Violations at 85-01 102 Street
Queens, NY 11418 · BBL 4-09183-0001 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
19 DOB violations, newest first.
- Low pressure boiler boiler required
Violation issued-failure to file 2021 external low pressure inspection
Jun 30, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2021 external low pressure inspection
Jun 30, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2020 external low pressure inspection
Jun 30, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2020 external low pressure inspection
Jun 30, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2022 external low pressure inspection
Apr 25, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2022 external low pressure inspection
Apr 25, 2023
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 10, 2020
Dob violation - resolved - Plumbing none
Sprinkler system taken off the domestic water supply system without a backflow preventer installed
Nov 3, 2011
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Construction other optional
C-construction other optional
Feb 23, 1999
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed
ECB violations
The newest 50 of 81 ECB violations. The city keeps the complete history.
- Class - 2
Reissue ecb#35691862r failure to maintain building in code-compliant manner.noted at old building basement level the ceiling deteriorate,peeling and making at several locations.rem:repair and/or replace.
Feb 25, 2026 · Penalty $3,125
Active - Class - 1
Building or open lot occupied without a valid certificate of occupancyreissue ecb#35691863z noted:cofc#421098975 expired on 8/6/2020.rem:obtain a valid certificate of occupancy.
Feb 25, 2026 · Penalty $6,250
Active - Class - 2
Failure to maintain building in code compliant manner.noted:smoke doorby stairway#b at basement level not self-closing.rem:repair and/or replace.
Feb 25, 2026 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:emergency lights not working at stairway#3.rem:repair/replace light.
Feb 25, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code compliant manner.noted:front gable roof has missing slate shingle at north side.additionally few slate shingles are cracked & chipped.observed from new building roof.rem:rep
Mar 21, 2025 · Penalty $1,250
Resolve - Class - 1
Reissue#35679015y building or open lot occupied without a valid certificate of occupancy.noted:cofo#421098975 expired on 08/06/2020.new building attached to 2 original landmark buildings occupied as school with
Mar 21, 2025 · Penalty $6,250
Active - Class - 2
Reissue#35679014m failure to maintain building in code-compliant manner.noted at old building basement level,the ceiling deteriorated,peeling & flaking at several locations.rem:repair and/or replace.
Mar 21, 2025 · Penalty $3,125
Active - Class - 2
Reissue#35679016x faiure to maintain building in code-compliant mannernoted rear original building from 1898 with flat roof has cracks in parapet wall above the old cut steel.observed from new building roof.rem
Mar 21, 2025 · Penalty $3,125
Resolve - Class - 2
Observed in the basement in the old building no back flow preventer on the sprinkler system. also the sprinkler system that connects to room b013 is tied into the domestic water line and not the dedicated fire
Sep 30, 2024 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner. original building from 1898 rear one with flat roof has cracks in parapet wall above old steel that was cut, can be seen from new building roof. remedy: re
Apr 9, 2024 · Penalty $625
Resolve - Class - 1
Reissue #35671750y. building or open lot occupied without a valid certificate of occupancy. c of o #421098975 j005 exp.8-6-2020 new buildingoccupied attached to 2 original land market building on new c of o on
Apr 9, 2024 · Penalty $6,250
Active - Class - 2
Reissue #3567171x. failure to maintain building in code-compliant manner exit 1, 2, 3 at basement level tin ceiling deteriorated. remedy: repair and/or replace.
Apr 9, 2024 · Penalty $1,562
Active - Class - 2
Reissue #35655214k (6/1/22) failure to maintain building in code compliant manner:at exit 1,2 & 3 at basement tin ceiling deteriorated with paint brittles,peeling,chipped & partial rusted.remedy:repair and/or r
Mar 14, 2023 · Penalty $1,562
Active - Class - 1
Reissue #35655215m (6/1/22) building on open lots occupied w/o certificate of occupancy records of c of o #421098975 j005 exp 8/6/2323 new building occupied attached to original landmark no records of signed of
Mar 14, 2023 · Penalty $6,250
Active - Class - 2
Failure to maintain building in code-compliant manner. noted:observed during inspection of basement boiler room,walls throughout have spalling/peeling masonary from water penetration. remedy:repair and/or repla
Jun 1, 2022 · Penalty $625
Resolve - Class - 1
Reissue#35591635z building or open lot occupied w/o a valid c of o. noted:observed upon review of dob records,tco#421098975t005 expired on 8/6/2020 for new bldg. bldg fully occupied and operational as a school.
