DOB building violations

The newest 50 of 69 DOB violations. The city keeps the complete history.

  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 4, 2021

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 4, 2021

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 4, 2021

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 6, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 6, 2020

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 28, 2017

    Dob violation - resolved
  • Elevator elevatorrequired

    Cease use

    Apr 28, 2017

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 29, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 29, 2016

    Dob violation - resolved
  • Residential elevator periodic inspection/test elevatorrequired

    Failure to perform category 5 inspection

    Jun 1, 2016

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2014 inspection report

    Oct 1, 2015

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2014 inspection report

    Oct 1, 2015

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2014 inspection report

    Oct 1, 2015

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 12, 2014

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 29, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 22, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 22, 2012

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2011 inspection/test

    Oct 1, 2012

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2010 cat 1 insp/tst

    Aug 15, 2012

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 26, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 13, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 13, 2010

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Vcat1-elevator annual inspection / test elevatorrequired

    Oct 8, 2010

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Lblvio-low pressure boiler boiler required

    Dec 31, 2009

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Lblvio-low pressure boiler boiler required

    Dec 31, 2009

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Lblvio-low pressure boiler boiler required

    Dec 31, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 23, 2007

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Nov 19, 2004

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Feb 19, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 10, 2000

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 20, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed

ECB violations

The newest 50 of 73 ECB violations. The city keeps the complete history.

  • Class - 2

    Failure to maintain building in code-compliant manner: no fire stopping per bc 712.3; 27-345. noted: in electric meter room, fire stopping was missing around pipes. remedy: provide/maintain fire stopping.

    Mar 2, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: emergency light did not work when tested at, cafeteria "4 lights

    Mar 2, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: interiorsmoke doors do not self-close properly at, 4th flr-smoke door near rm #411, and 427. 3rd flr-smoke door near rm #328. 2md flr-staircase "g".

    Mar 2, 2026 · Penalty $1,250

    Active
  • Class - 2

    Re-issue #35691616l. failure to maintain building in code-compliant manner. noted: mortar cracking above exp 1. above noted letters. crackedbrick exp 2 a few corridors down from exit m3. remedy: repair and/or r

    Mar 2, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code compliant manner.exit 2 doors do not open had to be kicked open door on left,door on right also hard topush.room 158 door frame rusted large holes and parts missing at base

    Mar 19, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue#35679009h failure to maintain building in code-compliant manner.mortar cracking and falling and above grass exp 1 above noted letters,cracked brick exp 2 a few corridor down from exit m3.rem:repair and/

    Mar 19, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35679010p failure to maintain building in code-compliant manner.section of roof lifting up later coming apart by chimney.rem:repair and/or replace.

    Mar 19, 2025 · Penalty $3,125

    Resolve
  • Class - 2

    Federal boiler model-nyps2125. btu-7,875,000. boiler not registered. also missing ladder and platform by boiler. correct violating conditions and submit a certificate of correction.

    Aug 13, 2024 · Penalty $625

    Active
  • Class - 2

    Federal boiler model-nyps2125. btu-7,875,000. boiler not registered. also missing ladder and platform by boiler. correct violating conditions and submit a certificate of correction.

    Aug 13, 2024 · Penalty $625

    Active
  • Class - 2

    Federal boiler model-nyps2125. btu-7,875,000. boiler not registered. missing ladder and platform at boilers. correct violating conditions and submit a certificate of correction.

    Aug 13, 2024 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. section of rooflifting up, layer coming apart by chimney. remedy: repair and/or replace.

    Apr 9, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. mortar crackingand falling out above grass area at exp. 1 above metal letter, bricks cracking by window exp. 2 a few windows down from exit m3. cracking of

    Apr 9, 2024 · Penalty $625

    Active
  • Class - 2

    Reissue#35663168z.exit door not self-closing.noted 4th floor rm 411,3rd floor rm 328,2nd floor stair g,1st floor gym right rear,exterior door at exit m2,exit#2 and cafeteria.remedy:comply with code.

    Mar 6, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner:no fire stoppingper bc 712.3;27-345. noted:the electrical meter room at cellar level has holes above the entrance door and on the ceiling in various areas t

    Jun 9, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner:illumination forexits,exit discharges and public corridors per bc 1006.1;27-381. noted:at gymnasium entrance em#27 by 138,gymnasium,small cafeteria em#40,1s

    Jun 9, 2022 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self-closing. noted:at 4th fl level smoke by 411,3rd fl smoke by 328,2nd fl stair g by 201,stair c by 232,1st gymnasium right rear,exterior door at exit m2,exit 2,exit 13,large cafeteria exterior

    Jun 9, 2022 · Penalty $625

    Resolve
  • Class - 1

    No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. file application, install dlm, and perf

    Aug 27, 2020 · Penalty $1,250

    Resolve
  • Class - 1

    No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. file application, install dlm, and perf

    Aug 27, 2020 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner illumination forexits,exit discharges and public corridors per bc 1006.1;27-381. noted:at 1st fl gym and auditorium emergency lights out/non operational thr

    Mar 18, 2019

    Resolve
  • Class - 2

    Exit door not self closing noted: at 1st fl hallway doors near elevator, exit m4 self closers/door checks are in disrepair/non operational. remedy: repair/replace door

    Mar 18, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. noted:at 4th flhallway double doors near rm 411,2nd fl stair e,c,g,1st fl exit m1,stair g,exit m4 and auditorium doors are in disrepair/racked. remedy:repa

    Mar 18, 2019

    Resolve
  • Class - 2

    36,50. found federal mod #nyps2125 steam boiler not registered. 50- missing ladder and work platform. register boiler and correct all violating conditions. submit a certificate of correction.

