Violations at 21-21 Ditmars Boulevard

Queens, NY 11105 · BBL 4-00880-0001 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

20 DOB violations, newest first.

  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 in 2020

    Jun 20, 2021

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 6, 2006

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 19, 2003

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    Oct 17, 2001

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 16, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed

ECB violations

The newest 50 of 85 ECB violations. The city keeps the complete history.

  • Class - 2

    Failure to safeguard the public and property affected by construction operations. at time of inspection observed parapet wall missing aroundentire sidewalk shed at exposure #3(playground) causing dangerous haza

    Aug 12, 2026 · Penalty $5,030

    Resolve
  • Class - 2

    Miscellaneous chapter 33 violations. at time of inspection, observed aloose netting at multiple locations at exposure #2 making a safety hazard to public by potentially flying debris. remedy: comply with code.

    Aug 12, 2026 · Penalty $2,530

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner: no fire stopping per bc 712.3; 27-345. noted: at the time of inspection observed firestopping missing in various places around electric meter room. remedy:

    Feb 4, 2026 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self-closing. noted: on the 1st floor exit 6 and exit 7 exterior doors not self-close properly. remedy: repair/replace door.

    Feb 4, 2026 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner: illuminations for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: emergency lights do not work when tested, 1st flr-#1, #2. 5th f

    Feb 4, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: interiorsmoke doors do not self-close properly. 5th flr-"staircase b", "staircase c". 4th floor-"staircase c", "staircase d". 2nd flr-"staircase b",

    Feb 4, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissue#35671726y failure to maintain building in code-compliant manner.roof level bulkhead have cracks and spalling.rusted rebars exposed.rem:repair and/or replace.

    Feb 29, 2024 · Penalty $1,562

    Active
  • Class - 2

    Reissue:35636497x-failure to maintain building in code-compliant manner:roof level bulkheads all of them cracks and spalling,rusted rebars exposed.rem:comply with code.

    Feb 14, 2023 · Penalty $1,562

    Active
  • Class - 2

    Reissue:35542758h-failure to maintain building in code-compliant manner:vert cmacks on wall at gas meter room.rem:comply with code.

    Feb 14, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner noted:@roof level bulkhead4&5 cracks in wall&@bulkhead2&3 wall&ceiling in state of disrepair w/spalling concrete/plaster exposed rusted rebard due to water penet

    Mar 16, 2022 · Penalty $625

    Active
  • Class - 2

    Reissued #35542758h failure to maintain building in code compliant manner.noted:at basement level gas meter room vertical crack in cmu wall missing firestopping around pipe in cmu wall.remedy:repair and/or repl

    Mar 16, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Oil leak at burner,cover missing on low water cut off,bolts & dogs missing on front door on boiler,valve missing on oil suction line b/4 anti syphon

    May 10, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner noted:observed duringinsp fireproof selfclosing door by rm455&staircase exit doors by rm409,355,209&1fl exit4 werent selfclosing due to being "racked".repair &/o

    Mar 22, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner.noted:observed duringinsp of bsmt gasmeterrm,vert crack on wall approx4'l.repair &/or replace.

    Mar 22, 2021 · Penalty $625

    Resolve
  • Class - 2

    Reissue35486605n failure to maintain bldg in codecompliant manner.noted:observed during insp of bsmt boilerrm along courtyard(exp4)wall,cracks on wall&ceiling,also missing pieces of concrete.wall porous allowin

    Mar 22, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissued35486606p exit door not selfclosing noted:observed during inspexterior exit door@exit4-5&exterior exit door@exit9 werent selfclosingdue to excessive rubbing &/or frame being in disrepair.repair/replace

    Mar 22, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Exit door not self closing properly.at 5th fl. one door near rm no 555one exit door near stair"e" at 4th fl.near stair "e" 2 doors,at 3rd floor at zim near exit "d" 1 door & near stair "e" 1 door.at 2nd floor n

    Mar 5, 2020 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35402364k date:03/22/19.failure to maintain building code in code compliant manner at boiler room at courtyard side of building exp-4 multiple cracks along wall ceiling at courtyard side.remedy:repair a

    Mar 5, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. at corner of ditmars blvd&21 st near room no 501 at mens room at 5th fl&at staircase "f" and room no 501 from roof&outside wall water penetrating different

    Mar 22, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner illumination forexits,exit discharges and public corridors per bc 1006.1;27-381 at staircase h all 5 floor 1st fl,2nd fl,3rd fl,4th fl,5th fl at one place 2

    Mar 22, 2019

    Resolve
  • Class - 2

    Reissue#35316803m date of issue 1/30/18 failure to maintain building code in code compliant manner at boiler room at courtyard side of building exp-4 multiple cracks along wall ceiling at courtyard side. remain

    Mar 22, 2019

    Resolve
  • Class - 2

    Reissue#35316806h date of issue 1/30/18 exit door not self closing at 3rd fl near room 354 right hand side door no self closing,also on 3rd fl exit 6 door hits jam,at 1st fl way to playground exit 6-6 middle ex

    Mar 22, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. illumination for exits, exit discharges and public corridors per bc 106.1 27-318. note at 3rd floor gym exit door d emergency lights not lite.rmdy:repair and

    Jan 30, 2018

    Resolve
  • Class - 2

    28-301.1 failure to provide natural or mechanical ventilation to occupied space per mc 401.2 note at basement level in boiler room storage area stored gas lawn mower and weed wacker and leaf blower.rmdy:comply

    Jan 30, 2018

    Resolve
  • Class - 2

    Exit door not self closing: note at 3rd floor by room 354 right hand side door not closing broken hinge also on 3rd floor exit 6 door hits jam. rmdy: repair or replace door.