Jun 1, 2022 · Penalty $6,250
Active - Class - 2
Reissue #35548110m failure to maintain building in code-compliant manner. noted: observed at basement level by exit 3, the tin ceiling is brittle, deteriorated and rusted. remedy: repair and/or replace
Jun 1, 2022 · Penalty $1,562
Active - Class - 2
Reissue #35548109p failure to maintain building in code-compliant manner. noted: observed at basement level, boiler room walls are porous allowing water to penetrate throughout. remedy: repair and/or replace
Jun 1, 2022 · Penalty $1,562
Resolve - Class - 1
Reissue35591870z bldg or open lot occupied w/o valid c/o.noted:during insp observed 2bldgs on lot&both occupied as public school&are fully operational.older bldg is landmark w/o cofo&newer bldg on left has cofo
Jan 21, 2022 · Penalty $6,250
Active - Class - 2
Condensate tank and pumps leaking correct violating condition and submit a certificate of correction
Nov 17, 2021 · Penalty $625
Resolve - Class - 1
Reissue#35533917l building or open lot occupied without valid certificate of occupancy.noted:two buildings on lot and both occupied as public school and are fully operational.the older building is landmark with
Nov 3, 2021 · Penalty $6,250
Active - Class - 1
Re-issue #35577227z.building or open lot occupied without valid certificate of occupancy.noted:two buildings on lot that make up school.older building is landmark with no cert of occupancy.new building on left
Sep 15, 2021 · Penalty $6,250
Active - Class - 1
Reissue35548111y bldg or open lot occupied w/o valid c/o.note:observed2bldgs on lot 1old landmark school bldg.another1 on left side is nb which is occupied w/o c/o.current c/o421098975t005 expired8-6-20.also it
May 24, 2021 · Penalty $6,250
Active - Class - 1
Building or open lot occupied without a valid certificate of occupancy note there are 2 buildings on the lot that ake up to the school the older landmark building has no cof o the newer building has temporary c
Feb 16, 2021 · Penalty $2,500
Active - Class - 2
Failure to maintain building in code compliant manner note at the basement elevl near exit #3 the tin ceiling has deteiorated is rusty cracked and has holes in various places maintain building repair.replace
Feb 16, 2021 · Penalty $625
Active - Class - 2
Failure to maintain building in code compliant manner noted at basement level next to boiler room there is a storage area with water penetrating the walls laking puddles and standing water water proof and maint
Feb 16, 2021 · Penalty $625
Resolve - Class - 2
Reissue #35486735o failure to maintain building wall(s) or appurtenances note at exp #1 the brickwork at the upper floors level on either side of window is in disrepair mortar missing form brick joints maintain
Feb 16, 2021 · Penalty $3,125
Resolve - Class - 2
The first floor door does not work in automatic mode
Sep 21, 2020 · Penalty $625
Resolve - Class - 1
1. provide brake maintenance . 2 . the emergency brake (rope gripper) tighten all 4th bolts
Sep 21, 2020 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building wall(s) and or appurtenances - noted: at exp. 1 front, brickwork missing mortar. remedy: maintain exterior walls
Mar 20, 2020 · Penalty $1,250
Resolve - Class - 2
Failure to comply with dot regulations as per 34 rcny 2-05 and admin code provisions 19-107,11-108 or 19-121. noted: at time of my inspection of a new 3 story building construction in progress, i observed a
Jul 19, 2019 · Penalty $625
Active - Class - 2
Jobsite fence not constructed pursuant to subsection. noted: at time of my inspection of a new 3story building,c onstruction in progress i obsrved that the jobsite fence which was shown as a 8'chain-link fen
Jul 19, 2019 · Penalty $400
Active - Class - 1
Falure to file evidence of compliance with workers compensation law and/or disability benefits law noted: at time of my inspection of a new 3story building, construction activities in progress.upon researchin
