Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 38
- Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2024 external low pressure inspection
Nov 14, 2025
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2023 external low pressure inspection
Sep 23, 2024
Dob violation - active - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Nov 8, 2018
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed
Show 28 more ↓
- Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 23, 2015
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 23, 2015
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 15, 2014
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 15, 2014
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jul 15, 2014
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 5, 2013
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 5, 2013
Dob violation - resolved - Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2011 inspection/test
Oct 1, 2012
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 17, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 17, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 17, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 17, 2012
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 27, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 27, 2011
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 27, 2011
Dob violation - resolved - Construction other optional
C-construction other optional
Oct 23, 2009
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 3, 2008
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed
ECB violations · 61
- Class - 2
Emergency signs at elevator call stations missing,defective or non-compliant with section requirements.noted:emergency signs at elevator call station map missing at elevator call station lobby g at br level obs
Jul 22, 2026 · Penalty $625
Resolve - Class - 2
Reissue on ecb #35725166x. failure to maintain building in code-compliant manner. noted: fire rated classrooms and smoke doors not self-closing due to binding, missing and/or faulty hardware on classrooms 12, 1
Jul 22, 2026 · Penalty $3,125
Active - Class - 2
Reissue on ecb #35725165y. failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: emergency illuminated discharge exit
Jul 22, 2026 · Penalty $3,125
Active - Class - 2
Reissue on ecb#35725163k failure to maintain building in code compliant manner.noted;generator that supplies emergency power for south wiring portion of school is not working and has not been working for quite
Jul 22, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner.use of prohibited door and/or hardware per bc 1008.1.8;27-371(j).noted:illegal installation of hardware kick stops on fire rated doors and classrooms on roo
Jul 22, 2026 · Penalty $1,250
Active - Class - 2
Reissue on ecb #35725764m. exit door not self-closing. noted: emergency exterior exit door not self-closing due to binding, missing and/or faulty hardware at exterior door exit 8 at sc level observed when teste
Jul 22, 2026 · Penalty $1,562
Resolve - Class - 2
Re-issue 35684699k. failure to maintain building in code-compliant manner. at the time of inspection, generator that supplies emergency power for south wing is not working. remedy: repair and/or replace.
Sep 16, 2025 · Penalty $3,125
Active - Class - 2
Re-issue 35684697r. failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridor per bc 1006.1; 27-381. at the time of inspection, one emergency light in ha
Sep 16, 2025 · Penalty $3,125
Active - Class - 2
Re-issue 35684696p. failure to maintain building in compliant manner. at the time of inspection, stair exit door "h" on 3rd floor, library exit doors, corridor door next to library, stage exit door "b", room #3
Sep 16, 2025 · Penalty $3,125
Active - Class - 2
Re-issue 35684698z. exit door not self-closing. at the time of inspection, exit doors #1, #15, #3, 12 are not self-closing. remedy: repair/replace.
Sep 16, 2025 · Penalty $1,562
Resolve
Show 40 more ↓
- Class - 2
Failure to maintain building in code-compliant manner. at 3 floor room327, 2fl. 216, 1fl. stage right, 121, cafeteria, 30, corridor by rm 20, 18 and gym by exit 9 doors are not closing properly. remedy: repair
Jul 29, 2024 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. at auditorium, bx #5, 6, and gym emergency lights are not lighting corr
Jul 29, 2024 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner. at exposure 1(front) flagpole lanyard in disrepair. remedy: repair and/or replace.
Jul 29, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1, 27-381. south wing generator not working for emergency lihting, basement room 3
Jul 29, 2024 · Penalty $625
Active - Class - 2
Exit door not self-closing. at 1 floor exit 1, 12, 13, main entrance and smoke 15 doors are not closing correctlty. remedy: repair/replace door.