    Sep 25, 2018

    Active
  • Class - 2

    36,50. found federal mod #nyps2125 steam boiler not registered 50-missing ladder and work platform; register boiler and correct all violating conditions and submit a certificate of correction.

    Sep 25, 2018

    Resolve
  • Class - 2

    36,50. found federal nyps 2125 steam boiler not registered; 50-missing ladder and work platform. register boiler and correct all violating conditions. and submit a certificate of correction.

    Sep 25, 2018

    Active
  • Class - 2

    Reissue#35225807x noted: at time of observed on the 2nd fl corridor fire proof sepf closing door adjacent to room#233 are inoperable door isrubbing on the floor & does not close. need to be repair or replace do

    Jan 25, 2018

    Resolve
  • Class - 2

    Reissue# 35145026n. noted: @ time of insp, on the 2nd flr corridor fireproof self closing door adjacent to room# 233 are inoperable, door is rubbing on the flr & does not close. rem: repair/replace door.

    Feb 22, 2017

    Resolve
  • Class - 2

    Exit door not self closing re-issue #35147513j.noted:@the 2nd flr nearstaircase"c" &beside room 233;found corridor smoke doors not self closing &the doors jams on flr.reissue:35147513j.rem:comply w. code.

    Mar 31, 2016

    Resolve
  • Class - 2

    Exit door not self-closing.not:@ 2nd fl near rm 233 corridor smoke doors not closing.stwy"f"(6)door is racked.rem:repair/replace doors.comply w/ notice of violation.

    Sep 30, 2015

    Resolve
  • Class - 2

    Defective emergency lighting @ gym,caferteria,auditorium multiple fixtures not operational.rem:repair/replace fixtures.

    Apr 9, 2014

    Resolve
  • Class - 2

    27-766.reissue 35023254j.missing f.a.i in gas meter room bsmt.rem:provide fai.

    Apr 9, 2014

    Resolve
  • Class - 2

    27-766 reissue #34958132z no fresh air vent provided in gas meter room. rem:provide fresh air vent.

    Jun 18, 2013

    Resolve
  • Class - 2

    Fail to maintain.note:water penetrating thru roof over gym. rem:make necessary repairs.

    Jun 18, 2013

    Resolve
  • Class - 2

    Reissue #34958135y fail to maintain. note:@stair d concrete cracking @windows exposing lintels @1st & 2nd floors. rem:make necessary repairs.

    Jun 18, 2013

    Resolve
  • Class - 2

    Reissue 349185166 at stair d near windows concrete cracking exposing lintle & ceiling spalling at 1st & 2nd flrs. rem:repair concrete.

    May 1, 2012

    Resolve
  • Class - 2

    At east side loose mortar in joints at top level of 1st flr windows west side over ramp section of brick work has loose & missing mortar. rem:repair all mortar joints.

    May 1, 2012

    Resolve
  • Class - 2

    Roof over gym has become porous allowing storm water to leak into gym.rem:repair or replace roof.

    May 1, 2012

    Resolve
  • Class - 2

    27-766:reissue 34918513x gas meter room has no fresh air ventilation. rem:provide ventilation.

    May 1, 2012

    Resolve
  • Class - 3

    Defective plaster at 1st to 2nd fl stairway d spalling and missing plaster at middle landing rem; repair plaster surface

    Jun 10, 2011

    Resolve
  • Class - 2

    Defective door at 1st floor exit #1 one of 4 exit doors requires extreme excessive force to open rem: repair door to properly open and self close

    Jun 10, 2011

    Resolve
  • Class - 3

    Reissue #34827922n defective glazed block at adjacent to door at cafeteria 2 cracked and loose at convectors rem: repair replace as required

    Jun 10, 2011

    Resolve
  • Class - 2

    28-301.1 27-766 reissue #34827923p no vent at gas meter room at old school section the gas meter room adjacent to boiler room has no fresh air or mechanical ventilation small room has water meter and no window

    Jun 10, 2011

    Resolve
  • Class - 2

    Reissue #34827924r spalling stucco at court yard breeze way area 2 holes in stucco ceiling rem: repair stucco surface

    Jun 10, 2011

    Resolve
  • Class - 2

    Reissue 34791674l spalling stucco ceiling adjacent to exit 5/6 exterior court yard.remedy repair ceiling.

    Jan 27, 2010

    Resolve
  • Class - 2

    Reissue 34791675n missing fai in gas meter room remedy provide f a i

    Jan 27, 2010

    Resolve
  • Class - 3

    Reissue 34607632k,34712170j,34791673j,glazed block cracked lose at exit #31st flr exit 12 1st floor exit 2 1st floor also caferteria tiles loose under convectors remedy make safe.

    Jan 27, 2010

    Resolve
  • Class - 2

    Re 34607632k defective doors roof access doors in staircase 3/4/ 5/6 corridor doors adjacent to m207,m109.also exit 12 vestibule door.remedyrepair doors.

    Jan 27, 2010

    Resolve
  • Class - 2

    Reissue 34712171l 34791672h roof parapet stone cap anchor bolts severly rusted & corroded remedy make repairs.

    Jan 27, 2010

    Resolve
  • Class - 1

    Bulging brick @ cafeteria ramp exit outside 1st floor affected area approx snxx10m remedy make safe fortwith.

    Jan 27, 2010

    Resolve
  • Class - 3

    Defective doors/hardware roof doors 3/4 & 5/6 corridor smoke door by room 428 door jamb loose stair 12 1st flr. remedy: repair/replace doors,jambs,hardware as needed.

    Jun 11, 2009

    Resolve
  • Class - 2

    No fresh air vent gas meter room in old building. remedy: supply ventilation.

    Jun 11, 2009

    Resolve