Jul 19, 2019 · Penalty $1,250
Active - Class - 1
Sec. 3307.4 warning signs,personnel & barriers-at the time of inspection i observed a large construction telehandler out of the side w/no flag man,or other personel protecting the school children on the sidewal
Apr 18, 2019 · Penalty $2,500
Resolve - Class - 1
Sec. 3303.14 drainage of job site waste on to public sidewalk-at the time of inspection i observed a waste pipe from the bldg under construction leading to & emptying out onto the public sidewalk. this is also
Apr 18, 2019 · Penalty $625
Resolve - Class - 1
Sec. 3303.2.3.1 failure to provide temporary lighting for constructionsites. at the time of inspection on an active jobsite i observed no temporary lighting. this is a hazard for workers fored to work in the da
Apr 18, 2019
Resolve - Class - 1
Failure to provide protection at side of excavation more than 5 feet in depth. at time of inspection i observed 2 workers in an excavation more than 5 feet in depth w/no protection & excavator at the leading ed
Apr 18, 2019 · Penalty $5,000
Resolve - Class - 1
No overhead protection on occupied school-at the time of inspection ofan active job site adjacent to an occupied school i observed no roof protection at exp#4. i observed cement droppings on the roof of the occ
Apr 18, 2019 · Penalty $2,500
Resolve - Class - 1
Bc28-105.12.2.built contrary to approved plan.equipment on site in contrary to the approved plan.note:at time of inspection i observed supported scaffold in place on exposure #3 that is contrary to the approved
Jul 27, 2018
Resolve - Class - 2
Bc3314.8.1.guardrails and toeboards/all working platforms need to havetop,mid,endrail and toe boards.note:at time of inspection i observed supported scaffold in place on exposure #1 and #4 missing a complete gu
Jul 27, 2018 · Penalty $625
Active - Class - 2
No storage on shed.pedestrian protection does not meet code specifications.note:at time of inspection i observed sws in place south storage of construction material on top of the sws roof and that does not meet
Jul 27, 2018 · Penalty $2,400
Active - Class - 2
Reissue#35225810r failure to maintain bldg in code compliant manner. noted: at time of inspection observed at the basement cafeteria'a'&'b' place of assembly permit signs are not posted & are missing at these
Jan 26, 2018
Resolve - Class - 2
Reissued# 35146946k, failure to maintain bldg wall(s). noted: @ time of insp observed vertical cracks throughout the entire perimeter of schools retaining wall @ various locations. rem: maintain exterior bldg w
Feb 23, 2017
Resolve - Class - 2
Reissue# 35146947m. failure to maintain bldg in code compliant manner. noted: @ time of insp @ basment cafeteria 'a' and 'b', place of assembly permit signs are not posted & are missing @ these locations. rem:
Feb 23, 2017
Resolve - Class - 2
Failure to maintain bldg in code compliant manner.note @ basement level in cafeteria "a" & "b" occupancy signs are missing.rem comply w/ nov
Sep 3, 2015
Resolve - Class - 2
Reissue:35023585y failure to maintain bldg walls or appurtenances,@ various locations vertical cracks in parimeter masonry wall & retaining wall.rem comply w/ nov
Sep 3, 2015
Resolve - Class - 2
Reissue 35023586x.illegal kick down door stops installed on multiple classroom doors throughout.rem:remove hardware.
Mar 27, 2014
Resolve - Class - 2
Kick down door stops installed on most doors throughout bldg. remedy: remove door stops.
Jun 25, 2013
Resolve - Class - 2
Vertical cracks in retaining wall at various locations. remedy: make necessary repairs.
Jun 25, 2013
Resolve - Class - 2
Bc1008.1.8 27-371j prohibited hardware at 2nd floor class room doors have kicks stops installed prohibiting proper operation of self closing doors rem remove hardware
Jun 10, 2011
Resolve