Violations at 46-02 47 Avenue

Queens, NY 11377 · BBL 4-02284-0006 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

31 DOB violations, newest first.

  • Low pressure boiler boiler required

    Violation issued-failure to file 2018 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 8, 2015

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2012 inspection/test

    Mar 31, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 23, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 16, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 12, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 16, 2007

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Nov 19, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 19, 2003

    Dob violation - dismissed
  • Elevator elevatorrequired

    4p5836

    Apr 25, 2002

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 1996

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 17, 1995

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    May 31, 1994

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Aug 16, 1993

    Vp*-violation unserved ecb- dismissed
  • Elevator elevatoroptional

    1

    Jun 28, 1993

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Apr 12, 1993

    Vp*-violation unserved ecb- dismissed
  • Elevator elevatoroptional

    1

    Apr 7, 1992

    Dob violation - dismissed

ECB violations

The newest 50 of 74 ECB violations. The city keeps the complete history.

  • Class - 2

    Exit door not self-closing.noted:at the time of inspection observed on1st flr-exit 2a exterior exit right door does not self-close properly when tested.rem:repair/replace door.

    Jul 17, 2026 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted:at the time of inspection observed on 4th flr-staircase h left door is missing glass panel on smoke door.rem:repair and/or replace.

    Jul 17, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissue#35725319h failure to maintain building in code-compliant manner.noted:at cellar level in old wing discontinued coal hatch with heavily corroded steel members all around it underside is in disrepair.rem:

    Jul 17, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35725320p failure to maintain building in code-compliant manner.noted:interior fpsc doors do not self-close properly at 5th flr-staircase f,c.3rd flr-staircase d.2nd flr-staircase f,h basement-staircase

    Jul 17, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue: 35498244p-failure to maintain building in code-compliant manner. cellar level foundation wall are porous allowing water to come into cellar. remedy: comply with code.

    Sep 11, 2025 · Penalty $6,250

    Active
  • Class - 2

    Reissue: 35682688x-failure to maintain building in code-compliant manner. fireproof doors not working at 5th floor corridor by rm 528, 515, 4th floor 414, 328. remedy: comply with code.

    Sep 11, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue: 35682681r-failure to maintain building in code-compliant manner. heavily corroded steel members @ discontinued coal hatch. remedy: comply with code.

    Sep 11, 2025 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted at cellarlevel in old wing, discontinued coal hatch with heavily corroded steelmembers all around its underside. remedy: repair and/or replace.

    Jun 14, 2024 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted at new wing cellar sprinkler room, illegal storage at equipment including pressure washer, floor scrubbers, buckets, bins, ladder and buckets with cl

    Jun 14, 2024 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self-closing. noted exit #2 exterior doors are bent and rub. exit #5(cafeteria kitchen) exterior door is reached on fence. mentioned doors are not opening or closing properly without excessive for

    Jun 14, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted seward fire proof self closing smoke doors not working properly when tested. at5th fl corridor by rm 528 and 515 4th fl rm 414; 3rd fk ny rm 328, 2nd

    Jun 14, 2024 · Penalty $625

    Active
  • Class - 2

    Reissue #35674994y. failure to maintain building wall(s) or appurtenances. noted at old building cellar foundation walls have become porous,allowing water to penetrate into the building. remedy: maintain exteri

    Jun 14, 2024 · Penalty $1,250

    Active
  • Class - 2

    Reissue#35655508x failure to maintain building wall(s)or appurtenancesnoted:at old building,cellar level,foundation wall has become porous allowing the water in the cellar all over.rem:maintain the exterior wal

    May 18, 2023 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35655509h altered/changed building occupied without a valid certificate of occupancy as per 28-118.3;28-118.3.2 noted:tco#4052874-00002 expired on 4/27/22 building is fully operational as a public schoo

    May 18, 2023 · Penalty $3,125

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. no fire stopping per bc 712.3;27-345. noted:observed during inspection of electrical room,opening in block wall approx 2'x3' hole compromises fire stopping

