roofy

Violations at 87-29 79 Avenue

Queens, NY 11385 · BBL 4-03846-0040 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

35 DOB violations, newest first.

  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 14, 2019

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 18, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 18, 2015

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 18, 2015

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2014 inspection/test

    Jun 10, 2015

    Dob violation - dismissed
  • Elevator elevatorrequired

    Nyc department of education

    Jun 18, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    Nyc department of education

    Jun 18, 2014

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 23, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 16, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 16, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 16, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 3, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 3, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 3, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 15, 2010

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 28, 1993

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 28, 1993

    Dob violation - dismissed

ECB violations

The newest 50 of 57 ECB violations. The city keeps the complete history.

  • Class - 2

    Failure to maintain building in code-compliant manner. at time of inspection observed at basement level masonry chimney has bricks missing at base of chimney. remedy: repair and/or replace.

    Jun 30, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.use of prohibited door and/or hardware per bc 1008.1.8;27-371(j).noted:installation ofdoor step/kick stops in cafeteria smoke fire rated doors on all emerge

    Mar 10, 2026 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self closing.noted:emergency exterior doors not self closing due to faulty hardware or binding on exit 2 1st fl,exit 5 1st fl exit 9 2nd floor,exit 8 2nd fl and exit 2a,rm 107c freight elevator ar

    Mar 10, 2026 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:fire ratedclassrooms & smoke doors not self closing due to missing or faulty hardware and or binding on classrooms 332,337,334,342,233,232,235,240 & c

    Mar 10, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.stairs coming from 2nd floor at exp 1 steel stairs rusted and have holes in them.rusted parts falling.rem:repair and/replace.

    Mar 7, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.noted emergency lights not operable throughout entire building due to standby generator being out of service.rem:repair and/or replace.

    Mar 14, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building wall(s) or appurtenances.noted:observed vertical crack aprox 12 ft in length at west elevation (79th ave) left side of exit #9.remedy:maintain exterior building wall.

    Mar 7, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    Reissued #35582329j failure to maintain building in code compliant manner:noted:observed spalling concrete at electrical room due to water penetration via foundation walls.remedy:repair and/or replace

    Mar 7, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Exit door not self-closing properly at basement level gym room no-c07 3 exit door not self closing properly at 2nd floor old building exit-8way to out side 1 exit door not self closing properly at the time of i

    Jun 16, 2021 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35498188j date of issue#06.04.2020 failure to maintain building in code compliant manner noted observed within basement electrical room water penetrating from the exterior into the electrical room pooli

    Jun 16, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35498189l date of issue:06.04.2020 failure to maintain building in code compliant manner noted observed storage room that leads out into playground adjacent to boiler rm have approx 10 to 12 gas powered

    Jun 16, 2021 · Penalty $1,562

    Resolve
  • Class - 1

    No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. file application, install dlm, and perf

    Mar 11, 2021 · Penalty $1,250

    Resolve
  • Class - 1

    No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. file application, install dlm, and perf

    Mar 11, 2021 · Penalty $1,250

    Resolve
  • Class - 1

    No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. file application, install dlm, and perf

    Mar 11, 2021 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: observed storage room that leads out into playground(adjacent to boiler rm)have approx 10 to 12 gas powered machines eg snow blows.john deer lawn mower,

    Jun 4, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: observed within basements electrical room water pentrating from the exterior into the electrivcal room pooling on the ground. remedy: repair &/or replac

    Jun 4, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: observed illegal storage of combustible material eg. plastic folding tables,woodenchairs,plastic garbage bins,(bakers)scaffold,shopping cart,floor scrub

    Jun 4, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner use of prohibited door &/or hardware per bc 1008.1.8;27-371(j). noted: observed illegal kick stop installed throughout 1st fl at 108 boy bathroom,115,101,136,14

    Jun 4, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. noted: at nw side (79 ave), parapet w/spaulding and missing masonry. rmdy: comply with code.

    Jul 9, 2018

    Resolve
  • Class - 2

    Missing fire stopping. @ rooms 238b & 338b,mop sink, approx 1 1/2' * 2' hole in wall, above mesh door head, to concealed ceiling space. rem: provide fire stop- seal holes.

    May 8, 2012

    Resolve
  • Class - 2

    Failure to post-provide certificate of occupancy posted tco expired for new & old bldg #400821893t032 expired 9/18/2011 & 402332356t009 expired 3/13/2012. rem:post provide valid c/o or discontinue illegal use.

    May 8, 2012

    Resolve
  • Class - 2

    The foundation wall has become porous and allowing rain water to enterthe bldg causing interior damages in the electrical room at cellar lvl rem: water proof foundation wall

    Apr 15, 2011

    Resolve
  • Class - 2

    The plaster on the wall & ceiling is spawing located in room 235 on the 2nd floor lvl rem: repair &/or replace plaster

    Apr 15, 2011

    Resolve
  • Class - 2

    Failure to maintain bldg walls & appurtenances noted: cornice @ 2nd fl windows defective missing section location exit from new addition to school yard werer old bldg meets new bldg remedy: maintain bldg repair

    Jun 9, 2010

    Resolve
  • Class - 2

    Failure to maintain bldg in a code compliant manner noted: corridor doors adjacent to rooms 248 & 249 are missing frame exists remedy: maintain bldg install fireproof self closing corridor doors

    Jun 9, 2010

    Resolve
  • Class - 2

    Sec. 1017.1;27-369. failure to maintain bldg in code-compliant manner:provide required corridor width per bc 1016.2;27-369. defects noted: 2nd flr: stair b landing near room #251 occupied by tall desk w/chair

    May 15, 2009

    Resolve
  • Class - 3

    Failure to maintain bldg. defect noted: 2nd flr, stair 'a' near rm. 254 door does not close. remedy: replace door.

