Violations at 75-25 Bell Boulevard
Queens, NY 11364 · BBL 4-07753-0001 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
4 DOB violations, newest first.
- Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed
ECB violations
The newest 50 of 61 ECB violations. The city keeps the complete history.
- Class - 2
Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. at 1st fl. gym exit-a8 one exit light, at 1st floor auditorium 3 emerge
May 14, 2026 · Penalty $1,250
Active - Class - 2
Exit door not self closing.noted:at 1st fl exits 11 & 3(2nd fl)exit 6 and 3rd fl staircase c all doors in disrepair/not closing when tested.rem:repair/replace door.
Jul 16, 2025 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:at 1st fl auditorium and cafeteria emergency lights not working when t
Jul 16, 2025 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code compliant manner.noted:at 1st fl cafeteria ceiling tiles loose/falling with water damage/staining throughout various areas.rem:repair and/replace.
Jul 16, 2025 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner.door frames rusting at base on both sides of frame of exit 4 and units 2,4,5 in boilerroom for ems lights.rem:repair and/or replace.
Jul 11, 2024 · Penalty $625
Resolve - Class - 2
Reissued35577568r failure to maintain bldg in codecompliant manner.noted:atoi observed@roof level parapet walls below42"&missing fence &or railing in 1sec of roof all 4side of corner.repair &or replace roof fen
Jun 23, 2022 · Penalty $1,562
Resolve - Class - 2
Reissued35577569z failure to maintain bldg in codecompliant manner.atoi observed@3fl rm311,315b,318,312&2fl rm214&1fl rm117a door arent working properly when i tested during insp repair &or replace doors
Jun 23, 2022 · Penalty $1,562
Resolve - Class - 2
Failure to maintain onsite document.upon request for 6 moth periodic insp as per bc 3307.6.5.8 and daily inspection log bc 3307.6.5.10.1 for sidewalk shed in place along perimeter on bell blvd (exp #1) & 217 st
Oct 4, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted:observed at basement level water pooling on floor due to chimney leaking in storage room by hot water heater.rem:repair and or replace.
Aug 6, 2021 · Penalty $625
Resolve - Class - 2
Exit door not self-closing noted:observed during inspection exterior exit doors at exit 3,exit 7,exit 11 were not operational at time of inspection.rem:repair/replace door.
Aug 6, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted:observed during inspection,room#311,315b,318,214,117a and auditorium exit 8 fpscd were not operating or self closing at time of inspection.rem:repair
Aug 6, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner noted:observed roof parapet walls below 42 inches and missing fencing/railing in one section of roof.rem:repair and or replace.
Aug 6, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted:observed during inspection of boiler room area(near hot water heater)exit door to egress ladder was blocked by a gas pipe traveling vertical in front
Aug 5, 2021 · Penalty $625
Resolve - Class - 3
Reissue#35221843p failure to maintain bldg walls or appurtenances. noted: at roof,parapet is less than 36" in height. remedy: comply w/notice of violation.
Jun 19, 2020 · Penalty $500
Resolve - Class - 2
Exit door not self closing noted t (3rd fl) stair b,c (2nd fl) exits (1st fl) exit 1,2,3 ,10 (mam entry) door checks area is disrepair non opertaional repair/replace door
Sep 9, 2019
Resolve - Class - 2
Failue to maintain building in code compliant manner noted at (2nd fl) stair exit 6,5,5,a (1st fl) stair b eixt 3 ,8 1,,2,10 (main entry) doors are in disrepair/racked repair and or replace
Sep 9, 2019
Resolve - Class - 2
50a-50b.50c=easthond f.t.s.h. lp steam mobile boiler e8p 400 2015 50(a) mechanical fresh air supply not interlocked with burner operation.50(b) smoke alarm system not operating 50(c) evidence of leakage at safe
Mar 18, 2019 · Penalty $1,562
Resolve - Class - 2
Bc3307.6.4.9.obstructed sign.note:observed parking sign is partially obstructed by sidewalk shed parapet wall.rem:comply with code
Oct 11, 2018 · Penalty $625
Resolve - Class - 3
Failure to maintain wall(s)or appurtenances.noted:@roof,parapet high less than 36" (inches).rem:comply w.code.
Nov 29, 2016
Resolve - Class - 3
Failure to maintain bldg wall(s) or appurtenances.noted:@roof,chimney w.parging,spalling masonry.rem:comply w.code.
Nov 29, 2016
Resolve - Class - 3
Failure to maintain bldg in code compliant manner.noted:@bulkhead,interior,paarging and cracking masonry @door frame/wall.rem:comply w.code.
Nov 29, 2016
Resolve - Class - 2
Failure to maintain bldg in code compliant manner.noted:@auditorium,ceiling the missing several area.rem:comply w.code.
Nov 29, 2016
Resolve - Class - 2
Failure to maintain bldg in code compliant manner,no fire stopping perbc 712.3,27-345.noted:@gas meter run,penetrations @ceiling and wall(s).rem:comply w.code.
