Violations at 61-15 Francis Lewis Blvd
Queens, NY 11364 · BBL 4-07723-0001 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
The newest 50 of 82 DOB violations. The city keeps the complete history.
- Elevator elevatorrequired
E-elevator elevatorrequired
Sep 2, 2021
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 2, 2021
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 2, 2020
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 2, 2020
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 2, 2020
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 22, 2018
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 8, 2017
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2015 inspection/test
Dec 1, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 29, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 28, 2016
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 8, 2015
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 8, 2015
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 5, 2014
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 5, 2014
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2012 inspection/test
Mar 31, 2014
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 18, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 18, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 25, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 25, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 25, 2012
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2011 inspection/test
Oct 1, 2012
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2010 cat 1 insp/tst
Aug 15, 2012
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 25, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 25, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Oct 25, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 3, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 3, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 3, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 3, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 3, 2010
Dob violation - resolved - Low pressure boiler boiler required
Lblvio-low pressure boiler boiler required
Dec 31, 2009
Dob violation - dismissed - Low pressure boiler boiler required
Lblvio-low pressure boiler boiler required
Dec 31, 2009
Dob violation - dismissed - Low pressure boiler boiler required
Lblvio-low pressure boiler boiler required
Dec 31, 2009
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 8, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 8, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 8, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 27, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 27, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 27, 2007
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 2, 2007
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 25, 2007
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 25, 2007
Dob violation - resolved
ECB violations
The newest 50 of 66 ECB violations. The city keeps the complete history.
- Class - 2
Reissued ecb #35721237x. failure to maintain building in code-compliant manner. noted smoke doors not self-closing at: 1st floor #139, #139a, #115; 2nd floor #207, #212, #231; 3rd floor #319b. remedy: repair an
May 5, 2026 · Penalty $3,125
Active - Class - 2
Reissued ecb #35721234k. failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridorsper bc 1006.1; 27-381. noted emergency lights not working at: 1st floo
May 5, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code compliant manner.upon inspection:self closing doors did not operate properly 1st floor 139a,123,121,115a,2nd floor 207,212,231,3rd floor 322,319b basement gym door.rem:maint
Jul 18, 2025 · Penalty $1,250
Active - Class - 2
Reissue ecb#35677580h exit door not self-closing.noted exit door 3,13,& 14 needs excessive force to open and does not self-close.rem:repair or replace.
Jul 18, 2025 · Penalty $1,562
Active - Class - 2
Reissue#35677579k failure to maintain building wall(s)or appurtenancesnoted:at exp#1 front entrance,ada ramp surface are a with spalling,uneven concrete ramp creating a hazardous condition.rem:make necessary re
Jul 18, 2025 · Penalty $6,250
Active - Class - 2
Reissue#35677582l failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:emergency light at gym(5)3rd floor exit 11 stair g
Jul 18, 2025 · Penalty $3,125
Active - Class - 2
Reissue#35677584p failure to maintain building in code-compliant manner.noted at 3rd floor room 323.at 2nd floor rooms 207 and 220.loose electrical outlet board at floor creating tripping hazard.rem:make necess
Jul 18, 2025 · Penalty $3,125
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted:at room#323 loose electrical outlet board at floor creating a tripping hazard.rem:make necessary repairs.
Jul 19, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted:at gym,various ceiling tiles are missing.rem:replace ceiling tiles.
Jul 19, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner:illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted:at gym,5 emergency exit lighting found inoperational when tested.rem:r
Jul 19, 2024 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner:use of prohibited door and/or hardware per bc 1008.1.8;27-371(j).noted:at exit 15 doorkickdown door holder attached to exit door.rem:remove the illegal hard
Jul 19, 2024 · Penalty $625
Resolve - Class - 2
Exit door not self-closing.noted:exit door#4,6,9,11,12,13 need excessive force to open and do not self-close.rem:repair/replace door.
