Violations at 150-20 12 Avenue
Queens, NY 11357 · BBL 4-04538-0001 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
12 DOB violations, newest first.
- Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2021 external low pressure inspection
Jun 30, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2021 external low pressure inspection
Jun 30, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2022 external low pressure inspection
Apr 25, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2022 external low pressure inspection
Apr 25, 2023
Dob violation - active - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed
ECB violations
The newest 50 of 61 ECB violations. The city keeps the complete history.
- Class - 2
Failure to maintain building in code-compliant manner. noted: missing fire stopping on several locations in electrical switch gear room withcompletion on all electrical work and permits which were expired, incl
Mar 16, 2026 · Penalty $1,250
Active - Class - 2
Exit door not self-closing. noted: fire rated exterior door not self-closing due to faulty or missing hardware and or binding on exterior auditorium door exit(1) first floor and cellar level boiler room emergen
Mar 16, 2026 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: emergency discharges lights not operating when tested on box #4
Mar 16, 2026 · Penalty $1,250
Resolve - Class - 2
Failure to maintain building in code-compliant manner. noted: fire ratde classrooms/smoke doors not self-closing due to missing hardware binding or faulty hardware on classrooms 302, 207, 100, 101, and 117, inc
Mar 16, 2026 · Penalty $1,250
Active - Class - 2
Reissue on ecb #35725138z. failure to maintain building in code-compliant manner. noted: missing/cracking and detached deteriorating concrete on ada/handicapped ramp at exit 4 exterior to crub at railing post b
Mar 16, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381 atthe time of inspection observed and noted at 1st floor gym 2 place eme
Sep 18, 2025 · Penalty $1,250
Resolve - Class - 2
Reissue #35678697x date of issue: 03-22-2024. failure to maintain building in code-compliant manner. at the time of inspection observed and noted at ramp by exit 4 concrete is cracking and disrepaired, deterior
Sep 18, 2025 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner.ramp by exit 4 concrete is cracking and detoriated in many areas of ramp.rem:repair and/or replace.
Mar 22, 2024 · Penalty $625
Active - Class - 2
Failure to maintain bldg in codecompliant manner illumination for exits,exit discharges&public corridors per bc1006.1;27-381 atoi i observedthat@1fl level in auditorium in main entrance side 4emergency exit sig
Apr 13, 2022 · Penalty $625
Resolve - Class - 2
Exit door not self closing. note: observed at 3rd fl level staircase a exit door#3 left handside right door not self closing. remedy: repair/replace door.
Mar 24, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. note: observed at roof level middle bulkhead on roof missing flashing approx 6. remedy: repair &/or replace.
Mar 24, 2020 · Penalty $625
Resolve - Class - 2
Reissue#35317324j date of issue 3/1/18 exit door not self-closing. at bulkheads on staircase "a" and "b" staircase "c" doors not self closing and at 1st fl gymnasium exit 1 one door not self closing properly at
Mar 19, 2019
Resolve - Class - 2
Exit door not self closing. noted: at bulkeads on staircases a and b staircase c doors not self closing observed. rmdy: repair replace door.
Mar 1, 2018
Resolve - Class - 2
Reissue #35222113h. failure to maintain bldg in code compliant manner(interior) noted in the gas meter room in the basement is being used as a storage, with school supplies.boxes books papers etc. rmdy: remove
Apr 7, 2017
Resolve - Class - 2
Re-issued ecb #35128200p for: failure to maintain bldg in code compliant manner. in the basement,adjacent to the gas meter & boiler rm,combustibles are being stored. school supplies,boxes,books,papers,etc occup
Oct 11, 2016
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. missing ventilationaat gas/electrical rm in the basement. remedy: repair &/or replace.
Oct 11, 2016
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. in the basement adjacent to the gas meter & boiler rm,combustibles materials are being stored. school supplies.papers books,boxes,etc occupied approx 10'x30'sq
Oct 11, 2016
Resolve - Class - 2
Exit door, not self-closing. at transportable school, door between 2 classroom do not close properly. rmdy: repair/replace door.
Oct 11, 2016
Resolve - Class - 2
Exit door not self closing. at bulkhead area staircase (a), door do not close properly. rmdy: repair/replace door.
Oct 11, 2016
Resolve - Class - 2
Failure to maintain building in code-compliant, adjacent to the gas meter and boiler room combustibles materials are being storage. paper school supplies, books boxes, etc combustibles occupy approximately
Oct 11, 2016
Resolve - Class - 2
Failure to provide power for emergency exit lighting. emergency exit lights are not working at various locations on the 1st fl. corridors,stairs,etc. remedy: comply w/the notice of violation.
Apr 10, 2015
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. in the basement adjacent to the gas meter & boiler room combustibles are being stored. paper school supplies,books,boxes etc. combustibles occupy approx 10' by
Apr 10, 2015
Resolve - Class - 2
Re-issue #35085523m. failure to maintain bldg in code compliant manner;provide required corridor width per bc 1016.2;27-369. partial obstruction of cellar corridor. left of boiler room,shelves & school supplies
Apr 10, 2015
Resolve - Class - 2
Re-issue #35085750m failure to maintain bldg walls or appurtenances. failure to maintain exterior-no handrails at right side of center yard staris along 152 street w/17 risers & approx 4'open to fall from top
Apr 10, 2015
Resolve - Class - 2
Unsecured roll down gates. at 1st floor main entry, 3 roll down gates are not secured in the open position allowing unauthorized closure obstructing corridor passage. remedy: secure gates in open position.
