Violations at 40-30 99 Street

Queens, NY 11368 · BBL 4-01607-0001 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

21 DOB violations, newest first.

  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 19, 2003

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed

ECB violations

The newest 50 of 95 ECB violations. The city keeps the complete history.

  • Class - 2

    Reissue #35719894n date of issue: 05/15/2025. altered/change building occupied without a valid certificate of occupancy as per 28-118.3.1-28-228.3.2. noted tco #4607476-10 expired on 10/19/2023 no renewal on fi

    Apr 10, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue #35719895p date of issue: 05/15/2025. failure to maintain building in code-compliant manner. illumination for exits, exit dischargesand public corridors per bc 1006.1; 27-381. at the tume of inspection

    Apr 10, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue #35719896r date of issue: 05/15/2025. exit door not self-closing properly at the time of inspection at 1st floor exit-1, 2, 6, 7, 9 and 11 and 2nd floor stairway "j" one exit door due to rubbing on fram

    Apr 10, 2026 · Penalty $625

    Active
  • Class - 2

    Reissue #35719897z date of issue: 05/15/2025. failure to maintain building in code-compliant manner. at cellar level boiler room old coal chute hatch was heavily rusted and leaking water into the building. reme

    Apr 10, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue #35719898k date of issue: 05/15/2025. failure to maintain building wall(s) or appurtenances. at the time of inspection observed and noted at exp #398 street old building parapet walls have deteriorated

    Apr 10, 2026 · Penalty $6,250

    Active
  • Class - 2

    Failure to maintain building wall(s)or appurtenances.noted at exp#3(98street)old building parapet walls have deteriorated mortar joints between bricks.rem:maintain exterior building walls.

    May 15, 2025 · Penalty $2,500

    Active
  • Class - 2

    Failure to maintain building in code compliant manner.at cellar level boiler room old coal chute hatch was heavily rusted and leaking water into the building.rem:repair and/or replace.

    May 15, 2025 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self-closing.noted exterior doors at exit#1,2,6,7,9 & 11are not self closing properly due to rubbing on frames or saddles.rem:repair/replace door.

    May 15, 2025 · Penalty $625

    Active
  • Class - 2

    Reissue#35622667r failure to maintain building in code compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.approx.95% of emergency lights not working when tested th

    May 15, 2025 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35682668z altered/changed building occupied without a valid certificate of occupancy as per 28-118.3.1-28-118.3.2.tco#4607476-10 expired on 10/19/2023 no renewal or find co on file.building was occupied

    May 15, 2025 · Penalty $3,125

    Active
  • Class - 2

    Altered/changed building occupied without a valid certificate of occupancy as per 28-118.3.1-28-118.3.2. noted tco #4607476-10 expired on 10/19/2023, no renewal on file. building occupied as public school with

    May 29, 2024 · Penalty $1,250

    Active
  • Class - 2

    Reissue #35672782n. failure to maintain building in code-compliant manner: illumination for exit, exit discharges and public corridors per bc 1006.1; 27-381. noted approx. 75% of emergency lights not worthy whe

    May 29, 2024 · Penalty $1,562

    Active
  • Class - 2

    Reissue #35672781l. exit door not self-closing. noted exterior exit doors not opening or closing proper;y at: exit #1(2 doors), exit #11, exit #8, exit #9, exit #10 and exit #6. mentioned doors have defective c

    May 29, 2024 · Penalty $625

    Resolve
  • Class - 2

    Reissued#35643576j failure to maintain building in code-compliant manner:lack of emergency lights are not working properly at 5th floor 4th floor,3rd floor,2nd floor corridors and also auditorium hall.2nd floor

    May 19, 2023 · Penalty $3,125

    Active
  • Class - 2

    Reissued#35643575h exit door not self-closing at(5th fl)(4th fl)room#405,411 and also stair e.hallway and 1st floor exit#6 door not working properly when tested.rem:repair and/or replace doors.

    May 19, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Re-issued #35561132j failure to maintain bldg in code compliant mannernoted:at roof level bulkhead stair(f)observed vertical cracks through-out w/spalling & plaster & also paint.remedy:repair &/or replace

    May 17, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Re-issued #35561136r failure to maintain bldg in code-compliant mannerlack emergency light for exits.exit discharged 2 public corridors per bc1006.1/27-542.noted:at 2nd fl library w/(having)no emergency lights

    May 17, 2022 · Penalty $3,125

    Active
  • Class - 2

    Re-issued #35561137z exit door not self-closing.at time of inspection obseved at 5th floor,4th fl stairs & 3rd floor exit door not working properly when tested.remedy:repair &/or replace

    May 17, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Exit door not self closing noted:at(5th fl)stair e (4th fl)rooms 405,411 & stair e door checks were in disrepair/non-operational when testedremedy:repair/replace door

    May 5, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner lack of emergency lighting for exits,exit discharges & public corridors per bc1006.1/27-542.noted:at 2nd fl library w/{hauing}no emergency lights & no exit sign

    May 5, 2021 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner.noted:at 2nd fl library exit passageway/exit door blocked/obstructed by various item book-cases/chairs/desk etc.remedy:comply w/code remove obstruction.

    May 5, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner.noted:at(5th fl) stair e(4th fl) rm411,stair e,(1st fl) exit 6,stair e doors are in disrepair/racked.remedy:repair &/or replace.

    May 5, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner.noted:at roof level bulkhead stair f observed vertical cracks throughout w/spalling/plaster & paint. remedy:repair &/or replace.

