Violations at 148-06 25 Drive

Queens, NY 11354 · BBL 4-04802-0001 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

33 DOB violations, newest first.

  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 21, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 22, 2007

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 2, 2007

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 1, 2006

    Vw*-violation - work w/o permit dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 7, 2005

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Oct 1, 2005

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 26, 2005

    Vw*-violation - work w/o permit dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Nov 19, 2004

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 21, 2004

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 25, 2004

    Vw*-violation - work w/o permit dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 15, 2003

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 21, 2003

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 10, 2002

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Feb 19, 2002

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 2001

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 10, 2000

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 20, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 6, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    May 31, 1994

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Jul 16, 1993

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Apr 7, 1992

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Apr 25, 1991

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Jun 29, 1990

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Oct 12, 1989

    Dob violation - dismissed
  • Elevator elevatorrequired

    (51) repair or renew all rusting & deteriorating elev. equipment or file a b.n. & obtain a permit from this dept. as not in used or removed all equipment & file for same, or restore elev. to full & proper service so a complete inspection of same can be made by a insp from this dept

    Aug 1, 1988

    Dob violation - resolved

ECB violations

The newest 50 of 52 ECB violations. The city keeps the complete history.

  • Class - 2

    Failure to maintain building in code-compliant manner:no firestopping per bc 712.3;27-345.noted:inside gas meter room;firestopping was missing on pipes that penetrated thru cmu blocks.rem:provide/maintain fires

    Mar 17, 2026 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:interior smoke doors do not self-close properly at,2nd flr staircase c door#2.classroom doors do not self-close properly at 3rd flr-330,301,329,302,32

    Mar 17, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissue#35725388l exit door not self-closing.noted:on ground floor,exit 11 does not self-close properly.rem:repair/replace door.

    Mar 17, 2026 · Penalty $1,562

    Active
  • Class - 2

    Exit door not self-closing properly. at the time of inspection observed and noted at 2nd floor stairway d door no-2 1 exit door, 2nd floor stairway c door no-2 one exit door, 1st floor 1 corridor exit door near

    Sep 19, 2025 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. at the time of inspection observed and noted at ground floor level stai

    Sep 19, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue #35679002p date: 03-26-2024. failure to maintain building in code-compliant manner. lack of emergency lighting/emergency sign for exits, exit discharges and public corridors per bc 1006.1; 27-542. at th

    Sep 19, 2025 · Penalty $3,125

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.boiler room no exit signs or emergency lighting,exit sign in most of school falling apart original unit glass front with sticker letter and no battery backu

    Mar 26, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.active water leak at cellar level tunnel belting oil tank 10ft from door pipes leakingwater.rem:repair and/or replace.

    Mar 26, 2024 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35671988y exit door not self-closing.corridor doors by room 103,202,211 not closing,also staircase doors by staircase d by 103 and staircase c by 220 not closing.rem:repair/replace doors.

    Mar 26, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Reissued#35655027p.exit door not self-closing.observed stair d 2nd floor corridor near rooms 202,103,and exit 211 not closing properly.remedy:repair and/or replace door.

    Mar 7, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Reissued#35655026n.failure to maintain building in code compliant manner.illumination for exits,exit discharges and public.observed emergency exit light not working in the gym.remedy:repair and/or replace light

    Mar 7, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Exit door not self closing properly at the time of inspection.at firstfloor exit door way to 149st.two exit door are not self closing properly at the time of inspection.at first floor in auditorium left side ma

    Apr 14, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.at thetime of inspection i observed that at 1st floor gym two emergency exit

    Apr 14, 2022 · Penalty $625

    Resolve
  • Class - 2

    Found laars model# lo625 water boiler not register, maintain boiler; register the boiler and submit a certificate of correction

    Jun 25, 2021 · Penalty $625

    Resolve
  • Class - 2

    Boilers over 8' in height must have a ladder and platform, boiler needs manual type low water cutoff on boiler probe low water cutoff in wrong position, correct all violating conditions and submit a certificate

    Jun 25, 2021 · Penalty $625

    Active
  • Class - 2

    Boilers over 8' in height must have ladders and platforms correct all violating conditions and submit a certificate of correction

    Jun 25, 2021 · Penalty $625

    Active
  • Class - 2

    Ladders and platforms needed on all boilers over 8', need manual type low water cutoff on boiler probe low water cutoff in wrong position correct all violating conditions and submit a certificate of correction

    Jun 25, 2021 · Penalty $625

    Active
  • Class - 2

    Reissue#35322406j date of issue 3/2/18 failure to maintain building incode compliant manner no fire stopping per bc 712.3;27-345 missing fire stopping through ceiling in the boiler room and in basement level el

    Mar 20, 2019

    Resolve
  • Class - 2

    Reissue#35317319p date of issue 3/2/18 exit door not self closing,at 1st fl near stair "f" 2 exit doors,at 2nd fl corridor exit door near rmno 214 one door,at 3rd fl,2nd fl 2nd fl stair e,f at 1st fl stair a,b

    Mar 20, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner: no fire stopping per bc 712.3; 27-345. noted: missing fire stopping through ceiling in the boiler room. rmdy: provide/maintain fire stopping.

    Mar 2, 2018

    Resolve
  • Class - 2

    Exit door not self closing. oted: at 3rd floor, 2nd floor, 2st floor, stairs e,f at 1st floor stairs a,b and 1st floor public corridor near room #132 doors not self closing observed. rmdy: repair/replace door.

    Mar 2, 2018

    Resolve
  • Class - 2

    Exit door not self closing. noted: next to room 103 the doors ar enot working properly, also stairs e and next room 110 the doors are not closing. rmdy: repair/replace door.

    Apr 10, 2017

    Resolve
  • Class - 2

    Door not self closing. at 2ndflr stairway b door is racked to frame & jams on flr & not closing. rem:replace fire proof self closing door.

