Violations at 141-11 Holly Avenue

Queens, NY 11355 · BBL 4-05201-0021 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

27 DOB violations, newest first.

  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 5, 2021

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 5, 2021

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 21, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 21, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 15, 2019

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 15, 2019

    Dob violation - resolved
  • Construction other optional

    C-construction other optional

    Feb 14, 2018

    Vp*-violation unserved ecb- dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed

ECB violations

The newest 50 of 66 ECB violations. The city keeps the complete history.

  • Class - 2

    Exit door not self-closing. noted exit door #6 not self-closing. remedy: repair/replace door.

    Mar 19, 2026 · Penalty $625

    Active
  • Class - 2

    Reissue ecb #35725535m. failure to maintain building in code-compliantmanner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted emrgency lights at gym not working. remedy

    Mar 19, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue ecb #35725536y. failure to maintain building in code-compliantmanner. noted smoke doors not self-closing at: stair c-5th floor, exit#7, 7th floor, classrooms: 321, 331, 336, 225, 213, 329, 201. remedy:

    Mar 19, 2026 · Penalty $3,125

    Active
  • Class - 3

    Failure to maintain building in code-compliant manner. noted: small area of spalling limestone on facade at exposure #4. remedy: repair and/or replace.

    Sep 30, 2025 · Penalty $500

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: smoke doors not self-closing due to hardware or binding stair c 5th fl exit 7 1st fl, classrooms 321, 331, 336, 225, 219, 329 library and 201 dance

    Sep 30, 2025 · Penalty $1,250

    Active
  • Class - 2

    Re-issue ecb #35678935m. failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridorsper bc 1006.1; 27-381. noted: emergency lights not functioning upon te

    Sep 30, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35671736h failure to maintain building in code compliant manner.illumiation for exits,exit discharges and public corridors per bc 1006.1;27-381.noted 2nd floor gym,emergency light not operative tested.r

    Feb 4, 2024 · Penalty $1,562

    Active
  • Class - 2

    Reissue: fail to maintain bldg in code compliant manner:2nd fl gym emergency lights not working.remedy:comply with code.

    Mar 16, 2023 · Penalty $1,562

    Active
  • Class - 2

    Exit door not self-closing properly at the time of inspection.at 3rd floor neer rm 322 2 coridoor exit door not self closing properly,2nd floor neer rm-230 2 coridoor exit door not self closing properly at firs

    Apr 25, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner illumination forexits,exit discharges and public corridors per bc 1006.1;27-381 at 2ndfloor gym 2 emergency exit sign & 1 emergency exit light is not operat

    Apr 25, 2022 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self closing properly at 1st fl main entrance left side 1 exit door,1 exit door near room no 107 at 1st fl exit-3 1 exit door not self closing properly at the time of inspection. remedy: repair/re

    Mar 25, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. 3rd fl stair'g'2 place each place 1 exit sign. 2nd fl gymnasium in side 2 place

    Mar 25, 2021 · Penalty $625

    Resolve
  • Class - 2

    Work after hours w/o variance permit contrary to 28-105.12.5. at the time of inspection,work performed under job#402900009 was observed w/ workers working on the stairs and other locations after 6pm w/o an afte

    Sep 11, 2019 · Penalty $1,250

    Resolve
  • Class - 2

    Found kewanee boiler mdl# 7l284 with violating conditions. water column leaking water. safety valves leaking. combustion air interlock bypassed. vacuum tank pump leaking water. correct violating conditions and

    Apr 9, 2019

    Active
  • Class - 2

    Found kewanee boiler mdl# 7l284 with violating conditions. combustion air interlock bypassed. vacuum tank pump leaking water. correct violating conditions and submit a certificate of correction.