Nov 29, 2016
Resolve - Class - 3
Failure to maintain bldg in code compliant manner.noted:cars parked onnon public walkway/sitting area (public accessible).rem:comply w.code.
Nov 29, 2016
Resolve - Class - 2
Failure to maintain bldg in code complaint manenr,lack of emergency lighting for exit,exit discharges and public corridors per bc 1006.1,27-542.noted:emergency light now working when tested @gym (2 high hats, 2
Nov 29, 2016
Resolve - Class - 2
Reissue nov 34909721x.failure to maintain bldg wall(s) or appurtenances.noted:@217 street,spalling and cracked masonry,sagging lintels @windows for gym.rem:comply w.code.
Nov 29, 2016
Resolve - Class - 2
Water penetration to changing room stairwell from roof and or facade.standing water observed on landing 1 fl.stairwell adjacent to exit 9 1fl/note:stairwell is located behind auditorium wall having plaster dama
Feb 12, 2015
Resolve - Class - 2
Reissue 35074506p plaster damage @ auditorium wall,buckhead stair e,room 207.rem:maintain bldg
Feb 12, 2015
Resolve - Class - 2
@ kindergarden playyard along 217.st benches @ east end missing seating(guards)chipped & splintering wood edges.concrete bench bases have sections of concrete missing.rem:maintain premises.
Feb 12, 2015
Resolve - Class - 2
Reissue 35094507r kindergarden playyard retaining wall along 217st.leaning out of plumb.bldg outward @ west end.motar loose,missing,cracked kmany locations.rem:maintain bldg
Feb 12, 2015
Resolve - Class - 2
Occupancy contrary by the parking at front court yard, 7 cars noted in front yard & front of exit door. remedy: remove all cars.
May 22, 2014
Resolve - Class - 2
Mortar joints falling/missing from play yard retaining wall along 77 avenue, also multiple areas around parapet, corner stones, facade. remedy: make safe!
May 22, 2014
Resolve - Class - 2
Re-issue # 35028039j. plaster damage at room 207, auditorium, stair e bulkhead. remedy: repair walls/ceiling.
May 22, 2014
Resolve - Class - 2
Re-issue # 35028040r. defective lintel at teachers cafeteria near 217 street side, also sagging lintel at gym lintel 217 street side. remedy: replace lintel.
May 22, 2014
Resolve - Class - 2
Reissue: 34953950h. exterior window lintels are sagging adjacent to 217 street. remedy: repair/replace lintel.
Jul 26, 2013
Resolve - Class - 2
Reissue: 34953951j. the plaster on the wall is spalling located in thecloset of room 207 on the 2nd flr level. remedy: repair/replace plaster.
Jul 26, 2013
Resolve - Class - 2
The plaster on the wall is spalling located in the auditorium(1 flr) & storage closet room 207(2 flr).rem:repair &/or replace plaster.
May 11, 2012
Resolve - Class - 2
Gymnasium window lintels are sagging adjacent to 217 street.rem:replace window lintels.
May 11, 2012
Resolve - Class - 2
Corridor is being partially obstructed by a desk near room 311 on the 3rd flr level.rem:remove obstruction
May 16, 2011
Resolve - Class - 2
Reissue34835431z.exterior mortar between bricks is missing & loose & also sagging window lintels located on 217st side.rem:replace missing mortar & window lintels
May 16, 2011
Resolve - Class - 2
Exterior wall throughout bldg missing loose mortar joints also noted lintels sagging gym windows 217st side rem: make safe
Feb 24, 2010
Resolve - Class - 2
Reissue #34792684j plaster damage inside auditorium right side cracks forming on ceiling rem; make safe 2nd vio
Feb 24, 2010
Resolve - Class - 2
Reissue #34792683h missing firestopping around piping above door of electrical panel room rem: provide firestopping 2nd vio
Feb 24, 2010
Resolve - Class - 2
The plaster is spalling in the electrical room (at cellar level) & auditorium 1st flr level. remedy: repair/replace plaster on walls & ceiling.
Jun 22, 2009
Resolve - Class - 2
The electrical room is lacking firestopping at cellar level right above the door. remedy: provide/maintain firestopping.
Jun 22, 2009
Resolve - Class - 2
Reissue 34698849h. the concrete around the door frame (by the ash hoist) at cellar level is cracked. remedy: repair/replace concrete.
Jun 22, 2009
Resolve - Class - 2
Reissue 34698625z. exterior foundation wall has become porous and allowing rain into the bldg causing interior damages at cellar level on the north side. remedy: waterproof exterior foundation wall.
Jun 22, 2009
Resolve - Class - 2
Concrete around the exit door leading to the ash hoist at cellar level is cracked. remedy: repair/replace concrete.
Sep 18, 2008
Resolve - Class - 2
Ceiling tiles are missing approx 6 tiles near the windows at room 231 on the 2nd flr level. remedy: replace missing ceiling tiles.
Sep 18, 2008
Resolve - Class - 2
Plaster is spalling due to water penetration located at storage/located room in the kitchen 1st flr,cafeteria 1st flr level by exit #8. remedy: repair/replace plaster.
Sep 18, 2008
Resolve