Violations at 67-25 51 Road

Queens, NY 11377 · BBL 4-02423-0001 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

50 DOB violations, newest first.

  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Residential elevator periodic inspection/test elevatorrequired

    Failure to perform category 5 inspection

    Jun 1, 2016

    Dob violation - active
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2013 inspection/test

    Oct 31, 2014

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2013 inspection/test

    Oct 31, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    Nyc department of education

    Jun 4, 2014

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 2, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    May 2, 2013

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2011 inspection/test

    Oct 1, 2012

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 20, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 20, 2012

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2010 cat 1 insp/tst

    Aug 15, 2012

    Dob violation - active
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2010 inspection/test

    Dec 13, 2011

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 27, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 27, 2011

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Vcat1-elevator annual inspection / test elevatorrequired

    Oct 8, 2010

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 7, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 7, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 28, 2009

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 18, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 18, 2007

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 19, 2007

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 17, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 17, 2006

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 21, 2003

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 21, 2003

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Feb 19, 2002

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 2001

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 10, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 13, 1997

    Dob violation - active
  • Elevator elevatoroptional

    1

    Apr 7, 1992

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Jun 29, 1990

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Oct 12, 1989

    Dob violation - dismissed

ECB violations

The newest 50 of 80 ECB violations. The city keeps the complete history.

  • Class - 2

    Reissue#35691678r altered/changed building occupied without a valid certificate of occupancy as per 28-118.3.1-28-118.3.2.noted:temp cofo expired on 8-6-2011 job#400825452 has not been signed off.rem:obtain val

    Mar 5, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35691676n failure to maintain building in code-compliant manner.noted:2nd floor east wing corridor,water penetration damage with spalling plaster above most windows in corridors.rem:repair and/or replac

    Mar 5, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35677207n failure to maintain building in code-compliant manner.noted:doors not fixed,rm#303,304,312.classroom doors do not self-close at,3rd flr 301.2nd flr-258,245,256,212,212a.1st flr-105a.smoke door

    Mar 5, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue 35677205x. altered/changed building occupied without a valid cof o as per 28-118.3.1, 28-118.3.2. temp c of o expired on 8-6-2011 job #400825452 has not been signed off. remedy: obtain a valid c of o or

    Feb 18, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue 35677207j. failure to maintain building in code-compliant manner. doors not fixed, room 303, 304, 312. remedy: repair and/or replace.

    Feb 18, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue 35677208l. failure to maintain building in code-compliant manner. 2nd floor east wing corridor water penetration damage with spalling plaster above most windows in corridors. remedy: repair and/or repla

    Feb 18, 2025 · Penalty $3,125

    Active
  • Class - 2

    28-301.1 unlawful display of artwork in corridors greater than 20% perfdny 2008 code;fc 803.3.2 noted at 3rd,2nd,1st & ground floor;several classroom entry doors entirely covered with combustible paper decorati

    Feb 29, 2024 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.noted:at the 2ndfloor east wing corridor,water penetration damage with spalling plaster above several windows.rem:repair and/or replace.

    Feb 29, 2024 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:several fireproof self closing doors not closing properly at several locations.3rd floor-smoke door by rm 303.2nd floor-stairwell a smoke doors by rm

    Feb 29, 2024 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted several existing emergency lights inoperative when tested at many loca

    Feb 29, 2024 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35665588y altered/changed building occupied without a valid cofo as per 28-118.3.1-28-118.3.2 noted temp c/o expired on 08/06/2011.job#400825452 has not been signed off.rem:obtain valid cofo or disconti

    Feb 29, 2024 · Penalty $3,125

    Active
  • Class - 2

    Reissue #35577338l exit door not self-closing at staircase 1,2 3rd fl, 2nd fl staircase & first floor.remedy:repair/replace

    Jan 12, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35577345j altered/changed building occupied w/o valid c of o as per 28-118.1-28-118.3.2 job #400825452 has not been signed off & temp c/o expired 8/6/11.remedy:obtain valid c of o or discontinue illegal

    Jan 12, 2023 · Penalty $3,125

    Active
  • Class - 2

    Reissue35561599n alt/changed bldg occupied w/o valid cofo as per 28-118.3.1&28-118.3.2 temp c/o expired8/6-11 on current cofo on file.obtainvalid cofo or discont illegal occupancy

    Jan 24, 2022 · Penalty $3,125

    Active
  • Class - 2

    Reissue #35577380p exit door not self-closing.3rd fl stair 1 & 2,2 doors not self closing,2nd stair 1 & 2 2 exit doors not fixed.1st floor at exit 2 & 1 outside door.remedy:repair/replace door.