    Apr 9, 2019

    Active
  • Class - 2

    Re-issue#35222147y failure to maintain building wall(s) or appurtenances. noted:defective steel drop door,at cellar old ash hoist area rotten and loose steel supports for drop door. remedy:maintain exterior bui

    Mar 28, 2019

    Resolve
  • Class - 2

    Jobsite fence not constructed or maintained pursuant to subsection. atthe time of my inspection on an alteration job site of a 3 sty bldg. iobserved permit holder failed to maintain adequately construction fenc

    Mar 19, 2019 · Penalty $400

    Resolve
  • Class - 1

    Bc3314.5. platform and platofms on all working levels shall be fully planked or decked. note: at time of inspection i observed workers using supported scaffold to perform their job with several work platform

    May 29, 2018 · Penalty $2,500

    Resolve
  • Class - 1

    Bc3314.5.5 plank tied down. all planks shall be tied down to prevent dislodgement. note: at time of inspection i observed workers using supported scaffold to perform their job and with several planks not tied

    May 29, 2018 · Penalty $2,500

    Resolve
  • Class - 1

    Sec. 3307.6.5.7 installation inspection at the time of my inspection of a new 5 sty bldg at roof level,construction work in progress. upon request for installations inspection for sidewalk shed verifying that

    May 12, 2018 · Penalty $2,500

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. noted: at cellar level, in the boiler room an excessive amount of storage observed. storage consisting of package of paint of 1 gallons storage

    Mar 8, 2018

    Resolve
  • Class - 2

    Reissue: 35252843r failure to maintain building wall(s) or appurtenances. noted: defective steel drop door at cellar old ash hoist area, rotted and loose steel supports for door. rmdy: maintain exterior buil

    Mar 8, 2018

    Resolve
  • Class - 1

    Sec: bc 3310.8.4. site safety monitoring/log book. in response to an incident where an incident where a child was hit by a safe on a active jobsite. upon review site safety manager log book, observed that curre

    Mar 5, 2018 · Penalty $1,600

    Resolve
  • Class - 1

    Sec: 3301.1.1. responsibility of safety. in response to an incident where a child was hit by a sate on an active jobsite, observed that sates @ exp#3 & exp#1 swing in & out w/out proper lock/block system to pre

    Mar 5, 2018 · Penalty $1,600

    Resolve
  • Class - 1

    Failure to safeguard public & property. in response to an incident where a child was hit by a fence safe on a active jobsite. it was reported to me that gate was not properly locked to prevent movement & swing

    Mar 5, 2018 · Penalty $10,000

    Resolve
  • Class - 1

    Bc 3307.7.2 the respondent,registered architect,for job(#402899912)failed to comply w/bc 3307.7.2 & design the const fence gates such that they cannoot swing into an area accessible to the public.drawing eq-100

    Mar 5, 2018 · Penalty $8,000

    Resolve
  • Class - 2

    Failure to safeguard public and property observed concrete truck blocking pedestrian access to sidewalk during school opening hours. no barrier or protection in place to prevent children from approaching and to

    Feb 28, 2018 · Penalty $5,000

    Resolve
  • Class - 2

    Bc3307.2.1 dot permits. observed concrete truck parked on sidewalk blocking pedestrian sidewalk and delivering concrete during school opening hours (ps 24) contrary to dot permits on site which state, no work t

    Feb 28, 2018

    Resolve
  • Class - 1

    3303.11 inadequate egress/ingress reporting to incident 25471 where worker fell down supported scaffold and injured arm. observed supportedscaffold did not provide adequate egress/ingress.step of scaffold meas

    Feb 14, 2018 · Penalty $1,600

    Resolve
  • Class - 1

    Guard rails.at time of inspection of nb up to 4th fl observed at various areas that guardrail system inadequate.observed cables that were not taut an was able to be swayed more than 3",some cables did not have

    Dec 16, 2017 · Penalty $1,200

    Resolve
  • Class - 2

    Reissue #35085755l failure to maintain building wall(s) or appurtenances. noted: defective steel drop door. at cellar, old ash hoist area,rotted and loose steel supports for dorp door. drop door rusted and

    Apr 17, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner; note: at 329 classroom metal plae installed over vision panel obstructs vision. rmdy: repair and/or replace.