    Jun 7, 2012

    Resolve
  • Class - 2

    Classroom door hinge is defective noted : classroom door hinge is not fully attached to the door causing doors not to close properly locatedat room 228a & 230 on the 2nd fl level. remedy: repair &/or replace do

    Feb 2, 2011

    Resolve
  • Class - 2

    Exterior brick facade has become porous and allowing rain into stair a& b ( basement level ) next to room g51 and room 307 causing interior damages. remedy: water - proof exterior brick facade

    Feb 2, 2011

    Resolve
  • Class - 2

    Exit doors a & b @ basement level is not self closing. noted: fire proof self closing door hinge is defective causing doors not to close properly. remedy : repair and / or replace door hinge

    Feb 2, 2011

    Resolve
  • Class - 2

    Failure to maintain observed @ bsmt exit g (boys gym exit) glazed wall tile seperating from wall buckling out over exit doors. remedy: maintain bldg

    Jun 16, 2010

    Resolve
  • Class - 2

    Failure to maintain observed binding f.p.s.c. doors rubbing on fl bsmt stair a/b remedy: maintain bldg

    Jun 16, 2010

    Resolve
  • Class - 3

    Failure to maintain observed walkway behind auditorium stage by exit k, step cracking of walkway up to 1" in difference remedy: maintain premises

    Jun 16, 2010

    Resolve
  • Class - 2

    Reissue: 34692660r exterior brick wall approx 2'- 4- feet high by the main entrance is cracked & missing mortar at the ground level. remedy:repair/replace brick wall.

    Jun 4, 2009

    Resolve
  • Class - 2

    The concrete around the horizontal beam is cracked located at stair "a & b" on basement level. remedy: repair concrete.

    Jun 4, 2009

    Resolve
  • Class - 2

    Water penetration through the basement causing plaster to spall located in front of the room (313) in the corridor hallway on the ceiling. remedy: repair plaster in the ceiling in front of the room 13.

    Jul 7, 2008

    Resolve
  • Class - 2

    Ceiling tiles are missing located in various place throughout the school mostly on the 2nd flr. remedy: replace missing ceiling tiles.

    Jul 7, 2008

    Resolve
  • Class - 2

    Glazed concrete block wall has missing mortar between blocks located by exit a & b on the 2nd flr level. remedy: replace missing mortar.

    Jul 7, 2008

    Resolve
  • Class - 2

    Reissue: 34577352l mortar is missing between bricks located at the front entrance (ground level) 2'feet high brick wall leaning it loose. remedy: repair/replace brick wall.

    Jul 7, 2008

    Resolve
  • Hazardous

    Reissue# 34474865p, cracks in brick with mortar missing. location at front entrance left & right side low retaining wall. at east facade, adjacent to exit door to street & over 3fl window.

    Mar 31, 2006

    Resolve
  • Non-hazardous

    Cracks in brickwork with mortar missing. locations: at front entrance,left and right low retaining walls. at east facade, adjacent to exit door to street and over 3rd floor window. remedy: repair defective

    Apr 20, 2005

    Resolve
  • Non-hazardous

    Reissue: #34421942k fail. to provide panic hardware in p.a. location: 1st floor, gymnasium occupancy 650, all 3 exits. remedy: provide panichardware at 3 exits of gym.

    Apr 20, 2005

    Resolve
  • Non-hazardous

    Failure to maintain note in gymnasium on south wall above window concrete structual crack and spalling.remedy:make all necessary repairs.

    Jan 6, 2004

    Resolve
  • Non-hazardous

    Failure to provide panic hardware where required by law noted exits 5 and 6 cafeteria not equiped with panic hardware(occupancy load is 300)remedy:provide panic hardware.

    Jan 6, 2004

    Resolve
  • Non-hazardous

    Exit door swings aganist the flow of egress noted:door at bottom of staircase from exit 18 in gymnasium to girls lockeroom swings aganist flow of egress.remedy:repair replace door.

    Jan 6, 2004

    Resolve
  • Non-hazardous

    Failure to maintain hardware where required by law note in gymnasium all four exits (15,16,17,18)are not equired with panic hardware (occupancy load is 300)reissue.remedy:provide panic hardware.

    Jan 6, 2004

    Resolve
  • Non-hazardous

    Failure to use panic hardware where required by law, exit doors of gymnasium not equiped with required panic hardware ( occuopancy lard is 300 + ) remedy : provide panic hardware

    Jan 22, 2003

    Resolve
  • Non-hazardous

    Failure to use panic hardware where required by law, at exit doors of gymnasium. remedy: provide panic hardware.

    Jan 24, 2002

    Resolve
  • Non-hazardous

    Failure to maintain exterior building wall noted defects,approx 40"section of chair link fence is falling down .this is the perimeter of the school property located along 149 st.remedy:repair defect.

    Jan 24, 2001

    Resolve
  • Hazardous

    Failure to maintain exterior building wall hazardous noted defect an approx 20" section of retaining wall which supports a wrought iron fence has been severly damaged.damagd section is on 149 st side of buildi

    Jan 24, 2001

    Resolve
  • Non-hazardous

    73m05-device removed illegally, file and obtain permit for legally removing device.

    Dec 20, 2000 · Penalty $1,000

    Resolve
  • Hazardous

    Failure to maitnain bldg interior noted 1 no emergency lighting in corridors 2 parapet walls below 42 no guardrails at roof remedy maitnain bldg enterior

    Feb 4, 1999

    Resolve
  • Non-hazardous

    73x,restore or file for dismantile

    Mar 24, 1998

    Resolve
  • Non-hazardous

    73x, 73x-restore elev to service or file and dismantle

    Sep 10, 1992

    Resolve