Violations at 86-35 235 Court
Queens, NY 11427 · BBL 4-07955-0002 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
8 DOB violations, newest first.
- Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 1, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 1, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed
ECB violations
The newest 50 of 56 ECB violations. The city keeps the complete history.
- Class - 2
Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:at the lobby emg light#4 does not work when tested & 1st floor corrido
Feb 18, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:interior doors do not self-close properly at 1st flr-exit 8.classroom doors do not self-close properly at 2nd flr-214,213,212,211,209,208,207,206,205
Feb 18, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner,noted:at cellar gas room,coal bunker and coal shaft water penetration from foundation wall and doors.rem:repair and/or replace.
Mar 3, 2025 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted at exits 2,7 and 8 saddles in disrepair tripping hazards.rem:repair and/or replace.
Mar 3, 2025 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted at 3 floorat gym,301,305 and floor exit 5-6 water penetration at ceilings from roofs.rem:repair and/or replace.
Mar 3, 2025 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted at bulkheads stair b & f spalling at door and ceiling.rem:repair and/or replace.
Mar 3, 2025 · Penalty $1,250
Resolve - Class - 2
Exit door not self-closing. noted at 1st floor smoke at stair f, exit 1, 9 and auditorium left and exit 10 doors are misaligned not closing.remedy: repair/replace door.
Mar 3, 2025 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: at gym a emergency exit lighting found inoperational when tested
Mar 15, 2024 · Penalty $625
Resolve - Class - 2
Exit door not selfclosing properly@1fl exit7 inside 1door@1fl exit6 1door outside&@2fl exit7 1door not selfclosing properly@time of insp.repair/replace door.
Feb 18, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner illumination forexits,exit discharges and public corridors per bc 1006.1;27-381 at 1stfloor lunch room 3 plaches each place 2 light existing emergency light
Aug 28, 2020 · Penalty $625
Resolve - Class - 2
Exit door not self closing 1st floor way to 235 court 1 door is not self closing at 1st floor exit-7 middle door 2 door not self closing properly at the time of inspection.rem:repair/replace door.
Aug 28, 2020 · Penalty $625
Resolve - Class - 2
Sec. 28-301.1 unlawful display of artwork in corridors greater than 20% per fdny 2008 code;fc 803.3.2. noted: artwork displayed in corridors,on the doors,hanging off the ceiling is greater than 20% allowed.
Feb 11, 2020 · Penalty $1,250
Resolve - Class - 3
Reissue #35177523k failure to maintain building in code compliant manner. noted: exit door to play yard from room 102 corroded and deteriorated metal frame at bottom where attached. rotted. rmdy:repair/repl
Mar 7, 2017
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner.failure to provide wired glass vision panel per 27-371(b).noted:doors & exit doors do not have (1/4") wired glass vision panels throughout the bldg.rem:provide
Mar 31, 2016
Resolve - Class - 3
Reissue #35128482m failure to maintain bldg in code-compliant manner.noted:exit door to play yard from rm#102,corroded & deteriorated metal from @bottom where attached rotted.rem:repair or replace.
Mar 31, 2016
Resolve - Class - 2
Failure to maintain building code compliant per bc 1016.2; 27-369. noted: at corridor adjacent to room 102,partial obstruction of corridor w/table,chairs and combustible artwork and supplies leaving 4 1/2'pass
May 8, 2015
Resolve - Class - 3
Reissue 35099741h failure to maintain bldg code complaint. noted: at exit door form room 102, the aluminium buck/frame is corroded and rotted through at bottom. rmdy: comply w/code, repair or replace.
May 8, 2015
Resolve - Class - 3
Fail to maintain. note corroded & deteriorated metal door frames 1)@bottoms where attached. quantity/location: 2)exit #2 to street from auditorium. 3)exit to play yard from rm #102. rem:maintain & replace defec
Jul 14, 2014
Resolve - Class - 2
No fresh air vent in gas meter room.rem:provide fresh air.
May 24, 2012
Resolve - Class - 2
27-765)no ventilation in occupied rooms 114d office setup w/ students.rem:provide ventilation as per code.
May 24, 2012
Resolve - Class - 2
Sec. 712.3;27-345 missing fire stop. at cellar level electric room,fire stop missing at conduit penetrations. remedy: provide required fire stop.
Jul 6, 2011
Resolve - Class - 2
Storage in gas meter room. cellar level gas meter room has storage of old & new maintenances material. remedy: remove all items maintain room clear.
Jul 6, 2011
Resolve - Class - 2
Reissue: 346983294. 1) auditorium exit leading to 235 ct the glazed blocks are separating away from each other. 2) the glazed blocks is missing mortar between blocks adjacent to rm 203 on the 2nd flr. remedy:
May 8, 2009
Resolve - Class - 2
Reissue: 34698328m. exterior 6" high curb is missing sections of concrete leaving exposed rebars located on 235 court next to the metal railing. remedy: replace missing sections of concrete.
May 8, 2009
Resolve - Class - 2
Reissue: 34698327k. the entrance way above the door is lacking fire-stopping located at the electrical rm at cellar level. remedy: provide/maintain fire-stopping.
