Violations at 35-01 Francis Lewis Blvd

Queens, NY 11358 · BBL 4-05261-0001 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

The newest 50 of 79 DOB violations. The city keeps the complete history.

  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2018 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2018 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2018 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 19, 2021

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 19, 2021

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 2, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 2, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 22, 2019

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 25, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 25, 2016

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 24, 2015

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2014 inspection/test

    Jun 10, 2015

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 21, 2014

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 10, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 26, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 26, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 21, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 21, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 2, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 2, 2010

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Vcat1-elevator annual inspection / test elevatorrequired

    Oct 8, 2010

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 28, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 28, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 9, 2008

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 25, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 25, 2007

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 2, 2007

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 24, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 24, 2006

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Oct 1, 2005

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 1, 2005

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Nov 19, 2004

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 21, 2004

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 7, 2004

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 21, 2003

    Dob violation - dismissed
  • Elevator elevatorrequired

    4s207

    Apr 22, 2002

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 2001

    Dob violation - dismissed

ECB violations

The newest 50 of 92 ECB violations. The city keeps the complete history.

  • Class - 2

    Failure to maintain building in code compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.at thetime of inspection observed and noted at basement level cafeteria 6 pl

    Jul 29, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissue#35719781r date of issue:05.29.2025 failure to provide ventilation to gas meter room per p115.6(1968 code)fgc appendix e(e4)(2014 code)at the time of inspection at cellar level gas meter rm no ventilatio

    Jul 29, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35719782z date of issue:05.29.2025 fpsc doors/exit doors/corridor exit doors not self closing properly for difective hardware,door closure or hinges 2nd fl exit-1 1 exit door,3rd fl exit-1 1 exit door,e

    Jul 29, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35719783k date of issue:05.29.2025 failure to maintain building in code compliant manner.at the time of inspection observed and noted at room 1313 ceiling at exterior in disrepair loose paines and board

    Jul 29, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue:35719748m date of issue:05.29.2025 failure to maintain building in code compliant manner.at the time of inspection observed and noted at roof over gym on francis lewis blvd exterior no guardrails in tha

    Jul 29, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue:35719785y date of issue:05.29.2025 failure to maintain building in code compliant manner.at the time of inspection observed and noted at auditorium large thick cable running on wall right side throw ent

    Jul 29, 2026 · Penalty $3,125

    Active
  • Class - 1

    Failure to maintain building in code-compliant manner. noted at exposure 3(back) outside exit 4 exterior fence collapsed in yard. remedy: repair and/or replace fence.

    May 29, 2025 · Penalty $2,500

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted at auditorium large thick cable running on wall right side throw entire area imposing hazard. remedy: remove wire.

    May 29, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted at roof over gym on(francis lewis blvd) exterior, no guardrails in place. remedy: install guardrails.

    May 29, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted at room b13 ceiling at exterior indisrepair, loose panels and board. remedy: repair and/or replace ceiling.

    May 29, 2025 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self-closing. noted at 2 floor smoke stair b, auditoriumright, 1fl.(s) stair h, f, g, main exits 9-10, 4, 7-8, doors are not closing properly. remedy: repair/replace door.

    May 29, 2025 · Penalty $625

    Active
  • Class - 2

    Reissue #35578335k. failure to provide ventilation to gas meter room per p. 115.6(1968) code), fgc appendix e(ey)(2014 code), noted at gas room no ventilation provided. remedy: provide ventilation.

    May 29, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue #35684662r. failure to maintain building in code-compliant manner: illuminations for exits, exit discharges and public corridors perbc 1006.1(2014 code); 27-381, bc 1008.1(2022 code). noted at box #29,

    May 29, 2025 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue #3567299p. failure to maintain building in code-compliant manner. at classrooms on exposure 3 side spalling at columns between windows and ceiling missing area 5 of holes. remedy: repair and/or replace.

    Jul 9, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. at 2 floor room241, 1fl. cafeteria entrance, basement b29, gym entrance, boys locker room, door are not closing properly. remedy: repair and/or replace.

    Jul 9, 2024 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self-closing. at 3 floor smoke doors at stair 1, i 2fl. stair h, exit 4, 1 fl. exit 8 doors are not closing property. remedy: repair/replace door.

    Jul 9, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1: 27-381. at 2 floor bx #36, auditorium 34, 38, 40, 43, 1fl. bx #49, 35, 59 libra

    Jul 9, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain buildings in code-compliant manner. reissue #35672995r. at exposure #3 from roof and masonry stone coping water penetration into classroom 5, stair a and b spalling ceiling bulkhead, 3 floor

    Jul 9, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue #35655264z failure to maintain building in code compliant manner: from exterior exp #3, missing masonry/waterproofing caused interior walls damaged due to water infiltration in classrooms. remedy: repai

    Jul 17, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue #35655265k. failure to maintain building in code compliant manner. exterior wall at exp #3 caused water infiltration into interior walls created plaster spalling, paint peeling in classrooms + office @

    Jul 17, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted:observed in the classroom that run along exp#3 has excessive water damage causing spalling paint&plaster to classroom and office at the 3,2,1 fl. rem

    Jun 14, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted:observed exterior brick at exp#3 has become porous letting water to penetrate causing interior damage to the walls of the classroom on the 3rd fl to