Jul 29, 2024 · Penalty $625
Resolve - Class - 1
Failure to notify the department of an incident that resulted in a fatality or injury.note:worker injured finger requiring stiches taken to off site medical facility-alt 1 permit holder of 4 story site failed t
Jul 21, 2022
Resolve - Class - 2
Failure to maintain building in code compliant manner.observed at cellar level storage room next to boiler room being occupied by excess flamable material such as cardboard boxes,plastic,wood and gasoline power
Jun 14, 2022 · Penalty $625
Resolve - Class - 1
Bc3314.1 supported scaffold not comply w/code.note:at the time of my inspection of a 4 story bldg under active construction observed that supported scaffold not comply w/code:1)missing toe boards 2)missing mi
Aug 12, 2021 · Penalty $2,500
Resolve - Class - 2
Bc3301.2 failure to provide control access zone.note:at the time of myinspection of 4 story bldg on the 4th fl i observed missing door to the stairs w/out guardrails or established control access zone failure
Aug 12, 2021
Resolve - Class - 2
Failure to comply with the commissioners order contained in summons#violation#35559133z issued on 06-21-21 and to file a certificate or correction pursuan to 28-201.1 and 1rcny 102-01.bc 3314.4 inadequate scaf
Jul 28, 2021
Resolve - Class - 2
Failure to comply with the commissioners order contained in summons#violation#35559134k issued on 06-21-21 and to file a certificate or correction pursuan to 28-201.1 and 1rcny 102-01. faiure to maintain adequ
Jul 28, 2021
Resolve - Class - 1
1. repair car door safety edge .(c/u) 2 . provide properly leveling for top floor .( c/u ) . 3. missing dlm tag
Jun 29, 2021 · Penalty $1,250
Resolve - Class - 1
Bc33144-inadequate scaffold system.at the time of my inspeciton of a 4story alt 1 jobsite i observed inadequate supported scaffold missing netting inadequate plontey and not signed off in the scaffold company a
Jun 21, 2021
Resolve - Class - 2
Failure to maintain adequate housekeeping per section requirement.at the time of my inspection of a 4 story alt 1 construction site with thefloor stripping in progress, i observed inadequate housekeeping at lev
Jun 21, 2021
Resolve - Class - 1
Door zone restrictor not working tampered with disabled, in car phone not working.
Dec 27, 2019 · Penalty $1,250
Resolve - Class - 2
Missing spin out for cables
Dec 27, 2019 · Penalty $625
Resolve - Class - 2
Found kewanee steam boiler 1-boiler over 8' high, missing access ladder and work platform. correct violating condition and submit a certificate of correction.
Apr 22, 2019
Resolve - Class - 2
Found kewanee steam boiler. 1- boiler over 8' high, missing proper ladder and work platform correct violating condition and submit a certificate of correction.
Apr 22, 2019
Resolve - Class - 2
Failure to maintain building in code compliant manner. lack of emergency lighting for exits, exit discharges and public corridors per bc10061; 27-542. rmdy: repair and/or replace lighting. door stoppers. rmdy:
Jul 3, 2018
Resolve - Class - 2
Re-issue #35221241y.exit door not self-closing:at library rear exit #6 both doors dont self close.rem:repair/replace door
Jul 24, 2017
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: no fire stopping per bc 712-3; 27-345. note: @ electrical & boiler room. rem: provide/maintain fire stopping.
Nov 28, 2016
Resolve - Class - 2
Exit door not self-closing. noted: @ library exit#6 both doors dont self closeing. rem: repair/replace door.
Nov 28, 2016
Resolve - Class - 2
Failure to maintain bldg in code compliant manner: lack of emergency lighting for exits, exit discharges & public corridors per bc 1006.1, 27-542. note: @ gym all exit lights defective. rem: repair &/or replace
Nov 28, 2016
Resolve - Class - 2
Occupancy contrary.4 cars parked @ front yard via delivery curb cut & jumping curb to grass & grave area.rem:discontine illegal use.
May 18, 2012
Resolve - Class - 3
Missing sign.@ 3 flr stairway h,missing sign w/ key location for access to mesh gate to bulkhead.rem:provide sign or key access box w/ key.
