Violations at 93-06 63 Drive

Queens, NY 11374 · BBL 4-03095-0050 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

34 DOB violations, newest first.

  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jul 10, 2015

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 18, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 19, 2012

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2010 inspection/test

    Dec 13, 2011

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 29, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 19, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 17, 2007

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Nov 19, 2004

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 15, 2004

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 20, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 10, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 7, 1994

    Dob violation - dismissed

ECB violations

The newest 50 of 74 ECB violations. The city keeps the complete history.

  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. at the time of inspection observed and noted at 1st floor multipurpis r

    Jul 27, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissue #35725438k date of issue: 09/19/2025. failure to maintain building in code-compliant manner. use of prohibited doors and/or hardwareper bc 1008.1.8; 27-371(j). at the time of inspection observed and not

    Jul 27, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue #35725439m date of issue: 09/19/2025. exit door not self-closing properly. at the time of inspection observed at 1st floor exit-2 one exit door and at exit-3 three exit doors are not self-closing proper

    Jul 27, 2026 · Penalty $625

    Active
  • Class - 2

    Reissue #35725440j, date of issue: 09/19/2025. failure to maintain building wall(s) or appurtenances. at the time of inspection wetherle st,side main ent. in front of building there is water damage on canopy on

    Jul 27, 2026 · Penalty $6,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. no fire stopping per bc 712.3; 27-345. noted: in electric meter room, fire stopping missing in multiple areas. remedy: provide/maintain fire stopping.

    Sep 19, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building wall(s) or appurtenances. noted: in frontof building there is water damage on canopy on roof of building. remedy: maintain exterior building wall.

    Sep 19, 2025 · Penalty $2,500

    Active
  • Class - 2

    Exit door not self-closing. noted: 1st flr-exterior exit door do not close properly at "exit 2" and "exit 3". remedy: repair/replace door.

    Sep 19, 2025 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. use of prohibited door and/or hardware per bc 1008.1.8; 27-371(j). noted: mesh door leading to roof access has chain and lock on door. also rm #206 and 219

    Sep 19, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: interiorsmoke door does not self-close properly, 1st flr-"cafeteria door 138".classroom doors do not self-close properly, 3rd flr-317, 330. 2nd flr-

    Sep 19, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Re-issue #35684688p. failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors perbc 1006.1; 27-381. emergency lights-1a, 1-d, 1-e, near rm 108, 1-x, 1-

    Sep 19, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. at bulkhead stair b cracks around door, basement wall crack rebar exposed by window and hot water heater, exit 8 above 2 floor windows spalling concrete in

    Jul 25, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. at 3 floor exit signs by room 322 and 215, 2 fl emergency lights by gym

    Jul 25, 2024 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self-closing. at 1 floor smokeby room 131, by exit 2, 3 and exit 1, 3 and 4 are not closing properly. remedy: repair/replace door.

    Jul 25, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. at 3 floor doors 323, 319, 315, 313, 307, 2fl. gym entrance, 207, 209, 217, 232, 1fl.127, 131, 136, multipurpose kitchen, kitchen entrance, corridor by 112

    Jul 25, 2024 · Penalty $625

    Resolve
  • Class - 2

    Exit ddoor not self-closing.observed at ground level,cafeteria exit#1 and gym,exit doors do not close properly when inspected.remedy:repair or replace door.

    Jun 14, 2022 · Penalty $625

    Resolve
  • Class - 2

    Reissue #34854921p failure to maintain building wall(s) or appurtenances noted water damage to music room & electrical meter rm and also notd water damage to auditorium maintain building walls

    Jun 16, 2020 · Penalty $3,125

    Resolve
  • Class - 1

    No door lock monitoring installed in this controller as mandated by 3.10.12 of appendix k3 of the 2014 nycbc. this is a controller feature which ensures passenger safety. remedy; file application, install dlm a

    May 19, 2020 · Penalty $1,250

    Resolve
  • Class - 2

    Re-issue #35342166h.failure to maintain bldg wall(s)or appurtenances. note:@cellar electrical room(back left),music room(auditorium)ceiling,room 317 ceiling & auditorium ceiling by music room water penetrations

    Aug 13, 2019

    Resolve
  • Class - 2

    Re-issue 35342169n.exit door not self closing.note:at parking lot entrances door is still not self closing due to water penentration swelling up the door.rem:repair/replace door

    Aug 13, 2019

    Resolve
  • Class - 2

    Exit door not self-closing. noted: water penetration through exterior door, makes the door not self-closing at entrance door from parking lot observed. rem: repair/replace door.

    Jul 3, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. lack of emergency lighting for exits, exit discharges and public corridors per bc1006.1; 27-542. noted: defective emergency lighting package observed at li

    Jul 3, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. no fire stopping per bc712.3; 27-345. noted: missing fire stopping through ceiling at electric room. rem: provide/maintain fire stopping.

    Jul 3, 2018

    Resolve
  • Class - 2

    Re-issue viol #35099926y. failure to maintain building wall(s) or appurtenances. noted: water penetration at electric room, in the music room @ auditorium observed. also, through ceiling in the classrooms #317

    Jul 3, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner.re-issue #35099925m issued on 6/16/14 plaster damage exit 3 vestibule (skylight) & 1st fl music rm office auditorium.rem:comply w/the notive of vio.

    Aug 19, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner.re-issue #35099929j issue on 6/14/14 defective emergency lighting @gym 2nd fl,cafeteria & auditorium battery pack units.rem:comply w/the notice of vio.