    May 5, 2021 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self-closing. at 1st fl exit "6" left side 2 door,at 1stfl exit "5" left side 1 door,at 1st fl exit "9" left side 2 doors,1st fl exit "7" right side 2 doors are not self closing at the time of ins

    May 6, 2019

    Resolve
  • Class - 2

    Reissue: 35260357l failure to maintain bldg in code compliant manner noted: at time of inspection observed at 2nd floor, room 213 was divided into two rooms with full height partition and door with no ventilat

    May 4, 2018

    Resolve
  • Class - 1

    Inadequate safety measures/operation of a crane in a unsafe manner.at time of inspection of cn997/17,cd4977 i observed inv#9688 mark finegan in operation of a 276 ton max capacity crane. i was provided with the

    Dec 6, 2017 · Penalty $10,000

    Resolve
  • Class - 2

    Work does not conform to approved construction documents and or approved amendments.at time of inspection respondent allowed cn977/17,cd4977a 276 ton max capacity crane to set up and operate contrary to the app

    Dec 6, 2017 · Penalty $250

    Resolve
  • Class - 2

    Failure to safeguard all persons and property workers by construction operation, stop all work. noed at time of inspection worker had to walk more than 3'on ledge to reach to his landyard, because no other pro

    Jul 21, 2017 · Penalty $400

    Resolve
  • Class - 2

    Reissue #35214437y failure to maintain building in code compliant manner. noted at inspection obsered at 2nd floor room 213 was divided into two rooms with full height partition and door with no ventilation

    May 10, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: lack of emergency lighting for exits, exit discharges & public corridors per bc1006.1; 27-542. noted: emergency light packs not working @ 5th flr gym over exit

    Oct 14, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner (interior). reissued violation# 35147093m issued on 9/3/15 2nd flr rm# 213 was divided into 2 rooms w/ full height partition & door, no natural light or ventila

    Oct 14, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg wall(s)or appurtenances.@ transportable classrm designated t1 thru t10 metal apron dislodged w/ exposed rusting.edges & allows vermin to access crawl space below classrm @ various locat

    Sep 3, 2015

    Resolve
  • Class - 2

    Reissue nov 35108253k.failure to maintain bldg in code-complaint manner.@ 2nd sty rm #213 adjoining public corridor & rear office lacks adequate natural light & ventilation.(rm used as an office)occupied space.

    Sep 3, 2015

    Resolve
  • Class - 3

    Defective windows throughout bldg,windows not staying open.rem:repair /replace windows.

    Sep 5, 2014

    Resolve
  • Class - 2

    Reissue 35023787m.no ventilation for occupied space @ 2fl office room 213.rem:provide ventilation.

    Sep 5, 2014

    Resolve
  • Class - 2

    Windbreak metal skirting rusted/deteriorated/holes at base of transportable units 1 thru 10 various locations throughout metal rusted through with holes allowing wind & vermin to enter crawl space below units.

    Jul 17, 2013

    Resolve
  • Class - 2

    Doors not closing rusted jams and door base saddles heaving at mini school exit discharge doors 1,2,&3. rmdy: repair and/or repalce doors noted.

    Jul 17, 2013

    Resolve
  • Class - 2

    No natural/mechanical ventilation for occuied space (office) at 2nd story room 213. rmdy: provide ventilation or discontinue use as office.

    Jul 17, 2013

    Resolve
  • Class - 2

    Work without a permit:at 2nd floor room 213,full height partition installed w/door divids room back & front w/no fresh in front section to corridor used as office.rem:obtain permit if feasible or restore to pri

    Apr 3, 2012

    Resolve
  • Class - 2

    Partial obstruction at: 3,4,5th floor fire corridors have tables, chairs, boxes & numerous rolling carts. remedy: remove all items, maintain corridor width clear.

    Apr 3, 2012

    Resolve
  • Class - 2

    Re-34848059y.interior concrete ceiling is missing a section having the rebars exposed located in the paint room @ cellar level.rem:repair &/or replace concrete in paint room.

    Mar 9, 2011

    Resolve
  • Class - 2

    Interior classroom doors are missing.door closer in various rooms on every flr (doors are not self closing).rem:provide door closer on classroom doors.

    Mar 9, 2011

    Resolve
  • Class - 2

    Exit door #6 & kitchen exit to parking lot on the 1st flr level is defective.door closer & door hinge not fully attached to door frame.exit e & f on the 3 flr level is not self closing caused by door closer.rem

    Mar 9, 2011

    Resolve
  • Class - 2

    The glazed block wall is cracked vertically located on the 1st flr level by exit 9,10 is approx 2' long.rem:repair glazed block wall.

    Mar 9, 2011

    Resolve
  • Class - 2

    Re-34855017l.the concrete ceiling is spalling w/ the exposed rebars located in the fan blower room on the cellar level.rem:repair/replace concrete on the ceiling.

    Mar 9, 2011

    Resolve
  • Class - 2

    27-371(b) re-34848060l.interior classroom doors w/ the vision panel does not have the wire mesh install on various room in all flrs w/ plexiglass.rem:install wire mesh w/ glass.

    Mar 9, 2011

    Resolve
  • Class - 2

    Re-34855013y(partial).the plaster is spalling on the walls & ceiling located in room 509 & 510 on the 5 flr level.rem:repair &/or replace plaster on walls/ceiling.

    Mar 9, 2011

    Resolve
  • Class - 2

    Failure to maintain building exterior noted: steel steps located over auditorium have holes. remedy: maintain building.

    Apr 28, 2010

    Resolve
  • Class - 2

    Failure to maintain building exterior noted: dislodge & cracked flashing at parapet way. remedy: maintain building.

    Apr 28, 2010

    Resolve
  • Class - 2

    Failure to maintain building noted: water penetration at north cast basement wall & gas room. remedy: maintain building.

    Apr 28, 2010

    Resolve