DOB building violations

36 DOB violations, newest first.

  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 6, 2020

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 21, 2017

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 20, 2016

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 22, 2012

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2010 inspection/test

    Dec 13, 2011

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 26, 2011

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Vcat1-elevator annual inspection / test elevatorrequired

    Oct 8, 2010

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 12, 2010

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Feb 27, 2009

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 16, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 14, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 1, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 23, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 17, 2005

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 2, 2004

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - active
  • Elevator elevatoroptional

    1

    Apr 7, 1992

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Apr 25, 1991

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Jun 29, 1990

    Dob violation - dismissed
  • Elevator elevatorrequired

    (74)provide ladder in elevator pit as per code of this department

    Sep 14, 1989

    Dob violation - resolved

ECB violations

The newest 50 of 66 ECB violations. The city keeps the complete history.

  • Class - 2

    Reissue #35719882x date of issue: 05/12/2025. exit door not self-closing properly. at the the time of inspection at exit #3, 5, 7, 13, and 16 at gym exit-15 not self-closing properly. near room 112 one corridor

    May 1, 2026 · Penalty $1,562

    Active
  • Class - 2

    Exit door not self-closing. exterior doors at exit #3, 5, 7, 13 and 16not properly self-closing due to rubbing on saddles or weather strips.remedy: repair/replace door.

    May 12, 2025 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.at exit 15 toward to pasting/sport field curb approx 20'0 length show sign of deteriorated/spalling toward handrail.rem:repair/replace.

    Apr 27, 2023 · Penalty $625

    Resolve
  • Class - 2

    28-301.1 reissue#35555639h 3/9/2021.failure to provide natural or mechanical ventilation to gas meter room per p115.6(1968)fgc appendix e(e42014)at gas meter room.remedy:comply with notice of violation.

    Apr 11, 2022 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue#35490884r misc violations. failrue to provide ventilation to gas meter room. remedy: comply w/code.

    Mar 9, 2021 · Penalty $3,125

    Resolve
  • Class - 2

    Sec. 28-301.1 reissue#35454711k failure to provide ventilation to gas meter room per p 115.6(1968 code)fgc appendix e(e4)(2014 code). note: observed inside the gas meter room,ni ventilation. remedy: provide ven

    Mar 26, 2020 · Penalty $3,125

    Resolve
  • Class - 2

    Sec. 28-301.1 reissue#35326578y failure to provide ventilation to gas meter room per p115.6(1668 code),fgc appendix e(e4)(2014 code). noted:no ventilation provided to gas meter room. remedy: provide ventilation

    Oct 3, 2019 · Penalty $3,125

    Resolve
  • Class - 2

    Bc28-301.1/failure to provide ventilation to gas meter room per p115.6(1968 code)fac appendixe(e4)2014code in side the gas meter room no ventilation observed at the time of inspection.rem:provide ventilation.

    Apr 3, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner illumination forexits exit discharges and public corridors per bc10061;27-381 next to library outside one place two lights are not operational at the time o

    Apr 3, 2018

    Resolve
  • Class - 2

    Reissue#35236052k date of issue 04/10/17 exit door not self closing.cross corridor door near rm 214b,exit vestibule doors exit 13,stair exit2,,exit door near rm no 313,exit 15 in auditorium two doors,not self c

    Apr 3, 2018

    Resolve
  • Class - 2

    Reissue #35236055x date of issue 04/10/17.failure to maintain buildingin code compliant manner failure to maintain building in code compliant manner 12'x 12'ceiling mounted fixtures were changed to linear fourc

    Apr 3, 2018

    Resolve
  • Class - 2

    28-301.1 unlawful placement of furnishings, decoration or other object at exits that obstruct access to egress form or visibility thereof- per fdny 2008 code/fc-1027.4. there are 5 large vinyl banners hanging

    Apr 10, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner/ 12"x12" ceiling mounted fixtures were changed to linear fourcent ceiling mounted fixtures leaving a gap apprx 3"x12" on each side of light fixture/open gaps

