Violations at 74-10 Commonwealth Blvd

Queens, NY 11426 · BBL 4-07870-0074 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

23 DOB violations, newest first.

  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 in 2020

    Jun 20, 2021

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to priv res elevator - fail to correct defects on 2017 cat 1 insp/tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 20, 2017

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 20, 2017

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to priv res elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to priv res elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 24, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 24, 2016

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2012 inspection/test

    Mar 31, 2014

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2012 inspection/test

    Mar 31, 2014

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 2, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 2, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 2, 2007

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Oct 1, 2005

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Nov 19, 2004

    Dob violation - dismissed

ECB violations

34 ECB violations, newest first.

  • Class - 2

    Failure to maintain building in code-compliant manner. no fire stopping per bc 712.3; 27-345. noted: electric meter room does not have fire stopping around any of the pipes. remedy: provide/maintain fire stoppi

    Feb 13, 2026 · Penalty $1,250

    Resolve
  • Class - 2

    28-301.1. unlawful display of artwork in corridors greater than 20% per fdny 2008 code; fc 803.3.3.2. noted: at the main entrance there was ribbons and makeshift stars hanging from the ceiling. remedy: comply w

    Feb 13, 2026 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: interiorsmoke doors do not close properly at 3rd flr-classroom doors do not self-close properly at, 1st flr-105. remedy: repair and/or replace.

    Feb 13, 2026 · Penalty $1,250

    Resolve
  • Class - 2

    Re-issue #35692404y. failure to maintain building in code-compliant manner. noted: at 3rd floor bulkhead "a" and bulkhead "c" water penetration through the wall. remedy: repair and/or replace.

    Feb 13, 2026 · Penalty $3,125

    Active
  • Class - 2

    Exit door not self-closing. noted at 3 floor smoke at stair b, (5) at exit 3 and exit 1 doors are not closing correctly rubbing. remedy: repair/replace door.

    Feb 27, 2025 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted at room 311 water penetration at ceiling. remedy: repair and/or replace.

    Feb 27, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain in code-compliant manner. noted at 3 floor corridor by 326 and 1 floor auditorium right #141 doors are not closing correctly. remedy: repair and/or replace.

    Feb 27, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue #35678912l. failure to maintain building in code-compliant manner. noted at 3 floor bulkheads a and c water penetration at celing shutter doors. remedy: repair and/or replace.

    Feb 27, 2025 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner: use at prohibited door and/or hardware per bc 1008.1.8; 27-371(j). noted: illegal kick down door holders are attached to the classroom doors throughout the

    Mar 21, 2024 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self-closing. noted: at gym at exit #7 both doors are not self-cosing. remedy: repair/replace door.

    Mar 21, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: at 3rd floor bulkhead "a" and bulkhead "c" water penetration through the wall.remedy: make necessary repairs.

    Mar 21, 2024 · Penalty $625

    Active
  • Class - 2

    Reissue#35654959k(4/9/2022)failure to maintain building in code-compliant manner:stepping patterns on foundation wall in cellar electrical &gas meter rooms.rem:repair and or replace.

    Feb 23, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner.noted:@cellar level electrical&gas meter rm;have running step cracks aprx3'-4'l above entrance door.repair &or replace

    Apr 9, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner:illumination for exits,exit discharges&public corridors per bc1006.1;27-381.noted:@gym above exit7;exit sign inop.repair/replace lighting.

    Apr 6, 2022 · Penalty $625

    Resolve
  • Class - 2

    Exit door not selfclosing.noted:gym exterior exit door7 isnt working properly.repair/replace door.

    Apr 6, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner:use of prohibited door &or hardware per bc1008.1.8;27-371j.noted:there are kickdown door holders installed on various classrm doors thruout bldg.provide legal ha

    Apr 6, 2022 · Penalty $625

    Resolve
  • Class - 1

    No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. file application install dlm and perfor

    Feb 25, 2021 · Penalty $1,250

    Resolve
  • Class - 1

    No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. file application install dlm and perfor

    Feb 25, 2021 · Penalty $1,250

    Resolve
  • Class - 2

    Exit door not self closing properly at 3rd fl near stair case'c'middleexit door no 1 is not self closing properly at the time of inspection when tested. remedy: repair/replace door.

    Feb 12, 2021 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self closing at 3rd floor corridor exit door near room no 326 one door,at 1st floor auditorium door no-9 one door not self closing properly at gymnesium at 1st floor door no-7 two doors exit door

    Aug 27, 2020 · Penalty $625

    Resolve
  • Class - 2

    Sec. 28-301.1 unlawful display of artwork in corridors greater than 20% per fdny 2008 code;fc803.3.2. noted: artwork displayed in corridors & hanging off the ceiling is greater than 20% allowed per fdny codes.

    Feb 10, 2020 · Penalty $1,250

    Resolve
  • Class - 2

    B254, 50a-50b. 50a-backflow preventor missing gapper and discharge 50b-pittail on pressure gauge to be brass.

    Oct 2, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner. note: at inspection1st floor in gym air duct cover hanging and loose with potential fall hazard. rmdy: repair and/or replace.

    Feb 8, 2018

    Resolve
  • Class - 2

    28-201.1 reissue #35177799l. unlawful displa of artwork in corridors greater than 20% per fdn 2008 code; fc1027.4. noted: excessive artworkdisplayed in the corridors and hanging from ceiling is greater than 20

    Mar 9, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: @ 1st flr, paper decorations are plastered& hanging from ceiling throughout the bldg creating a fire hazard. rem: remove the paper decorations.

    Apr 21, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: @ 3rd flr @ room 340 water penetration from the roof causing ceiling tiles soiled. rem: make necessary repairs.

    Apr 21, 2016

    Resolve
  • Class - 2

    Reissue: 34697638n exterior concrete high wall is cracked & missing chunks of concrete locate at the courtyard,wall is approx 1'feet high. exterior brick facade is cracked located on the 2nd flr level on commen

    Apr 30, 2009

    Resolve
  • Class - 2

    Failure to maintain building in code-complaint manner. noted: glazed wall tiles are cracked vertically located in the girls locker room adjacent to the entrance door. remedy: repair and/or replace entrance door

    Aug 21, 2008

    Resolve
  • Class - 2

    Reissue: 34577526y failure to maintain building walls or appurtenancesnoted: roof has become porous and allowing rain water into the building causing interior damages in room 302 3rd flr level. remedy: maintain

    Aug 21, 2008

    Resolve
  • Class - 2

    Failure to maintain building walls or appurtenances. noted: concrete 1'foot high wall is cracked with missing chucks of concrete located at the courtyard. brick corner 2nd flr level adjacent to common wealth bl

    Aug 21, 2008

    Resolve
  • Hazardous

    Water penetration through the roof into room #302.remedy:stop water penetration/make all necessary repairs.

    Jun 20, 2007

    Resolve
  • Hazardous

    Illegal hardware installed in exit door gymnasium (door holder) remedy:remove illegal hardware

    Apr 10, 2006

    Resolve
  • Hazardous

    Exit door by main entrance not self closing.remedy:repair/replace door/hardware

    Apr 10, 2006

    Resolve
  • Hazardous

    Water penetration through thr roof in rooms # 340;302 also in bulkheads stair a & c.remedy:provide waterproofing

    Apr 10, 2006

    Resolve