Jul 19, 2024 · Penalty $625
Active - Class - 2
Reissue#35676252y failure to maintain building wall(s)or appurtenancesnoted:at exp#1,front entrance,ada ramp surface area with spalling,uneven concrete ramp creating a hazardous condition.rem:make necessary rep
Jul 19, 2024 · Penalty $3,125
Active - Class - 2
Reissued #35665527k: failure to maintain building wall(s) or appurtenances. at exp #1 front entrance to ada ramp. surface area is spalling, chopped, exposure aggregate. remedy: replace/repair
Jul 28, 2023 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code compliant manner:illumination forexits,exit discharges and public corridors per bc1006.1;27-381.on 1st and 2nd floor public corridor emergency light and auditorium,cafeteria
Jun 21, 2022 · Penalty $625
Resolve - Class - 2
Reissue#35582408y.exit door not self-closing.noted 3rd floor smoke by 322,2nd floor stair by 236,and 1st floor stair by room 129 and also auditorium and gym,doors are not working properly.remedy:repair and/or r
Jun 21, 2022 · Penalty $1,562
Resolve - Class - 2
Reissue#35582410n.failure to maintain building walls or appurtenance.at time of inspection observed at exp1 non-public wheelchair ramp has spalling masonry in various areas throughout.also exp2 brick columns ha
Jun 21, 2022 · Penalty $3,125
Active - Class - 2
Reissue35498455p noted:@exp1,nonpublic wheelchair ramp has spalling masonry in various areas thruout.also,@exp2,brick columns have running stepcracks in several areas.maintain bldg walls@exterior.
Aug 6, 2021 · Penalty $3,125
Active - Class - 2
Reissue35498457z noted:@3fl staira by 315,1fl on#12 by staira,#13by116,#10@exit3@auditorium left stage&auditorium,#5 by entrance,bsmt level#3 by cafeteria entry,cafeteria,#4@stairg,#22girls locker by entrance,g
Aug 6, 2021 · Penalty $1,562
Resolve - Class - 2
Exit door not selfclosing (reissue35498458k)noted:@3fl smoke by 322,2fl smoke@staire by 236,1fl smoke@stairf by 129,cafeteria smoke by exit15,exterior exit doors#3@auditorium left stage,#14@gym,#12by102&exit7,e
Aug 6, 2021 · Penalty $1,562
Resolve - Class - 2
Exit door not self closing. noted: at 2nd fl stair a,e(1st fl),stair b,c,exits 3.8.7(basement)exit 15,boys/girls locker rooms door chechs were in disrepair/non operational when tested. remedy: repair/replace
Jun 24, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner illumination for exits,exit discharges & public corridors as per bc 1006.1/27-381. noted: at 1st fl auditorium(nbasement)cafeteria,boys/girls locker rooms & gym
Jun 24, 2020 · Penalty $625
Resolve - Class - 2
Failure to mantain bldg in code compliant manner. noted: at basement gas meter room w/having storage of various items & materials crates,ladders,chairs etc. remedy: comply w/code.
Jun 24, 2020 · Penalty $625
Resolve - Class - 2
Reissue ecb#35448083h failure to maintain bldg walls or appurtenances.noted: at exp#1 non public wheel chair ramp w/spalling/cracked masonryconcrete observed also at 2 brick/mortar columns. remedy: maintain ext
Jun 24, 2020 · Penalty $3,125
Active - Class - 2
Reissue ecb#35448086n failure to maintain bldg in code compliant manner. noted: at(2nd fl)stair e,f,(exits)9a,11(1st fl)stair b,exits 8,7(basement)girls locker rm,exit 14 doors are in disrepair/racked.
Jun 24, 2020 · Penalty $1,562
Resolve - Class - 2
Re-issue #35342134nl/failure to maintain building in code compliant manner.note:at 2nd floor at exit#9a,11,stair f,e,at 1st floor exits #7.#8,#11,#5,#9 interior/exterior,auditorium.at basement stair b,g,j boys
Sep 3, 2019
Resolve - Class - 2
Re-issue 335342133l/exit door not self closing.note:at 3rd floor #322 at 2nd floor exit #9 #11 and stair b,at 1st floor stair c exterior,at basement exits b,c and cafeteria exit.doors not self closing when test
Sep 3, 2019 · Penalty $625
Resolve - Class - 2
Re-issue 35342136r;failure to maintain building in code-compliant manner;no fire stopping per bc712.3;27-345.note:at basement level electrical meter room fire stopping is missing in various locations.rem;provid
Sep 3, 2019
Resolve - Class - 2
Re-issue #35342137z;failure to maintain building wall(s)or appurtenances.note:at exposure#1 non public wheel chair ramp observed spalling and cracked masonary also observed on (2)brick/mortor columns.rem:mainta
Sep 3, 2019
Active - Class - 2
Re-issue#35342138k;failure to maintain building in code compliant manner.noted:at basement level electrical meter room observed several vertical and horizontal/stepcracks on the wall.rem;repair and or replace.