    Apr 10, 2017

    Resolve
  • Class - 2

    28-301.1 failure to maintain bldg in code compliant manner/observed at interior courtyard/ten gas powered lawn mowers and snow blowers stored on ope grass/lawn of school bldg directly next to building wall/all

    Apr 10, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. illumination for exits,exit discharges and public corridors per bc 1006.1-27-381.emergency lights are not operational when ested at following location cafet

    Apr 10, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. doors not self-closing. at following locations:second flr cross corridor door near rm214b; exit vestibule doors exit 13; stair a exit 2. rmdy:repair/replace/

    Apr 10, 2017

    Resolve
  • Class - 1

    Due to car accident & fire vehicle struck shed, light post & fence causing approx 40'-0 linear feet of shed to partially collapse. fence also defective & to be repaired & replaced. remedy: make all necessary re

    Apr 5, 2015

    Resolve
  • Class - 2

    Sec. 3314.4.3.3 installation inspection for supported scaffold. noted:supported scaffold on site,submitted by p.e. inspection report does not state that the scaffold was built as per approved construction docum

    Mar 26, 2015 · Penalty $400

    Resolve
  • Class - 1

    Sec. 3314.4.3.5 pre shift inspection for supported scaffold. noted: pre shift inspection was not perform by a competent person on site,mr. jhalak b anthony has no 4hrs users certificate or a 10hrs osha card,to

    Mar 26, 2015 · Penalty $400

    Resolve
  • Class - 2

    Pswo (supported scaffold) issued pursuant to 28-207.2 posted. work does not conform to approved construction documents. noted: installation of supported scaffold on all exposures,not showing scaffold to scaffol

    Mar 26, 2015 · Penalty $250

    Resolve
  • Class - 1

    Sec. 3314.4.5.2 training for supported scaffold user. noted: the following workers on site using supported scaffold did not have scaffold users cards 1)jhalak b achary 2)cristian j pineda 3)tyler anthony.

    Mar 26, 2015 · Penalty $1,600

    Resolve
  • Class - 1

    Failure to safegaurd all public & property affected by construction operations. noted: under appl#402894178,3 tanks of liquefied petroleum,propane being stored inside shipping container w/i doe public school,no

    Mar 26, 2015 · Penalty $2,400

    Resolve
  • Class - 2

    Failure to maintain adequate housekeeping per section requirement. noted: evidence of improper removal of debris from scaffold w/excessive spillage surrounding container in front of exit stair from scaffold. al

    Mar 26, 2015 · Penalty $400

    Resolve
  • Class - 1

    Sec. 3314.1 failure to maintain scaffold in a safe manner (so) as not to endanger public & property from falling materials,tools,debris. noted: excessive amount of debris stored on top of shed,scaffold w/bricks

    Mar 26, 2015 · Penalty $1,600

    Resolve
  • Class - 1

    Sec. 3314.8 failure to provide required guardrails & toe boards for scaffold platform throughout entire scaffold system all levels elevations under appl#402895809. remedy: provide required guardrails/toe boards

    Mar 26, 2015 · Penalty $1,600

    Resolve
  • Class - 2

    Re-issue # 35023739h. spalling masonry with loose mortar joints throughout. remedy: make safe.

    Apr 29, 2014

    Resolve
  • Class - 2

    Re-issue # 35023740p. illegal hardware at bulkhead doors with key cylinder in place. remedy: remove hardware.

    Apr 29, 2014

    Resolve
  • Class - 1

    Spalling mortar joints at grand central parkway service rd side, outside of exit 2,3,10 located at parapet level with evident signs of leaning. remedy: provide shed in front of exit 2,3,10, make safe.

    Apr 29, 2014

    Resolve
  • Class - 2

    Illegal hardware on bulkhead roof doors key cylinder in place. rmdy: remove hardware.

    Jul 16, 2013

    Resolve
  • Class - 2

    Reissue 34958186y exterior wall missing mortar joints throughout facade, courtyard,north, west sides. rmdy: make safe.