Feb 25, 2014
Resolve - Class - 2
Occupancy contrary to c of o. basement open area is sectioned off with gate & occupied with combustible paper school supplies & books. at time of inspection observed 6 male students & faculty. note no sprinkle
Feb 25, 2014
Resolve - Class - 2
Failure to maintain exterior. no handrails at right side of center yard along 152 street with 17 risers and aprox 4' open to fall from bottom up. remedy: provide hand/guard railing.
Feb 25, 2014
Resolve - Class - 1
Failure to provide unobstructed exit passageway. the rear exit passageway from the boiler room is obstructed with locked gate that sections off part of basement for school use. remedy: remove obstructions (gat
Feb 25, 2014
Resolve - Class - 2
Partial obstruction of cellar corridor. at cellar/basement, left of boiler room, shelves and school supplies partially obstruct exit corridor. remedy: remove all items/maintain area clear.
Feb 25, 2014
Resolve - Class - 2
Excessive corridor combustibles. at 3rd floor corridor adjacent to room 302, paper decorations installed along floor to ceiling & protruding from wall in fire corridor. remedy: remove excessive combustibles ar
Feb 25, 2014
Resolve - Class - 2
Reissue 34891365x the plaster on the wall is spalling and cracked. located in room b1 at the basement level. rmdy: repair and/or replace plaster.
Jul 3, 2013
Resolve - Class - 2
Reissue 34891364y foundation wall has become porous and allowing rainwater into the basement level causing interior damages at room b1. rmdy: water-proof foundation wall.
Jul 3, 2013
Resolve - Class - 2
Exterior metal flashing at the middle roof bulkhead is missing approximatly 10' linear feet remedy : replace missing metal flashing
Jan 25, 2011
Resolve - Class - 2
The plaster on the wall is spalling & cracked located in room b1 at basement level. remedy: repair and / or replace plaster on wall
Jan 25, 2011
Resolve - Class - 2
Exterior foundation wall has become porous and allowing rain into the bldg causing interior damages in room b1 @ basement level. remedy: water proof exterior foundation wall
Jan 25, 2011
Resolve - Class - 2
Reissue 34791185k.observed:water penetration through foundation wall cellar level from stair g to room b1. remedy:maintain bldg.
Jun 29, 2010
Resolve - Class - 2
Reissue 34791186m.observed:spalling/cracked plaster on wall.room b1,soffit above window rm 307. remedy:maintain bldg.
Jun 29, 2010
Resolve - Class - 2
Failure to maintain.observed:flagpole is rusted & pitted,especially @ base. remedy:maintain premises.
Jun 29, 2010
Resolve - Class - 2
Sec. 27-369 bc 1017.1 corridor hallway is partially obstructed by artsdisplayed on tables located on the 3rd flr level leading to the exits by rooms 306. remedy: remove obstructions.
Jun 4, 2009
Resolve - Class - 2
The plaster on the ceiling/wall is cracked/spalling in room b1 at basement level (under the auditorium) & room 307 3rd flr level adjacent to the window. remedy: repair/replace plaster.
Jun 4, 2009
Resolve - Class - 2
Reissue: 34692652r foundation wall has become porous & allowing rain into the cellar causing interior damages by stair "g". remedy: water proof foundation wall.
Jun 4, 2009
Resolve - Class - 3
Foundation wall has become porous and causing interior damage on the level adjacent to stairway "g". remedy: water proof foundation wall.
Jul 3, 2008
Resolve - Hazardous
Reissue #34474806p. exterior windows have become porous & allowing rain water in classroom 301 & 313 on the 3 fl causing interior damages. remedy: water-proof windows.
Jun 15, 2007
Resolve - Non-hazardous
Exit passageway or corridor required width decreased by obstruction. noted: first floor auditorium stage left and right side exit doors blocked on each side by two corrugated props, each approx. 5 feet wide x
Apr 21, 2005
Resolve - Non-hazardous
Failure to maintain building. defects noted: third floor class rooms 301 and 313 have water penetration over windows from lintels. also noted: first floor gymnasium window near drinking fountain and glass block
Apr 21, 2005
Resolve - Non-hazardous
Reissue: (34266823k) failure to maintain exterior building wall. defects noted: south facade (11 avenue) above exit 4 brick parapet wall inside faces have cracked brick and spalling, loose, mildewed mortar
Apr 21, 2005
Resolve - Non-hazardous
Reissue: (34421937x) failure to maintain building. defect noted: cellar room b2 block wall leaking water onto floor. remedy: maintain wall. make all necessary repairs.
Apr 21, 2005
Resolve - Non-hazardous
Reissue: (34421936y) failure to maintain building. defects noted: cellar corridor leading to fan room and stairwell g south block wall is leaking water onto floor. also noted: cellar stairwell f near room b1
Apr 21, 2005
Resolve - Non-hazardous
Failure to maintain noted in cellar room b2 water leaking from under and thru block wall.remedy:make all necessary repairs.
Jan 5, 2004
Resolve - Non-hazardous
Failure to maintain at cellar in corridor leading to fan room south block wall is leaking water.remedy:make all necessary repairs.
Jan 5, 2004
Resolve