Violations at 81-51 261 Street

Queens, NY 11004 · BBL 4-08717-0001 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

No DOB violations on record

ECB violations

45 ECB violations, newest first.

  • Class - 2

    Failure to maintain building in code-compliant manner. noted: interiorsmoke doors do not self-close properly at 3rd flr-"staircase c"-classroom doors do not self-close properly at, 3rd flr-303, 305, 308, 310, 3

    Feb 17, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted stair b and c bulkhead ceiling and walls spalling. remedy: repair and/or replace.

    Mar 6, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted at roof parapet railing 80 street is not 42". remedy: repair and/or replace.

    Mar 6, 2025 · Penalty $3,125

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at 3rd floor stair case c falling plaster due to water penetration.rem:make necessary repairs.

    Mar 21, 2024 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35672155y failure to maintain building in code-compliant manner.noted:at roof top parapet at 80 street side is less than 42".rem:provide parapet/protective railing.

    Mar 21, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35643135y.failure to maintain building in code compliant manner.noted at time of inspection,observed roof level parapet wall at exp2is less than 42" on 80th street side.remedy:repair and/or replace.

    Feb 24, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner.noted:observed duringinsp of roof level parapet wall@exp2(80thst) is <42" in ht repair &or replace

    Mar 30, 2022 · Penalty $625

    Resolve
  • Class - 2

    Reissue35546599h failure to maintain bldg in codecompliant manner.illumination for exit exit discharges&public corridor per bc1006.1-27-381 noted:observed during insp of emergency lights@cafeteria&gym 1light in

    Mar 30, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner.illumination for exits,exit discharges&public corridors per bc1006.1;27-381@1fl lunchrm1place 1light(right side from ent.)@1st fl auditorium 2place each place 1l

    Feb 17, 2021 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self closing. noted: at the 3rd fl by 218(stair c).staira by 313,stair b at the 2nd fl by 205 & 1st fl stair b by 102;the exitdoors are not working properly. remedy: repair/replace door.

    Feb 4, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. noted: the emergency lighting outside the cafateria by exit 6 & at the auditori

    Feb 4, 2020 · Penalty $625

    Resolve
  • Class - 2

    28-301.1;unlawful dispplay of artwork in corridors greater than 20% per fdny 2008 code :fc 803.3.2.noted:artwork displayed in corridoes throughout the building is greater than 20% allowed.comply with notice of

    Mar 5, 2019

    Resolve
  • Class - 2

    Reissue#35177549z failure to maintain bldg in code compliant manner. noted: water penetration at various rooms at 3rd fl throughout due to parapet leak. remedy: make necessary repairs.

    Mar 15, 2017

    Resolve
  • Class - 2

    Work w/out a permit.noted:@cellar 10 burner gas stove connected to gasline w/out the range hood & suppression system.no range hood & (ansal)system.rem:obtain or restore premises to prior legal condition.

    Apr 8, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner.noted:@rm 305 spalling plaster due to water penetration from parapet leak & various other locns @262 street side.rem:make necessary repair.

    Apr 8, 2016

    Resolve
  • Class - 2

    Failure to maintain in code-compliant manner.fsilure to provide wired glass vision panels per 27-371(b) noted:doors do not have wired glass vision panels throughout the bldg.rem:provide wired glass vision panel

    Apr 8, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg code compliant: lack of emergency lighting per bc 1006.1;27-542. noted: at 1st fl cafeteria,approx 50% inoperative emergency lighting w/battery back up over exit doors. remedy: comply

    May 11, 2015

    Resolve
  • Class - 2

    Illumination for exits defective. note exit lights not operating, locations. exit 8 (gym) (1). exit b 2nd fl (2). exit b 3rd fl (2). remedy: repair or replace defective exit lights.

    Jul 15, 2014

    Resolve
  • Class - 2

    Defective doors at 2fl corridor door doors dragging not closing properly rm: repair replace doors

    May 31, 2012

    Resolve
  • Class - 2

    Plaster damage in rooms 303 305 313 321 around windows also auditorium spalling plaster rem; repair walls

    May 31, 2012

    Resolve
  • Class - 3

    Defective plaster. spalling & crumbling plaster at stairway b bulkhead & gym windows. remedy: repair plaster surface.

    Jul 7, 2011

    Resolve
  • Class - 3

    Reissue #34835473r plaster damage. spalling plaster at various 3rd fl rooms & auditorium. remedy: repair plaster.

    Jul 7, 2011

    Resolve
  • Class - 1

    Lack of directional exit lighting on 1st flr at center of corridor andends of corridor on 1st flr. - haz - remedy: install exit signage.