May 8, 2009
Resolve - Class - 2
The plaster is spalling on the ceiling located above the auditorium exit door leading up to 235 court on the 1st fflr level. remedy: repair/replace plaster on ceiling.
May 8, 2009
Resolve - Class - 2
Reissue: 34698330l. the gym's wooden floor is sinking approx 2" adjacent by the water fountain on the 1st flr level. remedy: repair/replace wooden flrs.
May 8, 2009
Resolve - Class - 2
Failure to maintain bldg in code compliant manner gym wooden flr is sinking into the ground adj to the water foundation on the 1st flr levelremedy: repair and or replace wooden flr in gym.
Aug 22, 2008
Resolve - Class - 2
Failure to maintain bldg in code compliant manner noted: glazed block wall is separating and cracking by 2nd flr leading to roof level next to room 203. auditorium front exit on the 1st level leading to 235
Aug 22, 2008
Resolve - Class - 2
Failure to maintain bldg walls or appurtenances. noted: concrete 6" inches high is spalling w/ missing chunks of concrete located at 235 co urt adj to the railing and metal grade at street level. remedy: maint
Aug 22, 2008
Resolve - Class - 2
Reissue: 34577720x failure to maintain bldg in code compliant manner. noted: entrance door above the electrical room is missing fire stopping at cellar level. remedy: repair and or replace fire stopping at
Aug 22, 2008
Resolve - Hazardous
No fire stopping provided in electrical room in basement above entrance door frame & holes in door leafs.reissue #34519206h.remedy:provide/maintain fire stopping.
Jun 19, 2007
Resolve - Hazardous
Reissue #34519204y.missing & displace mortar & bricks location.east parapet(interior)at bottom middle section.chimney near top.3-2fl west facade at middle at corner of window(brick missing approx 2" x 3".remedy
Jun 19, 2007
Resolve - Non-hazardous
Illegal hardware (door knobs in exit dr at stair) in place of assemblyauditorium/p.a occupancy 402 p) installed remedy:remove/replace illegal hardware
Apr 17, 2006
Resolve - Non-hazardous
No fire stopping provided in electrical rm in bsmt above entrance dr frame & holes in dr leafs remedy:provide/maintain fire stopping
Apr 17, 2006
Resolve - Non-hazardous
Water penetration in roof (ceiling above the stage in auditorium 1st fl) remedy:provide waterproofing
Apr 17, 2006
Resolve - Non-hazardous
Reissue# 34474889j missing & displaced mortar & bricks location:east parapet (interior side), chimney; near top west facade, 2nd fl, south corner, brick missing over windows. remedy:repair defective brickwork
Apr 17, 2006
Resolve - Non-hazardous
Missing & displaced mortar & bricks locaiton :east parapet(interior side)chimney near top west facade 2nd floor south corner brick is missing over window remedy:repair defective brickwork
Apr 8, 2005
Resolve - Non-hazardous
Panic bar inoperative location:auditorium left front exit door cpa occupancy 402 remedy:repair/replace defective panic bar
Apr 8, 2005
Resolve - Hazardous
Failure to maintain.noted in cellar at boiler room southeast wall column has major structural crack(horizontal)runing through the side of column.*reissue* remedy: make safe immediately.make all necessary repair
Feb 13, 2004
Resolve - Non-hazardous
Use of illegal hardware.noted;padlock/sliding bolt installed at:(1) exit #1 leading to street(2) exit #2 leading to exit from corridor.remedy:remove illegal hardware.
Feb 13, 2004
Resolve - Non-hazardous
Failure to maintain.noted in rm 103 vertical structural cracks in block at window.remedy; make all necessary repairs
Feb 13, 2004
Resolve - Non-hazardous
Failure to maintain.noted: in rm 203 vertical structural cracks in block at window.remedy: make all necessary repairs
Feb 13, 2004
Resolve - Non-hazardous
Failure to maintain.noted: in cafeteria southeast wall.column eight foot vertical structural crack.*reissue* remedy: make all necessary repairs
Feb 13, 2004
Resolve - Non-hazardous
Failure to use panic hardware where required by law.noted: in gymnasium at hallway exit.door knob in use.occupancy load is 300+panic hardware required. remedy: provide panic hardware.
Feb 13, 2004
Resolve - Non-hazardous
Failure to maintain noted in cafeteria southeast wall. column has vertical structural crack. make all necessary repairs.
Mar 21, 2003
Resolve - Non-hazardous
Failure to maintain. noted in cellar at boiler room southeast wall. column has horizontal structural crack which runs from column thru wall.make all necessary repairs.
Mar 21, 2003
Resolve - Non-hazardous
Failure to use panic hardware where required by law location gym. remedy; provide panic hardware.
Aug 14, 2001
Resolve - Non-hazardous
Failure to maintain.upon inspection of the above address.(1)window throughout building are defective & inoperable.remedy:make all repairs/replacements.
Feb 16, 2001
Resolve - Non-hazardous
No panic hardware in place of assembly.upon inspection of the above address.the following places of assembly had no panic hardware on exit doors.exit doors.(3)gymnasium-four exit doors.
Feb 16, 2001
Resolve