    Oct 11, 2016

    Resolve
  • Class - 2

    Reissue #35085759z failure to maintain bldg in code compliant manner. use of prohibited hardware per bc 1008.1.8 & 27-371(j). note: lockableslide bolts at 2 bulkhead doors. remedy: comply w/notice of violation.

    Jun 8, 2015

    Resolve
  • Class - 2

    Occupancy contrary. 6 cars parked behind transportable units via jumping the curb along robinson street. remedy: discontinue illegal use or amend c of o and provide permitted curb cut.

    Feb 27, 2014

    Resolve
  • Class - 2

    Failure to maintain -no vision panel. classroom # 329, metal plate installed over vision panel obstructs vision. remedy: maintain vision panel clear -remove obstruction.

    Feb 27, 2014

    Resolve
  • Class - 2

    Prohibited hardware. at bulkhead to roof, lockable dead bolt installed when code allows hook and eye. remedy: remove prohibited hardware/provide code compliant hardware - hook & eye.

    Feb 27, 2014

    Resolve
  • Class - 2

    Defective stairway divider panel. at 2nd floor stair "c", plexi-thermoplastic divider panel installed. remedy: provide code complaint - fireproof divider panel.

    Feb 27, 2014

    Resolve
  • Class - 2

    Inoperative panic hardware. defective panic bar - door will not open from 1st floor auditorium with fully occupied seating for p.a.c.o. # 401772836. remedy: repair or replace defective panic bar hardware.

    Feb 27, 2014

    Resolve
  • Class - 3

    Re-issue # 34981860m. defective masonry wall. at office in bulkhead of stair f, cracked cmu block above door. remedy: repair cmu block.

    Feb 27, 2014

    Resolve
  • Class - 2

    Re-issue # 35022661m. defective steel drop door. at cellar old ash hoist area, rotted and loose steel supports for drop door atop access ladder. remedy: replace steel drop door.

    Feb 27, 2014

    Resolve
  • Class - 2

    Reissue #34981861y fail to maintain. note:the old ash hoist cellar door is rotten & loose @cellar lvl. rem:replace door.

    Jun 18, 2013

    Resolve
  • Class - 2

    Reissue #34882091n. metal door diving transportable classroom #1&2 is out of plumb & not properly closing/opening. rem:repair &/or replace metal door.

    Jun 12, 2012

    Resolve
  • Class - 2

    Defective steel drop door. at cellar rotted & loose steel supports for steel drop door atop access ladder adjacent to ash hoist. rem:repair steel drop door.

    Jun 12, 2012

    Resolve
  • Class - 3

    Cracked cmu block. at office in bulkhead of stairway f cmu block cracked above door. rem:repair cmu block.

    Jun 12, 2012

    Resolve
  • Class - 2

    Illegal hardware. at roof access door from stairway e bulkhead installed lockable dead bolt. rem:remove prohibited hardware.

    Jun 12, 2012

    Resolve
  • Class - 2

    (1) transportable school 1 @ playground metal door dividing class rms 1 & 2 improperly closing,leaning out of plumb causing friction from door to door strike.(2) transportable school 2 metal door dividing class

    Jan 18, 2011

    Resolve
  • Class - 2

    (1) @ hallway e. exit door e1 improperly closing friction @ door strike. (2) lunch rm hallway exit b door frame defective causing seperationfrom door frame to door opening (3) @ rm 213 entrance door self closi

    Jan 18, 2011

    Resolve
  • Class - 3

    Concrete block wall is cracked in 2 separate places: 1) 2nd flr gymasium at the corner by exit "f" & 2) electrical room at cellar level approx 3' feet long. remedy: repair concrete block wall.

    Jul 2, 2008

    Resolve
  • Class - 3

    Reissue: 34577353n interior concrete block wall is cracked at bulkhead#8 at roof level. remedy: repair concrete block wall.

    Jul 2, 2008

    Resolve
  • Class - 2

    Reissue: 34577355r plaster on the ceiling is spalling located at exit 5 & 6 on the 1st flr level leading to the children's playground. remedy: repair plaster on ceiling.

    Jul 2, 2008

    Resolve