    Mar 10, 2010

    Resolve
  • Class - 3

    Plaster damage in rooms 309,305,303,318 and auditorium. remedy: repairwall.

    Mar 10, 2010

    Resolve
  • Class - 2

    Interior exit door at stairway "c" 2nd floor level is defective. noted: door closer is broken casuing door not to close properly. rem;repair/ replace defective closer.

    May 15, 2009

    Resolve
  • Class - 2

    Exterior brick facade is cracked located on the 2nd floor (corner of 261 street & school yard) approximately 1' foot long between windows. rem: repair/replace brick facade.

    May 15, 2009

    Resolve
  • Class - 2

    The plaster on the ceiling is spalling located in room 124 (library) on the 1st floor floor level. rem: repair/replace plaster.

    May 15, 2009

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: plaster is spalling on the walls located in room 219 on the 2nd flr level. remedy:repair and or replace plaster on walls.

    Aug 19, 2008

    Resolve
  • Hazardous

    Reissue #34519169h.no firestopping provided in electrical room in basement at 1-ceiling,2-above door frame.remedy:provide/maintain fire stopping.

    Jun 19, 2007

    Resolve
  • Hazardous

    No fire stopping was provided in electrical room:1)above door frame;2)in wall. remedy:provide/maintain fire stopping.

    Apr 11, 2006

    Resolve
  • Hazardous

    Doors in rooms 216;cafeteria (2 doors) 1st floor by exit. not self-closing. remedy:repair/replace door/hardware.

    Apr 11, 2006

    Resolve
  • Non-hazardous

    Reissue #34279070h.chimney @ roof,bricks are loose and missing mortar.remedy:repair brickwork/chimney.

    May 20, 2005

    Resolve
  • Non-hazardous

    Failure to maintain noted in gymnasium at top of all windows sills concrete cracked & spalling remedy:make all necessary repairs

    Mar 1, 2004

    Resolve
  • Non-hazardous

    Failure to maintian noted in auditorium ceiling at rear due to sustained water damage plaster is cracked peeling and porous.remedy:make all necessary repairs.

    Mar 1, 2004

    Resolve
  • Non-hazardous

    50 50 pipe down valve discharge to a safe point to prevent scalding of persons and damaging equipment

    Jan 7, 2004 · Penalty $2,500

    Resolve
  • Non-hazardous

    50 50 install pipe down to safety valve discharge to prevent scalding of persons and damage equipement

    Jan 7, 2004 · Penalty $2,500

    Resolve
  • Non-hazardous

    Failure to maintain defect windows old many non operable allowing cold air to infiltrate remedy obtain permit make all repairs

    Nov 5, 2003

    Resolve
  • Non-hazardous

    No panic hardware.upon inspection of the above address no panic hardware in place of assembly.(1)auditorium two stage door exits.remedy:provide panic hardware in place of assembly.

    Feb 15, 2001

    Resolve
  • Non-hazardous

    Failure to maintain.upon inspection of above address.(1)exit's #4 #5 bulkhead leading to roof has spalling plaster on walls & ceiling.(2)room'#102,#207,#221.93) gymnasium-at window area's wall's & ceiling.remed

    Feb 15, 2001

    Resolve
  • Non-hazardous

    Failure to maintain upon inspection of the above address 1.chimney at roof area is in need of pointing and has stress cracks thru-out it.remedy:make all repairs.

    Feb 15, 2001

    Resolve
  • Hazardous

    Failure to maintain upon inspection of the above address.the play ground is missing 90% of its seats.only cement is in place.this is a hazardous condition and trip hazard.remedy:make all repairs/make safe.

    Feb 15, 2001

    Resolve
  • Non-hazardous

    Failure to maintain upon inspection of the above address.1.fresh air dampers for boiler #2 is inoperable.2.fresh air damper for hot water is inoperable.remedy:make all repairs.

    Feb 15, 2001

    Resolve
  • Non-hazardous

    Failure to maintain. defect: no emergency lighting in bldg. peeling paint thru out entire bldg. windows old, many non operable, allowing cold air to infiltrate. remedy: obtain permit. make all repairs.

    Mar 8, 1999

    Resolve
  • Non-hazardous

    Failure to maintain (hazardous) windows all. defect is: windows thruout building have rotted wood sashes and frames in danger of falling outto streets and classrooms. remedy: repair and replace immediately.

    Jul 15, 1998 · Penalty $2,500

    Resolve
  • Hazardous

    Failure to maintain ( hazardous) deect is: window sashes are rotted and missing from several windows at 2nd and 3rd floors of building at front. glass panes are/loose and could fall to street below

    Jul 6, 1998 · Penalty $2,500

    Resolve