controller. as mandated by code a-17.1 section 3.10.12.

    Jul 12, 2024 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at old building at 2nd floor,smoke door by room#233,do not close properly due todefective hardware.rem:repair/replace.

    May 26, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at old building,electrical room at cellar with illegal storage of misc.items.remremove illegal storage from electrical room.

    May 26, 2023 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliance manner.noted:at old building at 3rd floor,stairway c bulkhead spalling plaster due to water penetration.rem:make necessary repairs.

    May 26, 2023 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35654915z altered/changed building occupied without a valid certificate of occupancy as per 28-118.1;28-118.3.2.noted:temporary certificate of occupancy issued by building dept#402889718to22 expired on

    May 26, 2023 · Penalty $1,250

    Active
  • Class - 2

    Reissue#35654916k failure to maintain building in code-compliant manner.noted:at new building,roof top numerous stone pavers are cracked broken at various locations creating a tripping hazard.rem:repair/replace

    May 26, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner:no firestopping per bc 712.3;27-345.noted:observed at(cellar level)gas meter room,walldirectly above main entrance has holes approximately 5 inches(w)penetr

    May 27, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    Reissued#35561037l failure to maintain building in code-compliant manner.noted:observed at roof level of new building section,numerous stonepavers are cracked & broken at various locations and creating a trippi

    May 27, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35561039p altered/changed occupied without a valid certificateof occupancy as per 28-118.3.1-28-118.3.2.noted:observed buidling was altered under alt.type 1 permit#402889718-alt.1 that has not been sign

    May 27, 2022 · Penalty $3,125

    Active
  • Class - 2

    Altered/changed bldg occupied w/o a valid cert of occupancy as per 28-118.3.1;28-118.3.2. noted: bldg altered under app#402889718 & occupied as a public school under & expired temporary cert of occupancy t.c.o.

    May 18, 2021 · Penalty $1,250

    Active
  • Class - 2

    Emergency signs at elevator call stations missing,defective or non compliant w/section requirements. noted: observed at"95 building" 2nd fl elevator call station is missing its emergency signage. remedy: instal

    May 18, 2021 · Penalty $625

    Resolve
  • Class - 2

    Reissued#35495512z failure to maintain bldg in code compliant manner: noted: observed at new bldg's roof,cracked & broken stone pavers at various locations creating a trip hazard. remedy: repair &/or replace.

    May 18, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain buidling in code compliant manner noted at roof top at new building broken/cracked concrete blocks at various areas creating a tripping hazard reair/replace concrete blocks

    May 13, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. no fire stopping per bc 712.3;27-345. noted: at electrical room various large holes around conduits,some as large as 6"x18" w/no fire stopping. remedy: provide

    Nov 16, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at electrialroom,steam pipe leak creating a fire hazard. remedy: make necessary repairs.

    Nov 16, 2016

    Resolve
  • Class - 2

    Reissue 34922592p exterior metal grate adjacent to 191st st rusted/rotted at 1st fl level. remedy: repair defects.

    Jul 11, 2013

    Resolve
  • Class - 2

    Reissue 34779847z inadequate fire stopping at cellar electrical room. multiple open penetrations. remedy: provide fire stopping as per code.

    Jul 11, 2013

    Resolve
  • Class - 2

    Reissue 34840030y exterior foundation wall has become parous & allowing water to enter gas meter room & other locations at cellar. remedy: maintain water proofing.

    Jul 11, 2013

    Resolve
  • Class - 2

    Reissue: 34922593r. wooden ramp is rotten & falling apart located @ transportable #3 in the school yard. remedy: repair/replace wooden ramp.

    May 2, 2012

    Resolve
  • Class - 2

    Reissue: 34922589y. the plaster on the wall is spalling and cracked located in room 305 & 364 on the 3rd flr level. remedy: repair/replace plaster.

    May 2, 2012

    Resolve
  • Class - 2

    Reissue: 34922590l foundation wall has become porous and allowing rainwater into the gas meter room at the cellar level causing interior damages. remedy: water-proof foundation wall.

    May 2, 2012

    Resolve
  • Class - 2

    Reissue: 34922591n. the electrical room is lacking fire stopping around the pipe penetration going through the ceiling at the cellar level. remedy: provide/maintain fire stopping in the electrical room.

    May 2, 2012

    Resolve
  • Class - 2

    Reissue: 34922592p. metal grade adjacent to 191 street is rusted & rotten on the 1st flr level. remedy: repair/replace metal grade.

    May 2, 2012

    Resolve
  • Class - 2

    Exterior wooden ramp is rotten & falling apart located by transportable #3. remedy: repair &/or replace wooden ramp.

    Jul 7, 2011

    Resolve
  • Class - 2

    Exterior metal grade adjacent to 191 street is rusted & rotten on the 1st fl level. remedy: repair &/or replace metal grade.

    Jul 7, 2011

    Resolve
  • Class - 2

    Reissue: 34840029r. the electrical room is lacking fire stopping located at the pipe penetrations going through the ceiling leaving open gapat the cellar level. remedy: provide/maintain fire stopping.

    Jul 7, 2011

    Resolve
  • Class - 2

    Reissue: 34840030y exterior foundation wall has become porous & allowing rain water to enter the building causing interior damages in the gas meter room (old wing) at the cellar level. remedy: water proof exter

    Jul 7, 2011

    Resolve
  • Class - 2

    Reissue: 34840031x the plaster on the ceiling is spalling & cracked located in classroom 305 on the 3rd fl level. remedy: repair &/or replace plaster on ceiling.

    Jul 7, 2011

    Resolve
  • Class - 2

    67x10. 67x- car emergence phone inoperative

    Dec 22, 2010

    Resolve
  • Class - 2

    Exit corridor width by exit 7(cafeteria) is partially obstructed by a security desk which is being used as the main entrance/exit for the school.rem:remove obstruction (secruity desk) forthwith

    Mar 12, 2010

    Resolve
  • Class - 2

    The plaster on the wall is spalling & cracked located in room 305 on the 3rd flr level.remedy:repair &/or replace plaster on wall

    Mar 12, 2010

    Resolve
  • Class - 2

    Reissue:34712503z exterior foundation wall has become porous & and allowing rain water into the bldg causing interior damages in by the gas meter rm (old wing)@cellar level.remedy:waterproof exterior foundation

    Mar 12, 2010

    Resolve