    Jun 7, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted:observed during inspection of cellar level electrical room,storage of construction material,tools,tool boxes,carts plastic buckets. no storage permit

    Jun 7, 2022 · Penalty $625

    Resolve
  • Class - 2

    Alter/changed building occupied w/o valid c of o. noted:observed during inspection bldg occupied and operational as school. upon review of dob records tco#4052874-0000002 expired on 4/27/22. remedy:obtain valid

    Jun 7, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    Reissue#35578205m failure to maintain walls or appurtenances. noted:observed during inspection of cellar level,foundation walls throughout have become porous allowing water to penetrate into building. remedy:ma

    Jun 7, 2022 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain bldg in codecompliant manner:use of prohibited door &/or hardware per bc1008.1.8;27-371j.noted:observed thruout all 5flsapprox90% of classrm fpsc doors have kickstops installed on them.provi

    Jun 9, 2021 · Penalty $625

    Resolve
  • Class - 2

    Reissued35498244p failure to maintain bldg wall(s) or appurtenances noted:observed@various locations thruout cellar,foundation wall has become porous,allowing water to penetrate into cellar.maintain exterior bl

    Jun 9, 2021 · Penalty $3,125

    Active
  • Class - 2

    Re-issue #35447857h failure to maintain bldg wall(s) or appurtenances.noted:at cellar level the foundation wall is porous allowing water to come into the cellar at various locations.remedy:maintain exterior bld

    Jun 23, 2020 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35272457r failure to maintain bldg walls or appurtenances. noted: at cellar level foundation wall have be porous allowing water intothe locker room area. remedy: maintain exterior wall.

    Aug 19, 2019 · Penalty $3,125

    Active
  • Class - 2

    66l10,59bb07,99bb05. 66l10-rope gripper rejects automatically / o manual reset) 59bb07-expired brake maintenance data tag; 99bb09-expired cat i test tag.

    Aug 1, 2019

    Active
  • Class - 2

    B254,50a. burnham boiler mdl #4f-1325: 50ai missing ladder and platfo m for access to top of boiler rmdy: resolve violating condition and ubmit certificae of correction.

    Feb 13, 2019

    Active
  • Class - 2

    B254,50a. burnham boiler mdl #4e-1325: 50ai missing ladder and platform for access to top of boiler rmdy: resolve violating condition and submit certificae of correction.

    Feb 13, 2019

    Active
  • Class - 2

    Reissue:35222450z failure to maintain building walls or appurtenancesexerior walls have become porous water penetration into cellar at cellar locked room area. rmdy: maintain building walls.

    Jul 18, 2017

    Active
  • Class - 2

    Reissue:35222451k exit doors not self closign. exit doors not self closing at girls gym (5 floor), stair c, 4th flr, stair b, 1st flr, stair b,4th floor. remedy: repair/replace door.

    Jul 18, 2017

    Resolve
  • Class - 2

    Reissue:35235435n failure to maintain building in code compliant manner. cellar boiler room exit metal grate heav to operate. rmdy: repair/replace.

    Jul 18, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner noted: boiler room 2nd means of egress hatch is not properly operable,the hatch is made of heavy metal bars weighint apprx 50 lbs and not

    Apr 3, 2017

    Resolve
  • Class - 1

    Failure to maintain-provide unobstructed exit passageway.cellar boilerroom exit door e.illuminated exit sign leads to nowhere w. fixed metalgrate box w.no means of opening.rem:remove obstruction.

    Dec 5, 2016

    Resolve
  • Class - 2

    Exit doors not self closing. missing door checks at emergency door next to room 558, entry doors to girls gym-5th floor, stair c - 4th flr, stair b -1st flr, and stair b-4th flr. doors not closing-hitting frame

    Dec 5, 2016

    Resolve
  • Class - 2

    Reissue 351295448k failure to maintain exterior walls/appurtenances. exterior. water penetration in foundation wall allowing water to penetrate into cellar locker area. rmdy: maintain exterior building wall.

