Violations at 147-36 26 Avenue

Queens, NY 11354 · BBL 4-04803-0001 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

27 DOB violations, newest first.

  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 13, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 13, 2020

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 23, 2017

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Residential elevator periodic inspection/test elevatorrequired

    Failure to perform category 5 inspection

    Jun 1, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 28, 2016

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 18, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 21, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 25, 2004

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 21, 2003

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Feb 19, 2002

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed

ECB violations

46 ECB violations, newest first.

  • Class - 2

    Failure to maintain building in code-compliant manner.noted:interior smoke doors do not self-close properly at;1st flr-main entrance.classroom doors do not self-close properly at,3rd flr-300,309,311,326.2nd flr

    Mar 17, 2026 · Penalty $1,250

    Active
  • Class - 2

    Exitr door not self-closing properly. at the time of inspection observed and noted at 1st floor main entrance exit-'o' one exit door, 1st floor cafeteria main entrance one exit door, cellar level exit-6(inside)

    Sep 22, 2025 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. at the time of inspection observed and noted at memorial field locker room toilet at sidewall tiles at top level missing and broken. at north sidewall tile

    Sep 22, 2025 · Penalty $1,250

    Resolve
  • Class - 1

    Emergency in car stop switch not working damaged(cu).

    Oct 3, 2023 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self-closing properly at the time of inspection.at firstfloor gym neer exit-5 2 exit doors and exit-3 one exit door and at first floor cafeteria exit-4 one exit door and first door in main entranc

    Apr 14, 2022 · Penalty $625

    Resolve
  • Class - 2

    Found teledyne laars hot water boiler model lq-625-h-n-04, serial # 8191356 unregistered., maintain boiler; register the boiler and submit a certificate of correction.

    Jun 25, 2021 · Penalty $625

    Active
  • Class - 1

    No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. remedy; file application, install dlm a

    Apr 11, 2020 · Penalty $1,250

    Resolve
  • Class - 2

    28-301.1 failure to provide ventilation to gas meter room per p115.6(1968 code) fgc appendix e(e4)(2014 code) at basement level for old school building it has one gas meter room there is no ventilation. remedy:

    Mar 20, 2019

    Resolve
  • Class - 2

    Reissue#35317318n date of issue 3/2/18 failure to maintain building incode compliant manner,broken concrete landing at rear stairs,leading to playground area from street. also defective on public corridor/basem

    Mar 20, 2019

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: noted: broken concrete landing at rea stairs, leading to playground area from street. also defective floor on public corridor/basement east

    Mar 2, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: water penetration throughout retaining wall observed in the gas meter room, at basement level. rmdy: repair and./or replace.

    Mar 2, 2018

    Resolve
  • Class - 1

    Failure to maintain bldg in code compliant manner: no fire stopping per bc 712.3; 27-345, noted: at basement level in the boiler room fire stopping missing throughout ceiling and walls was observed.also missin

    Mar 2, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: lack of emergency lighting for exits, exit discharges and public corridors per bc 1006.127-542. noted: at 1st floor public corridor near room #132, and near

    Mar 2, 2018

    Resolve
  • Class - 2

    Exit door not self-closing. noted: exit m and staircase on the third floor the doors are not working, exit 3 and exit m on the first floor the doors are not working. rmdy:repair/replace door.

    Apr 10, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: use of prohibited door &/or hardware. note: at starcase #9,k,h & the cafeteria(rm#b26)slide bolts that are capable of being padlocked are installed on the exit

    Apr 13, 2015

    Resolve
  • Class - 2

    Reissue #35022630j. emergency sign at elevator call stations missing. note: at basement & 1st fl no directional emergency signs posted at the elevator call stations. remedy: comply w/the notice of violation.

    Apr 13, 2015

    Resolve
  • Class - 2

    Reissue #35101250n. failure to maintain bldg in code compliant manner:illumination for exits. note: approx 4 emergency lights at the front & rear of the auditorium are defective(failed test operation button).

    Apr 13, 2015

    Resolve
  • Class - 2

    Failure to maintain illumination for exits.note:approx(4)emergency lights.@ front & rear of auditorium are defective(failed test operation button).rem:repair/replace defective lighting.

    Sep 5, 2014

    Resolve
  • Class - 2

    Brick parapet wall is buldging inward at roof level adjacent to 149 street side. remedy: repair &/or replace brick parapet wall.

    Jul 9, 2013

    Resolve
  • Class - 2

    Reissue: 34981850z emergency signs at elevator call stations missing defective or non-compliant w/section requirement. noted: at basement & 1st fl - no sign or directional exit safety passageway to exit doors.

    Jul 9, 2013

    Resolve
  • Class - 2

    Operation of a place of assembly w/o a current c of o. noted: basementcafeteria seats approx 80 persons (new king) w/o proper permits or displays. remedy: obtain a place of assembly c of o.

    Jul 9, 2013

    Active
  • Class - 2

    Reissue #34893315r. missing emergency signs. at elevator call stationsbasement level no emergency signs posted missing. rem:provide post signs.