May 18, 2012
Resolve - Class - 2
Failure to maintain adequate firestopping observed:@ electric room in cellar open diamond lathe transform over entry doors.rem:maintain firestopping
May 19, 2010
Resolve - Class - 2
Failure to maintain.observed water penetration from roof into auditorium ceilings,2flr hallway & rooms 203,213,216,219.rem:maintain bldg
May 19, 2010
Resolve - Class - 2
Failure to maintain.observed spalling plastic @ auditorium ceiling & exit corridor rooms 203,213,216,219 & 2flr main corridor.rem:maintain bldg
May 19, 2010
Resolve - Class - 3
Failure to maintain.observed:three broken glass window blocks @ auditorium exit a.rem:maintain bldg
May 19, 2010
Resolve - Class - 3
Failure to maintain.observed:step crack app 3'long @ n-e corner of auditorium west side of bulkhead stair c/d.rem:maintain bldg
May 19, 2010
Resolve - Class - 2
Sec 28-307.1 corridor width decreased by obstructions noted on all flrs tables chairs bookcases garbage carns rem: remove all obstructions
Feb 27, 2009 · Penalty $4,000
Resolve - Hazardous
Glazed block wall is spalling located at exit "k" on the 1st level leading to playground. remedy: repair block wall.
Jul 25, 2007
Resolve - Hazardous
Reissue:#34474980k basement cafeteria, exit corridor near kitchen blocked by desk, 4 chairs, table & two storage racks. remedy:remove all obstructions.
Jun 1, 2006
Resolve - Hazardous
Reissue:#34474979n roof chimney concrete cap, south end id cracked & spalling. remedy:repair/patch cap
Jun 1, 2006
Resolve - Hazardous
Reissue:#34474978l ground fl gymnasium,glazed block wall near "g" locaation has a vertical crack approx. 15 feet & opposite wall has a vertical crack approx. 6 feet remedy:repair/patch wall
Jun 1, 2006
Resolve - Non-hazardous
50a/50b/50c. 50a pipe down the safety valve discharge to a safe point, to prevent scalding. 50b provide an inclined ladder or stairway to provide safe access to the top of the boiler. 50c repair the damaged ins
Oct 25, 2005
Resolve - Non-hazardous
50a/50b/50c/51. 51 operating the boiler without a hydrostatic after a welded repair. 50a pipe down the safety valve discharge to a safe point to prevent scalding of persons. 50b provide an inclined ladder or st
Oct 25, 2005
Resolve - Non-hazardous
Failure to maintain building.defects noted:ground floor gymnasium glazed block wall near "g" location has a vertical crack approx.15'feet and opposite wall has a vertical 6'foot crack.remedy:maintain wall.make
May 4, 2005
Resolve - Non-hazardous
Reissue: (34431004n)failure to maintain building.defects noted:roof leaking in classrooms 203 and 214.also noted:roof leaking in classrooms 216,221 and 215 girls bathroom.remedy:maintain roof.make all necessary
May 4, 2005
Resolve - Non-hazardous
Exit passageway or corridor required width decreased by obstruction.noted:ground floor corridor blocked:gym by 2 desks,2 tables and 5 chairs;classroom g6 by 3 wood shelves,1 desk and 2 chairs;classroom g14 by 3
May 4, 2005
Resolve
Complaints
No HPD complaints in our records
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1952
- Floors
- 3
- Residential units
- —
- Building area
- 130,347 ft²
- Lot area
- 116,150 ft²
- Zoning
- R1-2A
- Community board
- 406
- Council district
- 29
- Block / lot
- 2248 / 100
- Assessed value
- $16,987,500
- Landmark / historic district
- No
Questions about 71-25 113 Street
Who owns 71-25 113 Street?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Parks And Recreation.
Does 71-25 113 Street have violations?
NYC HPD has no housing violations on record for this property.
Is 71-25 113 Street rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 71-25 113 Street built?
City records list 1952 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.