    Jan 24, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue #35561599n.at level/changed bldg occupied w/out a valid c of oas per 28-118.3.1 & 28-118.3.2

    Jan 24, 2022

    Resolve
  • Class - 1

    Failure to maintain bldg in code-compliant manner.front yard by cornerof maurice ave & 67th street large letters from the name of the schoolave falling off,3 letters.remedy:repair &/or replace.

    Jan 24, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    Exit door not selfclosing properly@3fl@stair1&2 2exitdoor not selfclosing,2fl stair1&2 2exitdoor not selfclosing,@1fl@exitdoor 2exit not selfclosing properly,@1fl@exit1&2 (outside) 1exitdoor not selfclosing pro

    Jun 2, 2021 · Penalty $625

    Resolve
  • Class - 2

    Reissue35447613l doi8.19.19 failure to maintain bldg in codecompliant manner@2fle side w/retaiing wall (west side) w/exit3&n side ramp w/cracked pavement w/n rusted school sign.repair &/or replace.

    Jun 2, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue35447615p doi8.19.19 alt/changed bldg occupied w/o valid c/o asper 28-118.3.1&28-118.3.2.alt/changed bldg w/o valid c/o as per 28-118.3.1.t c/o expired8/6/11 on current c/o available/existing on file w/d

    Jun 2, 2021 · Penalty $3,125

    Active
  • Class - 2

    Section 8 and section 4 of schedule c missing required information fgc503.7; details describing venting system missing from plans as per fgc 106.5#7;; fgc-misc, comply with notice of violation; mc misc

    Mar 15, 2021

    Resolve
  • Class - 2

    Reissue 35344615n date of issue 6/25/18.exit door not self closing @ground fl exit 5,old wing 2 doors.exit 1&2 1door,exit-10 1 door.in cafeteria near girls bath 2 doors,1st fl exit 3 bottom of ramp 2 doors,new

    Aug 19, 2019

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner illumination for exit discharges & public corridors per bc 1006.1.@ 1st fl near exit-10 1place 2 lights & @ground fl near entrance lobby near women toilet 1 pla

    Aug 19, 2019

    Resolve
  • Class - 2

    Reissue #35344613j date of issue of 6/25/18.altered/changed bldg w/o avalid cert of occupancy as per 28-118-3.1.tco expired on 8/6/11 on current cofo available/existing on file w/dob @time of insp.rem:obtain va

    Aug 19, 2019

    Active
  • Class - 2

    Reissued #35344700h date of issue 6/25/18 failure to maintain bldg in code compliant manner @windo along 51 street road leaking thru-out water damage observed.rem:comply with code

    Aug 19, 2019

    Resolve
  • Class - 2

    Reissue #35344701j date of issue on 6/25/18.failure to maintain bldg in code compliant manner @2nd fl east side w/retaining wall(west side)@exit 3&north side ramp w/cracked pavement @north rusted school sign l

    Aug 19, 2019

    Resolve
  • Class - 2

    Noted: loose, cracked and missing masonry @ 2nd fl (east side), @ retaining wall (west side), @ exit 3, & north side ramp w/cracked pavement @ north rusted school sign letter hanging loose. rem: comply w/code.

    Jun 25, 2018

    Resolve
  • Class - 2

    Noted: @ window along 51st road leaking throughout. water damage obse rved. rem: comply w/code.

    Jun 25, 2018

    Resolve
  • Class - 2

    Reissue nov #34949680p. noted: elevator call signs missing/insufficient @ old bldg (wing). rem: comply with code.

    Jun 25, 2018

    Resolve
  • Class - 2

    Reissue nov #35084951y. @fpsc door between new & old school (wing) {stair b} @ main floor, @ 3rd floor {exit 5} and @ 1st floor {exit 3}, not self-closing when tested. rem: comply w/code.

    Jun 25, 2018

    Resolve
  • Class - 2

    @ auditorium, @ lunchroom & @ gym. noted: em lights not working when tested. rem: comply w/code.

    Jun 25, 2018

    Resolve
  • Class - 2

    Reissue nov #35222197j. noted: tco expired on 08-16-2011. no current c of o available/existing on file with dob at time of inspection. rem: comply with code.