    Jul 16, 2013

    Resolve
  • Class - 2

    Classroom door is not of plumb causes door not to close property at room 313 on 3rd floor level. (noted: door hitting door frame). remedy: repair &/or replace door.

    Jul 17, 2012

    Resolve
  • Class - 2

    Reissue: 34906571x brick facade parapet wall is missing mortar betweenbricks. located at above 1st floor parking garage & 4th floor level roof level on the west & north side section. remedy: repair &/or replace

    Jul 17, 2012

    Resolve
  • Class - 2

    Reissue 34827886p exterior brick facade at the parapet is missing mortar joints throughout the bldg rem: replace missing mortar joints

    Apr 18, 2011 · Penalty $2,500

    Resolve
  • Class - 2

    Failure to maintain exterior wall parapet noted mortar joints loose missing throughout bldg remedy make safe.

    Jan 14, 2010

    Resolve
  • Class - 2

    Exit door is missing located at ground fl lvl across from room 623 rem: replace missing door

    Feb 23, 2009

    Resolve
  • Class - 2

    Reissue 34692367h decorative stone tile is spalling & missing located at exterior exit 2&3 on the 1st fl lvl rem: repair & replace decorative stone tile

    Feb 23, 2009

    Resolve
  • Class - 2

    Reissue 34692366x corridor smoke doors are missing adjacent to room 150 across from exit 7 & 8 by boy locker room on the 1st floor lvl rem: replace missing doors

    Feb 23, 2009

    Resolve
  • Class - 2

    Reissue 34692368j exit door frame is rotten at the door saddle locatedat the gymnasium exit on 2nd fl lvl

    Feb 23, 2009

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: exit door atstairway "b" is not self closing on the 2nd flr. remedy: repair and orreplace exit doors.

    Aug 13, 2008

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: exit door frame is rotten by the door saddle located at the gym locker room leading to passageway into gym 2nd flr. remedy: replace and or repair door

    Aug 13, 2008

    Resolve
  • Class - 2

    Reissue: 34577596h failure to maintain bldg in code compliant manner. noted: concrete ceiling and decorative tile is spalling located at exit 2 & 3 on 1st flr level. remedy: repair or and replace tile and concr

    Aug 13, 2008

    Resolve
  • Class - 2

    Reissue: 34577595x failure to maintain bldg in code compliant manner. noted: corridor smoke doors are missing adj to room 150 by access roomexit 7 & 8 near boy locker room 1st flr level. remedy: replace and or

    Aug 13, 2008

    Resolve
  • Hazardous

    Exterior facade missing decorative tile w/loose & missing concrete at bottom corner at exit 2/3.remedy:make all necessary repairs to facade.

    Jun 21, 2007

    Resolve
  • Hazardous

    Missing corridor doors in front of locker room #150 at 1fl across from exit 7 & 8 & in front of room 114a.remedy:replace corridor doors.

    Jun 21, 2007

    Resolve
  • Hazardous

    Ceiling tiles loose & missing in front of exit 13.remedy:repair/replace ceiling tile.

    Jun 21, 2007

    Resolve
  • Hazardous

    Exterior door on roof bulkhead 2/3 does not close.remedy:make all necessary repairs to exterior door.

    Jun 21, 2007

    Resolve
  • Hazardous

    No panic bars installed on two exit way doors located in the gymnasium w/occupancy of 520.remedy:provide panic hardware at all exit doors.

    Jun 21, 2007

    Resolve
  • Non-hazardous

    85u5/40m7/

    Feb 6, 2007

    Resolve
  • Hazardous

    Failure to maintain roof. water penetration from roof into classroom 308 & 311.remedy:stop water penetrating into classroom

    May 19, 2006

    Resolve
  • Hazardous

    Failure to maintain corridors on 1 & 2 & 3 fl in disrepair on drs 1st all 2fl all & 3fl all corridors doors remedy:repair or restore corridors & panic hardware @ above location

    May 19, 2006

    Resolve