Sep 3, 2019
Resolve - Class - 2
Failure to maintain building in code-compliant manner. noted: at 2nd floor staircase e to 3rd floor water penetration/damage to underside of steps/cicling plaster/paint bubbling/falling.rmdy: repair and/or re
Jul 5, 2018
Resolve - Class - 2
Failure to maintain building in code-compliant manner. reissue:352218484 issued 11/30/16 noted: at electric meter room vertical cracks and step oracles at walls. rmdy: repair and/or replace.
Jul 5, 2018
Resolve - Class - 2
Reissue #35222388r issued 11/30/16 failure to maintain bldg walls or appurtenances noted:@entry way (exterior) non public wheel chair ramp w/spalling/cracked masonary also 2 brick/mortor columns spalling missin
Jul 5, 2018
Active - Class - 2
Failure to maintain building in code-compliant manner. no fire stopping per bc 712.3, 27-345 noted: at basement electric meter room fire stopping missing/none in various locations. rmdy: provide/maintain fire
Jul 5, 2018
Resolve - Class - 2
Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1 27-381 noted: at 1st fl auditorium (basement) boys gym emergency lighting not
Jul 5, 2018
Resolve - Class - 2
Failure to maintain building in code-compliant manner. noted: 2nd flr exit 9a, 11, stair f, e (1st floor) exits 7,8,11,5,9, interior/exterior, auditorium (basement) stair b, g, j boys gym, exits, c,d, 14 inter
Jul 5, 2018
Resolve - Class - 2
Exit door not self closing noted: at 3rd floor hallway near room 322, 2nd floor exits 9,11, stair b, 1st floor stair c exterior, exits base ment exits, b,c, cafeteria exit 15, 3 self closers non operational
Jul 5, 2018
Resolve - Class - 2
Failure to maintain building in code compliant manner, no fire stopping per bc 712.3; 27-345. noted: all cellar at gas meter room, penetrations at ceiling. rmdy: comply with code.
Nov 30, 2016
Resolve - Class - 2
Failure to maintain building walls or appurtenances. noted: at entryway (exterior),non public wheel chair ramp with spalling, cracked masonry. rmdy: comply with code.
Nov 30, 2016
Active - Class - 2
Exit door not self closing. noted: at gym (exit 14) and at 2nd flr corridor (room 213) fpsc door not self closing. rmdy: comply w/code.
Nov 30, 2016
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. noted: at electric meter room, vertical cracks and step cracks at walls. rmdy: comply with code.
Nov 30, 2016
Resolve - Class - 2
Exit corridor width is partially obstructed by musical stands along with a full drum srt by the front of the auditorium exits on the 1st flr level.rem:remove obstructions
May 18, 2011
Resolve - Class - 2
67x10)in car emergency phone inoperative.
Jan 11, 2011
Resolve - Class - 3
Defective corridor door near rm 225 2fl door does not chase rem: replace door
Feb 18, 2010
Resolve - Class - 2
The plaster on the ceiling is missing, leaving a hole approx 5' in diameter located by the boys locker room & gymnasium at basement level. remedy: repair/replace plaster on ceiling.
Jun 15, 2009
Resolve - Hazardous
Interior classroom door is missing a door closer in room 329 on the 3rd fl. remedy:replace missing door check(closer)
Jul 3, 2007
Resolve - Hazardous
Foundation wall has become porous and allowing rain water in causing interior damages to room b3 on basement level. remedy: water proof foundation wall.
Jul 3, 2007
Resolve - Hazardous
Vertical cracks approx 7'l located on the chimney on roof level. on the east & west side. remedy: repair chimney cracks in bricks.
Jul 3, 2007
Resolve - Hazardous
Mortar is missing below window on the 2nd fl above exit # 6 btwn bricks.remedy:replace missing mortar.
Jul 3, 2007
Resolve - Hazardous
Plaster is spalling leaving a hole on the ceiling located in room b20 on basement level. remedy: repair plaster on ceiling.
Jul 3, 2007
Resolve