    Jan 30, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. note at 3rd floor room 313 computer room electrical panel door ot staying closed. rmdy: repair and or replace.

    Jan 30, 2018

    Resolve
  • Class - 2

    Reissued violation #35235113k failure to maintain building in code compliant manner. noted: at electric meter room at basement level spalling concrete due to water penetration at room #2. rmdy: repair and/or

    Jan 30, 2018

    Resolve
  • Class - 2

    Reissued #35229014y failure to maintain building in code compliant manner. note: at boiler room at courtyard side of building exp4 multiple cracks along wall at ceiling at courtyard side. also

    Jan 30, 2018

    Resolve
  • Class - 2

    28-301.1 unlawful display of artwork in corridors greater than 20% per fdny 2008 code: fc 803.3.2 noted: artwork displayed in corridors throughout the school is more than the 20% allowed. rmdy: comply with

    Mar 31, 2017

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. noted: at boiler room at courtyard side, multiple cracks all along courtyard side. concrete fell off the steel beams and other areas exposin

    Mar 31, 2017

    Resolve
  • Class - 2

    Reissue #35222221p failure to maintain building in code compliant manner: noted: spalling concrete at electric meter room 2 due to water penetration. rmdy: comply w/notice of violation.

    Mar 31, 2017

    Resolve
  • Class - 2

    Reissue #35333393l failure to maintain building in code compliant manner: noted: spalling plaster at all the bulkhads at 5th flr due to water penetration and spalling plaster at room 403,503. rmdy: comply w/no

    Mar 31, 2017

    Resolve
  • Class - 2

    Reissue nov 35101903l.failure to maintain bldg in code compliant manner.noted:@roof,@stair e,bulkhead,spalling masonry @ wall(s).

    Dec 2, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. no fire stopping per bc1006.1, 27-542. noted: at electric meter room 1 penetrations at ceiling and at electric meter room 2, penetrations at ceiling. rmdy:co

    Dec 2, 2016

    Resolve
  • Class - 2

    Reissue nov35084638h.exit door not self closing.noted:defective door throughout bldg in multiple stairwells on all flrs.rem:comply w.code.

    Dec 2, 2016

    Resolve
  • Class - 2

    Reissue nov 351019041y.failure to maintain bldg wall(s)and appurtenances.noted:@parapet,spalling limestone above 5th flr windows.rem:comply w.code.

    Nov 28, 2016

    Resolve
  • Class - 2

    Failure to maintain.note:spalling limestone.@ roof parapet band above 5fl windows(main entrance)rem:maintain as per code

    Feb 4, 2015

    Resolve
  • Class - 2

    Reissue #35023812p.fail to maintain:note-spalling plaster walls,location:roof bulkhead stair"e"rem:maintain as per code.

    Feb 4, 2015

    Resolve
  • Class - 2

    Reissue #35084639j.failure to maintain.note:backup batteries/lighting defective @ emergency lights.locations gyn/caterteria,auditorium.rem:maintain as per code.

    Feb 4, 2015

    Resolve
  • Class - 2

    Defective emergency lighting noted at gym,auditorium, cafeteria multiple lights not operational.rem:repair fixtures.

    Jan 17, 2014

    Resolve
  • Class - 2

    Reissue 35023811n. defective doors throughout.multiple staircase doorsdragging/hitting frame stairwell doors on all levels.rem:repair/replace doors.

    Jan 17, 2014

    Resolve
  • Class - 2

    Loose window screens. at 5th flr above entry, 4th flr southeast along ditmars blvd & 3rd flr southwest along ditmars blvd, upper and lower exterior window screens are dislodged and subject to falling to fence

    Jul 8, 2013

    Resolve
  • Class - 2

    Spalling plaster. at stwy"e" bulkhead,various areas with spalling plaster throughout bulkhead. rmdy: repair plaster surfaces.

    Jul 8, 2013

    Resolve
  • Class - 2

    Defective doors. at 3rd flr stwy "d" with broken door closer & 4th flrstwy"e" with broken hinge. rmdy: replace door closers and hinge.

    Jul 8, 2013

    Resolve
  • Class - 1

    Defective stone facade. at parapet roof stones along ditmars blvd, spalling and scaling of stone work atop masonry brick - 5th flr adjacent to main entry. remedy: make safe immediately - repair stone masonry.

    Mar 20, 2012

    Resolve
  • Class - 2

    Corridor w/ combustible material @ 2nd, 3rd, 4th, 5th floor corridor have floor to ceiling and hanging wall to wall combustible art work throughout the fire corridor. remedy: remove excessive / combustible item

    Mar 31, 2011

    Resolve
  • Class - 2

    Defective door closers the fire proof self closing doors have broken door checks and do no self close properly ( various location throught out ) remedy: replace door checks

    Mar 31, 2011

    Resolve
  • Class - 2

    Reissue # 34871343r cracked concrete ceiling @ cellar level, electrical room has 4' long crack in concrete ceiling. remedy: repair concrete ceiling

    Mar 31, 2011

    Resolve
  • Class - 2

    Interior walls, the plaster is cracked/spalling located in room 418,501,503,506,516 & roof bulkhead e. remedy: repair/replace plaster.

    Aug 3, 2010

    Resolve
  • Class - 2

    The concrete ceiling in the electrical room at cellar level is crackedapprox 4' long. remedy: repair/replace cracked concrete ceiling.

    Aug 3, 2010

    Resolve