    Jun 25, 2018

    Active
  • Class - 2

    Reissue:35221199n exit door not self closing. notice doors between new and old wing on main floor and 2nd floor not closing closers not connected. rmdy: repair/replace door.

    Jul 24, 2017

    Resolve
  • Class - 2

    Reissue:35216175m failure to provide ventilation to gas meter room per 115.6 (1968 code) fga appendix e (34) (2014 code) at time of inspection noticed no ventilation of fresh air in gas meter room. rmdy: compl

    Jul 24, 2017

    Resolve
  • Class - 2

    Reissue:35221199l emergency signs at elevator call station missing, defective or non-compliant with section requirements. noticed on all 3floors of old wing no elevator call signs. rmdy: install and or repair

    Jul 24, 2017

    Resolve
  • Class - 2

    Reissue:35221197j altered/changed building occupied w/o a valid certificate of occupancy as per 28-118.3.1 and 28-118.3.2. notice at time of inspection as valid cofo. last tcofo was 8-16-11 #40082545stco36.rmd

    Jul 24, 2017

    Active
  • Class - 2

    Failure to maintain bldg in code compliant. interior reissue ecb#35146950n door closer defective between new & old wing. adjacent to stair bon main floor,no power going to units(door closer). remedy: repair &/o

    Nov 23, 2016

    Resolve
  • Class - 2

    Emergency signs at elevator call station missing defective or non compliant w/section requirements. emergency stations call signs missing inold wing,elevator all floors. reissue #35146951p. remedy: install &/or

    Nov 23, 2016

    Resolve
  • Class - 2

    Altered/changed bldg occupied w/o a valid c of o as per 28-118.3.1;28-118.3.2. altered bldg occupied w/o a valid c of o tco exp 8-16-11. reissue #35146952r remedy: obtain valid c of o or disc illegal occupancy.

    Nov 23, 2016

    Active
  • Class - 2

    Sec. 27-766 fresh air in gas meter room rs 161p115.4 & 6/tppn 1 of 1994 reissue ecb#34949679h gas meter room is lacking fresh air ventilating at cellar level. remedy: add fresh air in gas meter room.

    Nov 23, 2016

    Resolve
  • Class - 2

    Reissue 35084923r altered bldg occupied w/o a valid c of o.noted tco 400825452t036 expired 8/16/11.rem comply w/ nov

    Jul 30, 2015

    Active
  • Class - 2

    Reissue 350811950m emergency stations call signs missing.locations old wing,elevator,all floors.rem comply w/ nov

    Jul 30, 2015

    Resolve
  • Class - 2

    Reissue 35084951y failure to maintain bldg in code compliant manner.note door closer defective/ (doce) & frame racked.location 1st fl door @corridor to new wing near stair b.rem comply w/ nov

    Jul 30, 2015

    Resolve
  • Class - 2

    Fire proof doors not self-closing. noted: smoke doors between new & old wing adjacent to stair b on main floor, have broken door closers. remedy: replace door checks.

    Feb 3, 2014

    Resolve
  • Class - 2

    Re-issue # 35027834y. missing emergency signs at elevator call stations - old wing - all floors. remedy: install/provide emergency signs.

    Feb 3, 2014

    Resolve
  • Class - 2

    27-766. re-issue # 35027835x. missing fresh air inlet in gas meter room, old wing. remedy: provide fresh air inlet/ventilation.

    Feb 3, 2014

    Resolve
  • Class - 2

    Re-issue # 35027840k. tco # 400825452t036 expired 8/16/2011 with 8 outstanding requirements. remedy: obtain a valid c of o or discontinue illegal use.

    Feb 3, 2014

    Active
  • Class - 2

    Tco 400825452t036 expired 8/16/11. rmdy: discontinue illegal use or amend cofo.

    Jul 16, 2013

    Active
  • Class - 2

    Boiler room ground floor room g12 boilre room use for storage. carts, kitchen mixer, 5 gallonsplastic containers carton, old microwave, metal scaffolding stored etc. rmdy: remove all mainteance and misc ite

    Jul 16, 2013

    Resolve
  • Class - 2

    27-766- reissue 34949679h cellar-gas meter room no fresh air ventilation. remedy: provide fresh air ventilation.

    Jul 16, 2013

    Resolve