    Dec 5, 2016

    Active
  • Class - 2

    8v1,70o2,67l10

    Nov 17, 2015

    Resolve
  • Class - 1

    Failure to carry out demolition operations as required. noticed at time of inspection demolition of 2 sty bldg in progress noticed at exp#2 existing adjoining school 1 sty bldg to remain plans stack protection

    Aug 25, 2015 · Penalty $1,200

    Resolve
  • Class - 2

    Failure to maintain bldg walls and/or appurtenances.water penetration reissue ecb 35028051m.water penetrating into cellar from foundation walls.rem:comply with nov

    Jul 16, 2015

    Resolve
  • Class - 2

    - doors not closing - at 1st story exit 2 discharge doors. remedy: repair/replace doors noted.

    Jul 23, 2013

    Resolve
  • Class - 2

    Reissue vio #34941231n water penetrating foundation wall at cellar (area w/lockers). remedy: defect noted: maintain water proof integrity offoundation wall(s).

    Jul 23, 2013

    Resolve
  • Class - 1

    Failure to maintain bldg in code-compliant manner.at time of inspection i observed that the standpipe and sprinkler piping are installed tooclose to the fire pump in the cellar.fire pumps must be free from obst

    May 23, 2013

    Resolve
  • Class - 2

    Reissue #34907944y defective lights. at transportable unit 147 the emergency light not operating at exit door. rem:repair or replace emergency lighting.

    Mar 6, 2012

    Resolve
  • Class - 2

    Occuancy contrary. noted:23 cars parked in school yard at rear of minischool via legal work curbcut on 46 street. rem:remove all vehicles.

    Mar 6, 2012

    Resolve
  • Class - 2

    Reissue #34907942k foundation water penetration. the foundation has become porous allowing water to penetrate into cellar locker area. rem:water proof foundation. rem:waterproof foundation.

    Mar 6, 2012

    Resolve
  • Class - 2

    Defective light at transportable unit ts marked #147 emergency light not operative at exit door rem: repair emergency exit light

    Apr 15, 2011

    Resolve
  • Class - 2

    Defective doors. the fire proof self closing doors are racked & not self closing properly at 4th fl stairway e. 1st fl stairway c. 4th fl stairway c is not self closing. remedy: repair doors to properly self

    Apr 13, 2011

    Resolve
  • Class - 2

    Reissue #34848047r foundation with moisture penetration. the foundation has become porous allowing water penetration into cellar at locker room area. remedy: water proof foundation.

    Apr 13, 2011

    Resolve
  • Class - 2

    Reissue #34848048z defective plaster surface. at 5th floor stairway d bulkhead,spalling plaster surface with areas missing & crumbling. remedy: repair plaster surface.

    Apr 13, 2011

    Resolve
  • Class - 2

    Sec. 28-301.1;1001.3. failure to maintain egress clear and unobstructed. observed: at auditorium exit adjacent stage, storage of blackboards, furniture, speakers podium. remedy: maintain bldg.

    May 7, 2010

    Resolve
  • Class - 2

    Failure to maintain. observed spalling plaster on ceiling 5 flr bulkheads stairs b,d. remedy: maintain bldg.

    May 7, 2010

    Resolve
  • Class - 2

    Reissue 34770501k. failure to maintain. observed water penetration into cellar around locker room area. remedy: maintain bldg.

    May 7, 2010

    Resolve
  • Class - 2

    Reissue 34770500z. failure to maintain. observed: cracked concrete landing at exterior door boiler room to area way grating on 47 ave side. remedy: maintain bldg.

    May 7, 2010

    Resolve
  • Class - 2

    Failure to maintain. observed: exit lights unlit, not in operation t2,t4. remedy: maintain bldg.

    May 7, 2010

    Resolve