    Jun 14, 2022 · Penalty $625

    Resolve
  • Class - 2

    Reissue #35578334z failure to maintain building in code-compliant manner. noted: observed roof bulkhead b & e spalling plaster. remedy: repair and/or replace

    Jun 14, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35578336m fail to maintain building in code-compliant manner:lack of emergency lighting exits,exit discharges and public corridor per bc 1006.1;27-542. noted:observed several emergency light throughout

    Jun 14, 2022 · Penalty $3,125

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner:lack of emergency lighting exits,exit discharges and public corridor per bc 1006.1;27-542.noted:at gym(girl locker room)9 emergency lighting observed inoper

    Aug 11, 2021 · Penalty $1,250

    Resolve
  • Class - 2

    28-301.1 failure to provide ventilation to gas meter room per p115.6(1968 code)fgc appendix e(e4)(2014 code)noted:at gas meter room,no ventilation provide.rem:provide ventilation to gas meter room.

    Aug 11, 2021 · Penalty $1,250

    Active
  • Class - 2

    Nov#35498490k failure to maintain building in code compliant manner.noted:at roof top spalling plaster at bulkheads.rem:repair and/or replace.

    Aug 11, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35447907r failure to maintain bldg in code compliant manner. noted: at roof top bulkhead,spalling plaster at wall & ceiling. remedy:make necessary repairs.

    Jun 15, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35447911j exit door not self closing. noted: at roof top,bulkhead door not self closing due to broken door closer & missing panic bar. remedy: repair/replace door.

    Jun 15, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at all roof levels missing/none parapet walls fencing &/or guardrails throughout in various locations. remedy: comply w/code.

    Aug 29, 2019

    Resolve
  • Class - 2

    Exit door not self closing. noted: at roof top bulkheads door checks are indisrepair/non operational. remedy: repair/replace door.

    Aug 29, 2019

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. noted: at basement gym emergency lights non operational throughout in various lo

    Aug 29, 2019

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at rooftop bulkheads doors w/having no hardware installed missing/none panic bars,door handles/locks. remedy: comply w/code/provide legal hardware.

    Aug 29, 2019

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at 2nd fl stair c.b(1st fl)stair e,f(basement)stair b,6 & cafeteria doors are indisrepair/racked. remedy: repair &/or replace.

    Aug 29, 2019

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at roof bulkheads paint & plaster ceilings/walls peeling/falling & missing. remedyrepair &/or replace.

    Aug 29, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. noted: at gas meter room gas line are painted blue-instead of yellow. rmdy: comply with notice of violation.

    Jul 2, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: at gym apprx 20 ceiling tiles missing. rmdy: comply with nov.

    Jul 2, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner.no fire stopping per bc 712.3;27-345.noted:at electrical rm 4"x6"hole w/missing fire stopping

    Jul 13, 2017

    Resolve
  • Class - 2

    Re issue#35222116n failure to maintain bldg incode-compliant manner.noted:defective,loose/missing ceiling tiles throughout bsmt.rem:replace ceiling tiles.

    Jul 13, 2017

    Resolve
  • Class - 2

    Re issue#35222117p failure to maintain bldg in code-compliant manner.noted:exit doors are racked at following locations.3rd fl througout 2nd fl staircase g,1st fl staircase f,h cafeteria doors 2nd fl exit 9,10

    Jul 13, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: excessive storage consisting of (17) tv t-stands was observed @ 3rd flr near room 302. @ bsmt level (4) tables was observed @ corridors by the gymnasium

    Nov 30, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: lack of emergency lighting exits, exit discharges & public corridors per bc1006.1; 27-542. noted: broken or defective emergency lighting was observed throughou

    Nov 30, 2016

    Resolve
  • Class - 2

    Exit door not self closing. noted: @ 3rd flr throughout, @ 2nd flr staircase (g) exit (7), @ 1st flr staircase (f), exit 6, staircase (h), exit 8, @ basement in the cafeteria doors are not self closing. rem: re

    Nov 30, 2016

    Resolve
  • Class - 2

    Re-issue ecb# 35119458h, for: failure to maintain bldg in code complaint manner. noted: loose/missing ceiling tiles throughout basement. rem: repair &/or replace.

    Nov 30, 2016

    Resolve
  • Class - 2

    Re-issued ecb# 35119461z. for: failure to maintain bldg in code compliant manner. noted: racked stairwell doors @ basement level exits 7 & 8. doors werent properly closed. rem: repair &/or replace.

    Nov 30, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: water penetration through exterior wall @ bulkhead area, in the staircase (a) was observed. rem: repair &/or replace.

    Nov 30, 2016

    Resolve
  • Class - 2

    Racked stairwell doors 2fl.exit 9/10 & basement exit 7/8.doors weren't properly close.rem:maintain bldg

    Feb 10, 2015

    Resolve
  • Class - 2

    Defective door closer 2 fl.exit 6.closer keeps door open.rem:maintain bldg

    Feb 10, 2015

    Resolve
  • Class - 2

    Reissue 35027815z.spalling plaster on walls &/or celiling in rooms 107,130,208,230.rem:maintain bldg

    Feb 10, 2015

    Resolve
  • Class - 2

    Reissue 35099930r loose/missing tiles throughout basement.rem:maintain bldg

    Feb 10, 2015

    Resolve