    May 15, 2009

    Resolve
  • Class - 3

    Failure to maintain bldg. defect noted: 2nd flr classroom 208 wall - front at roof drain has spalling plaster from previous water penetration. remedy: repair wall.

    May 15, 2009

    Resolve
  • Class - 3

    Reissue: 34646520h. basement cafeteria glazed brick wall near exit 5 has 2 vertical cracks from flr up approx 8'. remedy: repair/patch/replace bricks.

    May 15, 2009

    Resolve
  • Class - 2

    Sidewalk shed does not meet bldg code specifications. noted: sidewalk shed #402344138-01-eq-sh. lights not illuminated on portion of shed erected along 87 st elevation. remedy: make safe-maintain shed as per

    Aug 25, 2008

    Resolve
  • Non-hazardous

    Re issue #34586221x. bsmt cafeteria glazed brick walls 4 corners have vertical crack from floor up to ceiling. remedy: repair wall

    Apr 24, 2008

    Resolve
  • Non-hazardous

    Re-issue 34586222h. water penetration through roof into classroom 208.remedy: stop water penetration.

    Apr 24, 2008

    Resolve
  • Non-hazardous

    Reissue #34523245m.water penetration through roof into vestibule at exit 6 also noted:roof leak into classroom 208 & adjacent boys bathroom.remedy:stop water penetration make all necessary repairs.

    Jul 26, 2007

    Resolve
  • Non-hazardous

    Reissue #34523246y.basement cafeteria glazed brick wall near exit 5 has a vertical crack from floor up approx 8'.remedy:repair/patch/replacebricks.

    Jul 26, 2007

    Resolve
  • Non-hazardous

    Reissue #34523247x.basement electrical equipment room concrete ceilingbeam horizontial crack located behind electrical panels.remedy:repair/patch beam.

    Jul 26, 2007

    Resolve
  • Non-hazardous

    Reissue #34523248h.basement:electrical equipment room open wire lath above entry doors & wall fire stopping missing.also noted:paint room wall penetrations missing fire stopping.remedy:provide/maintain fire

    Jul 26, 2007

    Resolve
  • Hazardous

    Basement:electrical equipment room open wire lath above entry doors & wall firestopping missing. also noted:paint room wall penetrations missing firestopping. remedy:provide/maintain firestopping.

    May 12, 2006

    Resolve
  • Hazardous

    Basement electrical equipment room concrete ceiling beam horizontal crack located behind electrical panels. remedy:repair/patch beam.

    May 12, 2006

    Resolve
  • Hazardous

    Basement cafeteria glazed brick wall near exit 5 has a vertical crack from floor up approx. 8 feet. remedy:repair/patch/replace bricks.

    May 12, 2006

    Resolve
  • Hazardous

    Reissue:#34482207n water penetration through roof into vestibule at exit 6.also noted:roof leak into classroom 208 & adjacent box's bathroom. remedy:stop water penetration. make all necessary repairs.

    May 12, 2006

    Resolve
  • Non-hazardous

    Altered building occupied w/out a valid c of o. noted:job#400821893,alteration 1, for modulor addition of basement & one story. now occupied. tco issued 09/15/04,expires:12/15/04 has expired.

    May 12, 2006

    Resolve
  • Hazardous

    Water penetration through roof into vestiblue @ exit 6.remmedy:stop water penetration make all necessary repairs

    May 25, 2005

    Resolve
  • Non-hazardous

    Failure to maintain building defect : leaky roof over rooms : 208, 209and boy's bathroom remedy : make all repairs

    Feb 10, 2003

    Resolve
  • Non-hazardous

    Failure to maintain building defect : spalling missing bricks over eixt 3 ( inside of auditorium ) remedy : make all repairs

    Feb 10, 2003

    Resolve
  • Non-hazardous

    *reissue* failure to maintain. defect is cracked and spalling concrete at retaining wall supporting perimeter fence. remedy: make all repairs.

    Jan 22, 2002

    Resolve
  • Non-hazardous

    Failure to provide emergency power exit lights on the 1st,2nd floor and stairs.failure to provide emergency power to exit lights on the 1st 2nd floor and stairs.failure to provide emergency power to exit/drtl

    Sep 20, 2001

    Resolve
  • Non-hazardous

    Failure to maintain defects are as follows play area in back of school has uneven surfaces and is severely cracked causing possible trips hazards remedy make all repairs

    Jul 17, 2001

    Resolve
  • Non-hazardous

    Failure to maintain defect is as follows retaining walls supporting perimeter fence has stress cracks & broken concrete on 88 st 78 ave and 87 st remedy make all repairs

    Jul 17, 2001

    Resolve
  • Non-hazardous

    Failure to maintain building crack wall in rm151 crack ceiling in rm102, 201, 103. crack ceiling beam in hallway a exit 4 above piping.remedy:do all repairs immediately.

    Jan 23, 2001

    Resolve
  • Hazardous

    Failure to maintain building:defect is large horizontal crack in office rm b51 on ceiling beam. remedy make safe do repairs immediately.

    Jan 23, 2001

    Resolve