    Aug 19, 2015

    Resolve
  • Class - 2

    Defective emergency lighting at gym 2nf floor, cafe, auditorium battery pack units. remedy: replace battery pack units.

    Jun 16, 2014

    Resolve
  • Class - 2

    Defective doors at 3rd floor corridor doors dragging & 2nd floor stair f doors not closing properly. remedy: repair/replace doors.

    Jun 16, 2014

    Resolve
  • Class - 2

    Missing vent covers at exterior wall, school yard & front of building. remedy: provide covers.

    Jun 16, 2014

    Resolve
  • Class - 2

    Re-issue # 34909826m. water penetration into electrical panel room water ponding in room at time of inspection, also at room 235,229 through ceiling. remedy: seal penetration.

    Jun 16, 2014

    Resolve
  • Class - 2

    Re-issue # 34981822l. plaster damage exit 3 vestibule (skylight) & 1st floor music room office auditorium. remedy: repair walls/ceiling.

    Jun 16, 2014

    Resolve
  • Class - 2

    Re-issue # 35023339z. school yard fence atop of retaining wall at children play yard equipment adjacent to lower yard driveway fence not attached to supports & fall hazard present. remedy: secure fence to lower

    Jun 16, 2014

    Resolve
  • Class - 1

    Severe corrosion of metal grating supports at inner court yard adjacent to exit 3. evident deflection noted with detaches supports. remedy: make safe, replace grating & supports.

    Jun 13, 2014

    Resolve
  • Class - 2

    Fall hazard at nw corner school yard fence not secured to post/adjacent to courtyard entrance (booth st) side. 5' fall. remedy: make safe.

    Jun 28, 2013

    Resolve
  • Class - 2

    Occupancy contrary 22 cars parked in center schoolyard cert of occupancy does not indicate off street parking rem; discontinue illegal use or amend c/o

    May 30, 2012

    Resolve
  • Class - 2

    Partial obstruction at auditorium stage right exit passageway partially obstructed w/ standing fan podium tables and stands rem: remove all items maintain corridor width clear

    May 30, 2012

    Resolve
  • Class - 2

    Spalling plaster at exit 3 vestibule skylight spalling and crumbling plaster in over head skylight pocket rem; repair plaster surface

    May 30, 2012

    Resolve
  • Class - 2

    Reissue #34909825k missing fire stopping at electric room w/ ceiling conduit penterations at boiler room w/ pipe penetrations above entry door rem: provide fire stop

    May 30, 2012

    Resolve
  • Class - 2

    Exterior wall @ eastside chimney mortar joints missing/washing out also eastside,auditorium missing mortar.also spalling brick with deteriorating chaulking @ west parapet (63dr side)rem:make all repairs

    Jun 2, 2011

    Resolve
  • Class - 3

    Reissue#34854922r.plastic damage in music room in auditorium.rem:repair ceiling

    Jun 2, 2011

    Resolve
  • Class - 2

    Reissue#34854921p.water penetration into music room by auditorium alsoin electrical panel room.rem:seal penetration.

    Jun 2, 2011

    Resolve
  • Class - 2

    Reissue:34854950y,34761954z,34645897n,34586929l,34519253k.missing firestopping @ cellar electrical panel room around pipe penetration in ceiling,also above door wire lath.rem:provide fireproofing

    Jun 2, 2011

    Resolve
  • Class - 2

    Reissue 34761954z.failure to maintain adequate firestopping observed: missing concrete bock above boiler room entrance door above cellar corridor entrance.at electric meter room,open penetrations around ceiling

    May 27, 2010

    Resolve
  • Class - 3

    Failure to maintain.observed:racked,warped stairwell doors 3 fl e,d, 2 fl c.doors won't properly close. remedy:maintain building.

    May 27, 2010

    Resolve
  • Class - 2

    Use of prohibited door hardware.observed:bulkhead door stair b has dead bolt lock, lock difficult to operate.remedy:use code compliant egress hardware.

    May 27, 2010

    Resolve
  • Class - 3

    Failure to maintain.observed:spalling plaster on ceiling of music roomadjacent auditorium stage.remedy:maintain building.

    May 27, 2010

    Resolve
  • Class - 2

    Failure to maintain.observed:water penetration through foundation @ electric meter room(back left corner) and music room adj auditiorium.powder water observed in electric room.remedy:maintain building.

    May 27, 2010

    Resolve
  • Class - 2

    Re 34645897n. missing fire stopping at electrical meter room at rear wall pipes that go into ceiling. also above door frame wire mesh not dob approved. remedy: seal all penetrations.

    Mar 5, 2009

    Resolve
  • Hazardous

    27-127 reissue 34586926x mortar missing b/t bricks & door lintel is rotten & rusted located @ 2 exits from cafeteria on the 1st lvl & 2 windows on south side facade is missing mortar on 2 lvl 3 fl stair f on bu

    May 27, 2008

    Resolve
  • Hazardous

    27-127 reissue 34586928j defective doors noted main entry door (middledoor wetherole side) hitting frame 3 fl stair b, 2 floor stiar c, e, corridor doors 1 floor stair f & corridor doors doors hitting frame & o

    May 27, 2008

    Resolve
  • Hazardous

    27-345 reissue 34586929l electical meter rm is missing fire stopping around pipe penetration through the wall on & door above entry rem: provide fire stopping where required

    May 27, 2008

    Resolve