    Jun 6, 2012

    Resolve
  • Class - 2

    Sec. 27-383(a) wall adjacent to the elevator is missing the directional exit safety passageway sign to the exit door on every floors. remedy: provide and maintain directional exit safety passageway sign

    Feb 4, 2011

    Resolve
  • Class - 2

    The plaster on the ceiling is spalling located in room b13 ( basement level due to plumbing pipes. remedy: repair and / or replaster on ceiling

    Feb 4, 2011

    Resolve
  • Class - 2

    Interior door is not properly closing due to defective door hinge (1) located by exit f & g on 3rd fl level. (2) corridor smoke doors on 2ndfl by room 206 & 3rd fl level by room 300 remedy: repair &/or replace

    Feb 4, 2011

    Resolve
  • Class - 2

    Roof has become porous and allowing rain water into room 138 ( 1st floor ) causing interior. remedy: water - proof exterior roof

    Feb 4, 2011

    Resolve
  • Class - 2

    67b10. 67b10- repair in car emergency phone.

    Feb 1, 2011

    Resolve
  • Class - 2

    Failure to maintain observed above exit door @ 149 st side vertical cracking of masonry wall above door wall seperating from door jam b remedy: maintain bldg

    Jun 15, 2010

    Resolve
  • Class - 2

    Failure to maintain adequate fire stopping observed open penetrations of cmu walls @ gas & electric meter rooms east wing remedy: maintain fire stopping

    Jun 15, 2010

    Resolve
  • Class - 2

    Brick facade is missing mortar between bricks located above the main entrance on the 3rd flr level. remedy: replace missing mortar.

    Jun 9, 2009

    Resolve
  • Class - 2

    Reissue: 34692927r the plaster is spalling off the wall located at stair 'l' on the 3rd flr level next to the window & bulkhead roof at stair 'm'. remedy: repair/replace plaster.

    Jun 9, 2009

    Resolve
  • Class - 2

    The concrete pavement leading to the delivery ramp is sinking leaving an 1/2 inch lip by 147th street & 26th ave. remedy: repair/replace concrete pavement.

    Jun 8, 2009

    Resolve
  • Class - 2

    Failure to maintain building in code complaints manners. noted: corridor hallway has a vertical crack adjacent to room b26a at cellar level approx 7'feel long & an 1/8" inch open gap. remedy: repair and/or repl

    Jul 14, 2008

    Resolve
  • Class - 2

    Failure to maintain building in code complaint manner. noted: stair "l"at 3rd flr the plaster is spalling adjacent to the window. remedy: repair and/or replace plaster.

    Jul 14, 2008

    Resolve
  • Non-hazardous

    Bulging and cracked brickwork with missing mortar. locations: 3rd fl to roof, all sides and auditorium exterior walls 1st to roof. remedy: repair defective brick work- throughout all facades.

    Apr 20, 2005

    Resolve
  • Non-hazardous

    Use of illegal hardware noted padlock/sliding bolt installed at(1)first floor exit"a"(2)first floor exit "b"(3)first floor exit "c"(4) firstfloor exit "d" a;; bolts are locked in the open position icey is need

    Mar 1, 2004

    Resolve
  • Non-hazardous

    Failure to maintain. noted: in gymnasium at west wall 8' vertical structural crack in brickwork. remedy: make all necessary repairs.

    Feb 24, 2003

    Resolve
  • Non-hazardous

    Failure to use panic hardware where required by law. noted: in auditorium at stage exit (right side) rear. door knob in use. occupancy is 300+ panic hardware required. remedy:provide panic hardware where requir

    Feb 24, 2003

    Resolve
  • Non-hazardous

    Failure to maintain: noted in room 228 vertical structural crack in wall at windows. remedy: make all necessary repairs.

    Feb 24, 2003

    Resolve
  • Non-hazardous

    Failure to maintain. noted: in room 328 12' structural crack (horizontal) at rear of classroom. remedy: make all necessary repairs.

    Feb 24, 2003

    Resolve
  • Non-hazardous

    Failure to maintain. noted! at west wall of old blvd vertical and horizontal structures cracks in brickwork (exterior wall) damage can be seen from roof or new wing. remedy: make all necessary repairs.

    Feb 24, 2003

    Resolve
  • Non-hazardous

    Reissue failure to maintain building defect is: horizontal crack across west wall in room #106. remedy: make all repairs.

    Jan 24, 2002

    Resolve
  • Hazardous

    Failure ot maintain building defect is: horizontal crack approx. 8 ft. long on wall in room #143. remedy: make safe.

    Jan 24, 2002

    Resolve
  • Hazardous

    Failrue to maintia bldg.-hazardous. defects noted: in cafeteria storeroom#143 (east wing) there is an approx 10' horizontal crack in wall. remedy: maintain bldg.

    Jan 24, 2001

    Resolve
  • Hazardous

    Failure to maintain bldg-hazardous. defects noted: room 106 has cracked wall. crack extends from one side of hte room to the other side. remedy: maintian bldg.

    Jan 24, 2001

    Resolve
  • Hazardous

    Failure to maintain bldg exterior noted violation issued by labor dept repairs unaddressed re shool windows as inoperable & hazardous violation open remedy maintain bldg exterior

    Jan 29, 1999

    Resolve