Violations at 61-25 Little Neck Parkway
Queens, NY 11362 · BBL 4-08361-0001 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
36 DOB violations, newest first.
- Elevator elevatorrequired
E-elevator elevatorrequired
Dec 30, 2020
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 6, 2019
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 28, 2018
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 14, 2017
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 6, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 11, 2014
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2013 inspection/test
Oct 31, 2014
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 2, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 25, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
May 21, 2008
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
May 23, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 27, 2003
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Elevator elevatorrequired
4p5197
Mar 12, 1999
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 13, 1997
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Jan 13, 1997
Dob violation - active - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 8, 1996
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Aug 29, 1995
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 17, 1995
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 7, 1994
Dob violation - dismissed - Elevator elevatoroptional
1
Apr 7, 1992
Dob violation - dismissed - Elevator elevatoroptional
1
Apr 25, 1991
Dob violation - dismissed - Elevator elevatoroptional
1
Jun 29, 1990
Dob violation - dismissed - Elevator elevatoroptional
1
Oct 12, 1989
Dob violation - dismissed
ECB violations
34 ECB violations, newest first.
- Class - 2
Failure to maintain building in code-compliant manner.noted no guardrails installed at all second floor parapet wall height is approx.28' height from the ground parapet wall height is approx.30' height guardrai
May 12, 2026 · Penalty $1,250
Active - Class - 2
Work without a permit.noted:at front of premises.installed illuminatedchanging sign without a permit.rem:obtain all required permit.
Jul 21, 2025 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: exit light for exit 6 door sign does not turn on when tested. re
Jul 21, 2025 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted:failure tomaintain classroom doors on 2nd flr rooms 219,205,203,201.1st flr rooms 101,102,105,108,118 & 120.and also in the basement at room 14 hallwa
Jul 21, 2025 · Penalty $1,250
Resolve - Class - 2
Exit doors not self-closing.noted:exit doors not self-closing on 2nd flr at exit 3 & 5.1st flr exits 10 & 11 and in basement at exits 13 & 14.rem:repair or replace.
Jul 21, 2025 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner-no fire stoppingper bc 712.3. failure to maintain firestopping in electrical room around conduits. remedy: put firestopping in areas that is needed.
Jul 21, 2025 · Penalty $1,250
Active - Class - 2
Failure to maintain bldg in codecompliant manner.noted:observed duringinsp of exterior 2fl window thruout,lintels rusting/oxidizing repair &/or replace
Aug 18, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in codecompliant manner.noted:observed duringinsp of roof level structure missing mortar,step cracks thruout.repair&/or replace
Aug 18, 2021 · Penalty $625
Resolve - Class - 2
Reissue #35452397m failure to maintain bldg in code-compliant manner. noted:at cellar level,gas meter room converted into a storage room! w/shelving full of chemical supplies & other misc. items/materials.remed
Jun 23, 2020 · Penalty $1,562
Resolve - Class - 2
Reissue #35452500l exit door not self-closing noted:at 2nd fl exit 4, exit door not self-closing due to defective door closer. remedy: repair/replace door.
Jun 23, 2020 · Penalty $1,562
Resolve - Class - 2
Exit door not self closing noted:at (2 floor) exit 4 door checkin disrepair/non operational when tested.remedy:repair/replace door.
Sep 18, 2019 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner illumination for exits,exit discharges and public corridors per bc 1006.1/27-391 noted:at (1st fl)cafeteria,gym and auditorium emergency lights ar non opera
Sep 18, 2019 · Penalty $625
Resolve - Class - 2
Failure to maintain buildig in code compliant manner.noted:at (2nd fl)exit 5(1st fl)exit 5,8,2,3 doors are in disrepair/cracked.remedy:repairand or replace.
Sep 18, 2019 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner.noted: at basement gas meter rm storage of various items/materials.remedy:comply with code.
Sep 18, 2019 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner.noted:at roof level bulkheads and machine room with water penetration/damage to walls and ceilings with cracks throughout in various location in maching rm.
