Violations at 22-41 41 Street
Queens, NY 11105 · BBL 4-00794-0017 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
4 DOB violations, newest first.
- Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed
ECB violations
46 ECB violations, newest first.
- Class - 2
Failure to maintain building in code-compliant manner. at time of inspection swollen cement finish, missing cement finish and cracks were observed in corner on retaining wall at exposure #2. remedy: repair and/
Feb 3, 2026 · Penalty $1,250
Active - Class - 2
Reissue#35678680j failure to maintain building in code compliant manner.cellar level boiler room,gas motor room,electrical room,water comingfrom foundation walls spalling and deterioration.rem:repair and/or rep
Mar 18, 2025 · Penalty $3,125
Active - Class - 2
Reissue 35665547h faiure to maintain building in code-compliant mannerroom 311,rm 202,209,211 room 102 and gas meter room in cellar doors not working properly dont fully close.rem:repair and/or replace.
Feb 23, 2024 · Penalty $1,562
Resolve - Class - 2
Reissue 35665549l failure to maintain building in code-compliant manner.cellar level boiler room,gas meter room,electrical meter room water coming in from foundation walls.rem:repair and/or replace.
Feb 23, 2024 · Penalty $1,562
Resolve - Class - 2
Re-issue #35650966k failure to maintain building in code-compliant manner. observed at cellar level, gas and electrical meter rooms water coming into foundation wall. remedy: repair and/or replace
Feb 9, 2023 · Penalty $1,562
Resolve - Class - 2
Re-issue#35548436m/35650963p observed emergency lights are not workingat cellar level,1st fl,2nd fl and 3rd fl such as #5,13,14,21,25,24,35,36,37. these lights are not operational when i tested at time of inspe
Feb 9, 2023 · Penalty $1,562
Resolve - Class - 2
Re-issued#35650965z failure to maintain building in code-compliant manner. observed at 3rd fl rm#311 and 2nd fl rm#202,209,211 and also 1st fl rm#102 and cellar level gas meter room doors are not working proper
Feb 9, 2023 · Penalty $1,562
Resolve - Class - 2
Reissue#35548437y noted:the boiler,gas and electrical meter rooms at basement level have water coming in from the foundation wall.rem:repairand/or replace.
Mar 17, 2022 · Penalty $1,562
Resolve - Class - 2
Reissue#35548439h noted:at rooms 311 by teacher's restroom,202,209,211(computer room),102 and the gas meter room at cellar level;the doors are not working properly.rem:repair and/or replace.
Mar 17, 2022 · Penalty $1,562
Resolve - Class - 2
Reissue#35548440p noted:at cellar level smoke by cafateria kitchen,smoke at exit 8,and smoke at exit 9;the exit doors are not working properly.rem:repair/replace door.
Mar 17, 2022 · Penalty $1,562
Resolve - Class - 2
Reissue#35548436m noted:at 3rd floor em#33 stairwell #,em#31 by stair d,auditorium,#29 at stairwell b,2nd floor #26 at stairwell b,#25 at stairwell a,1st floor #21 at stairwell a,#24 at stairwell b,#11 by exit
Mar 17, 2022 · Penalty $1,562
Resolve - Class - 2
Exit door not selfclosing.noted:@3fl staira by 310,multipurpose rm smoke by stairc,smoke by exit8,cafeteria smoke@exit9,smoke by cafeteria kitchen,smoke by staird&smoke by exit5;exit doors arent working properl
Mar 10, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in codecompliant manner.noted:@3fl rm308,1fl rm106,electrical closet by 106&cellar gasmeter rm,doors arent working properly.repair &/or replace.
Mar 10, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in codecompliant manner:use of prohibited door &/or hardware per bc1008.1.8;27-371j.noted:@all levels thruout bldg:have kickdown door holders installed on various classrms&exit/smoke do
Mar 10, 2021 · Penalty $625
Resolve - Class - 2
Reissue35486670j noted:@bsmt level boiler,gas&electrical meter rm;havewater damage to walls from foundation wall leaks.repair &/or replace.
Mar 10, 2021 · Penalty $1,562
Resolve - Class - 2
Reissue35486671l noted:@3fl em33@staira,em32,#31 by staird,2fl em26 by203,25 by staira,21 by staira,1fl em24 by stairb,cellar level cafeteria em8 by exit8,em1 by exit4 exterior door;emergency lights inoperative
Mar 10, 2021 · Penalty $1,562
Resolve - Class - 2
Exit door not self closing properly at 3rd fl auditorium one exit doorstair'b'&exit 6 & 1 exit door near stair'a'& exit 4. 2nd fl one exit door near stair'a'& exit 4. at 1st fl main entrance (2nd dery)entrance
Mar 13, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner illumination for exits,exit discharges & public corridors per bc 1006.1;27-381 at 3rd fl light no.26.31.33 3 place each place 2 lights,2nd fl light no. 25,26 at
Mar 13, 2020 · Penalty $625
Resolve - Class - 2
Reissue#35383924z date of issue 3-11-19 failure to maintain bldg code comliant manner at basement level boiler room,gas room & electrical room water damage to walls due to water penetration through. remedy: rep
Mar 13, 2020 · Penalty $1,562
Resolve - Class - 2
Exit door not slef closing .at 3rd floor multipurpose hall back side of stage right side on e door & basement boiler room exit to play ground exi 10.one door exit door not self closing at the time of inspection
Mar 11, 2019 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner illumination for exits,exit discharges and public corridors per bc 1006.1;27-381 at 3rd fl at multi purpose hall light no -30 ,32 at 3rd fl light no-28 1st
Mar 11, 2019 · Penalty $625
Resolve - Class - 2
Reissue #3529071h date of issue 01.23.2018.failure to maintain building in code compliant manner at basement level boiler room,gas room and electrical room water damage to walls due to water renetration through
Mar 11, 2019
Resolve - Class - 2
Reissue #35235052x/failure to maintain building in code compliant manner.note:at basement level,boiler room,gas room,and electrical room.water damage to walls due to water penetration throughtout walls.rem:repa
Jan 23, 2018
Resolve - Class - 2
Exit door not self closing. noted: at 3rd fl,auditorium area,exit doors,left & right stage,have defective in the top hinge & not close properly. remedy: comply w/code/repair the doors.
Mar 9, 2017
Resolve - Class - 2
Failure to maintain bldg in code complaint manner. noted: at 3rd fl,corridor close to rm#303 & bulkhead stairway'a',water damage to ceiling due to water penetration throu roof. remedy: comply w/code/repair ceil
Mar 9, 2017
Resolve - Class - 2
Failure to maitnain bldg in code complaint manner. noted: at basement level,boiler room,gas room & electric room,water damage to wall due towater penetration through wall. remedy: comply w/code/repair the wall.
Mar 9, 2017
Resolve - Class - 2
Reissue #34906075r defective flr. at 1st flr exit #7 missing & broken asphalt flr tile with uneven sub flooring creating a trip condition. rem:repair flooring.
Mar 14, 2012
Resolve - Class - 2
Excessive flammable art work in corridors. at 1st,2nd,& 3rd fl corridors,excessive combustible art work lines all walls creating fire hazard. remedy: remove all items.
Mar 25, 2011
Resolve - Class - 2
Partial obstruction of corridors. 3rd floor fire corridor is partial obstructed w/tables,chairs tall cabinets,tv,& card board items. remedy:remove all item,maintain corridor width.
Mar 25, 2011
Resolve - Class - 1
Sec. 1014.2;27-361 obstructed exit door. exit door #10 is jammed in the frame & saddle & can not be opened. remedy: replace exit door.
Mar 25, 2011
Resolve - Class - 2
Reissue: #34847529p defective floor. 1st floor exit 7,missing floor tiles w/eroded & uneven subflooring,creating a trip condition. remedy: repair floor.
Mar 25, 2011
Resolve - Class - 2
Interior floor tiles are missing & wooden sub- floor is rotten & missing causing a tripping hazardous condition located on the 1st floor by exit 7. remedy: repair/replace floor tiles & sub floor
May 21, 2010
Resolve - Hazardous
Reissue #34393580r. failure to maintain - interior. plaster walls & ceilings are spalling, cracking & mildew forming due to water penetration in stairwel b, rooms 112, 210, 308, 310, 311, 312, auditorium
Aug 17, 2007
Resolve - Hazardous
Reisssue: #34393579j. failure to maintain - exterior. water penetration thru walls in stairway b & rooms 112, 210, 211, 212, 308, 310, 311, 312 & the 3rd floor auditorium roof leaking water & damaging the
Aug 17, 2007
Resolve - Non-hazardous
Spalling plaster at stairwell b 1st & 3rd fl. 3rd fl auditorium & rms 110, 312, 311, 310, 308, 303, 210, 211, 212, 112 damaged walls. remedy: repair walls.
May 19, 2006
Resolve - Non-hazardous
Reissue: 34474788k. water penetration through walls at stairwell b 1st& 3rd fl, rooms, 110, 312, 311, 310, 308, 303, 210, 211, 212, 112, & 3rd fl auditorium. remedy:repair water penetrated exterior walls.
May 19, 2006
Resolve - Non-hazardous
Basement stairwell d blocked by 25 chairs and writing board. remedy: remove furniture form stairwell d.
May 19, 2006
Resolve - Non-hazardous
Exit passageway of corridor required width decreased by obstruction. noted: basement stairwell d blocked by 4 tall metal cabinets and 41 stacked corrugated boxes. also noted: basement stairwell c blocked at
Apr 15, 2005
Resolve - Non-hazardous
Failure to maintain building. defects noted: plaster walls with water penetration from exterior walls at landing 3 floor stairwell d, class rooms 310 and 210. remedy: maintain wall. make all necessary repairs.
Apr 15, 2005
Resolve - Non-hazardous
Failure to obtain permit for temporary construction of sidewalk- shed a front portion of building. remedy: obtain permit.
Jan 4, 2002
Resolve - Non-hazardous
Failure to provide emergency power exit lights on all floors corridors and stairs.failure to provide emergency power to exit lights on all floors,corridor, and stairs.failure to provide emergency power to exit
Feb 21, 2001
Resolve - Non-hazardous
Failure to provide 3" floor number signs at stair landing on all floors.failure to provide 3" letter sign i.d. signs on all floors.remedy:provide signage as per local law 16/84 code.
Feb 21, 2001
Resolve - Non-hazardous
Failure to maintain upon inspection of the above address the following condition exist.(1)crack in wall by door,from floor to top of door,rooms 106,309.remedy:make all repairs.
Jan 9, 2001
Resolve - Non-hazardous
Failure to maintain building. defects are: spalling and crack conc on window sill on south facade @ 3rd pl ext. crack pavement @ south east side of bldg next to cr park. crack on walls in room 104,106 & 108. no
Mar 29, 2000
Resolve - Non-hazardous
Failure to maintain. defect. no emergency lighting in stairwells. spalling plaster and peeling paint thru-out entire building. remedy: obtain permit, install lighting, repair plaster and paint.
Apr 5, 1999
Resolve - Non-hazardous
Failure to maintain. parapets and all walls, loose & crumbling mortar allowing water to leak through causing spalling plaster & peeling paint. windows nonoperable. remedy: make all repairs, obtain all
Apr 5, 1999
Resolve