Sep 18, 2019 · Penalty $625
Resolve - Class - 2
Reissue #35094514p (noted):@1st fl rm#102 & 2nd fl class rm#214 converted into 4 rms by erecting partition walls & separate doors.now class rms are 102a & 214a.rem:obtain permit.
Jul 25, 2018
Active - Class - 2
2x10,12q3,68m7. 2x10 in car phone inoperative.12q3 install guard on incar lights in car.68m7 missing mcp
Nov 2, 2017
Active - Class - 2
Defective battery packs for gym, auditorium, cafeteria emergency lighting, 1st floor. remedy: repair/replace battery packs.
Jun 3, 2014
Resolve - Class - 2
Re-issue # 35028020j. work without permit. conversion of multiple rooms throughout creating smaller rooms 1st/2nd floor. remedy: obtain permit.
Jun 3, 2014
Active - Class - 2
Reissue 34958072x work w/o a permit. noted: a partition wall has beenereted creating 3 separate rooms located in room 214 on the 2nd floor level. rmdy: obtain permit or change back to prior legal conditions.
Jul 29, 2013
Active - Class - 2
Work w/o a permit. noted: erected a partition wall in room 214 (2nd fl) subdividing into 2 separate rooms & installed a door in the corridorwall leading into 2nd room of 214. no permits filed at time of inspect
Jul 6, 2012
Active - Class - 2
Roof has become porous & allowing rain water into the building causing interior damages in room 201 (2nd floor). remedy: water proof roof.
Jul 6, 2012
Resolve - Class - 2
Corner of 61 ave and marathon pkwy a 3" inch high curb that is missingand cracked w/ exposed rebars showing rem: repair and/or replace 3"inch curb
Jun 23, 2011
Resolve - Class - 2
Reissue:34780087n.the electrical rm is lacking fire stopping above th e dr (metal grill) @ the cellar level.rem:provide/maintain fire-stopping
Mar 15, 2010
Resolve - Class - 3
50. fitzgibbon ftfb boiler lp stm oil, 1952. 50-referenced boiler structure has an elevation in excess of 8ft w/no fixed ladder for access to top of the unit.install a fixed steel ladder & platform for use by
Sep 25, 2009
Resolve - Class - 3
X0. fitzgibbon ftfb lp stn boiler, oil, 1952. 50-referenced boiler structure has an elevation in excess of 8ft w/no fixed ladder for access to the top of the unit.install a fixed steel ladder & platform for use
Sep 25, 2009
Resolve - Class - 2
The electrical room is lacking fire-stopping located at the cellar level. remedy: provide/maintain fire-stopping in the electrical room.
Jun 30, 2009
Resolve - Class - 2
Interior wall has a horizontal crazy above the chalkboard in room 201 on the 2nd flr level. remedy: repair/replace interior cracked wall.
Sep 16, 2008
Resolve - Non-hazardous
Water penetration through roof into room #202.remedy:stop water penetration make all necessary repairs.
May 24, 2005
Resolve - Non-hazardous
Failure to maintain. noted at cellar in rear of auditoriun due to sustained water. damage plaster craked, peeling and porons. make all necessary repairs.
Mar 10, 2003
Resolve - Non-hazardous
Failure to provide adequate emergency power exit lights on the 2nd floor and stair.failure to provide emergency power to exit lights on the 2nd floor and stair.failure to provide emergency power to exit-directi
Apr 30, 2001
Resolve - Non-hazardous
No panic hardware.upon insepction of the above address.the following places assembly have no panic hardware.auditorium-one stage door exit.gymnasium-all 4 exit doors.rem:install panic hardware in place of assem
Jan 31, 2001
Resolve - Non-hazardous
Failure to maintain.upon insepction of the above address.the following rooms have spalling plaster on walls or ceiling or both.1)room #123,rm 218,#216.rem:make all repairs.
Jan 31, 2001
Resolve - Non-hazardous
Failure to maintain defect is:at front of bldg., provide handicap ramp.egress problem for handicap wheelchairs.remedy:maintain bldg. make repairs.
Apr 25, 2000
Resolve