Violations at 30-45 42 Street
Queens, NY 11103 · BBL 4-00696-0014 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
24 DOB violations, newest first.
- Low pressure boiler boiler required
Violation issued-failure to file 2021 external low pressure inspection
Jun 30, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2021 external low pressure inspection
Jun 30, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2020 external low pressure inspection
Jun 30, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2020 external low pressure inspection
Jun 30, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2018 external low pressure inspection
Jun 20, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2018 external low pressure inspection
Jun 20, 2023
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued-failure to file 2018 external low pressure inspection
Jun 20, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2018 external low pressure inspection
Jun 20, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2022 external low pressure inspection
Apr 25, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued-failure to file 2022 external low pressure inspection
Apr 25, 2023
Dob violation - active - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2017 inspection report
Jan 17, 2020
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2017 inspection report
Jan 17, 2020
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst
Sep 6, 2019
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2016 inspection report
Apr 6, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 3, 2015
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 7, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 7, 1994
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jun 7, 1994
Dob violation - dismissed
ECB violations
The newest 50 of 97 ECB violations. The city keeps the complete history.
- Class - 2
Reissue ecb #35693194j. failure to maintain building in code-compliantmanner. at the time of inspection i observed ceilings and walls spalling and cracking at bulkheads a, b, d, e and f. remedy: repair and/or r
Feb 6, 2026 · Penalty $3,125
Active - Class - 2
Reissue #35693190m. failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. at the time of inspection noted several emergency l
Feb 6, 2026 · Penalty $3,125
Active - Class - 2
Reissue #35693192x. at the time of inspection noted: smoke doors not self-closing. stairway y-4th floor, stairway d-2nd floor, auditorium-2 entry locations, first floor by elevator, first floor by exit 3 and 12
Feb 6, 2026 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code compliant manner.noted at bulkheads a,b,d,e & f ceiling & walls spalling and cracks.rem:repair and/or replace.
Mar 18, 2025 · Penalty $1,250
Active - Class - 2
Reissue#35676420m failure to maintain building in code compliant manner.noted roof level from room old side running & step crack throughout walls.rem:repair and/or replace.
Mar 18, 2025 · Penalty $3,125
Active - Class - 2
Reissue#35676471y failure to maintain building in code compliant manner.noted at corridor by elevator,smoke by 505,510,4 fl.corridor by 412(5)by stair f,corridor by 409.corridor 402,3fl.corridor by 308,313,2fl
Mar 18, 2025 · Penalty $3,125
Active - Class - 2
Reissue#35676472x failure to maintain building in code compliant manner.noted at cellar electrical room water penetration and porous foundation walls.rem:repair and/or replace.
Mar 18, 2025 · Penalty $3,125
Resolve - Class - 2
Reissue#35676473h failure to maintain building in code-compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:at 2 floor box#2b,2l,1 fl and 3 lights,caft. 2 ligh
Mar 18, 2025 · Penalty $3,125
Active - Class - 2
Reissue#35676474j exit door not self-closing.noted exit 9,12,5 kitchendoors are not closing properly.rem:repair/replace door.
Mar 18, 2025 · Penalty $1,562
Resolve - Class - 2
Exit door not self closing.noted exit door#9 rubs on frame,difficult to open exit#12 rubs on saddle not self closing fully.rem:repair and/orreplace.
Feb 27, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner:illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted existing emergency lights hot operative in auditorium(2 lights) in nor
Feb 27, 2024 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:in cellar level electrical room water penetrating ceiling slab at for left corner.rem:repair and/or replace.
Feb 27, 2024 · Penalty $625
Resolve - Class - 2
Reissue#35671977z failure to maintain building in code compliant manner.noted interior fireproof self closing doors not closing or opening properly at several locations:5th fl smoke doors by room 505 & old/new
Feb 27, 2024 · Penalty $625
Active - Class - 2
Reissue#35671978k failure to maintain building in code compliant manner.noted:at roof level fan room vertical crack in wall that runs along the chimney additionally outside the fan room chimney has missing mort
Feb 27, 2024 · Penalty $625
Active - Class - 2
Reissued#3564437p failure to maintain building in code-compliant manner.at roof level in the far room on the old building sold has a runningcrack and spalling and missing masonry in various area.rem:repair and
Feb 14, 2023 · Penalty $1,562
Active - Class - 2
Exit door not self-closing smoke door on 3rd floor next stwy d not closing properly also 2 fl next stwy d,2fl stwy a & south play/lunch roomdoor.rem:repair/replace door.
Feb 14, 2023 · Penalty $625
Active - Class - 2
Failure to maintain building in code compliant manner:illumination forexits,exit discharges and public corridors per bc1006.1;27-381.noted the emergency lights 1-x and 1-n at the cafeteria are inoperable when t
Mar 11, 2022 · Penalty $625
Resolve - Class - 2
Reissue#35548356m.noted at 5th floor smoke by 511,4th floor smoke by 411a by elevator,stair y by 470,3rd floor smoke by 311,2nd floor smoke by 213,smoke by 211,auditorium entrance door on the right,right rear s
Mar 11, 2022 · Penalty $1,562
Resolve - Class - 2
Reissue#35548357y.noted at roof level,the fan room has running cracks and spalling and missing masonry in various areas throughout.remedy:repair and/or replace.
Mar 11, 2022 · Penalty $1,562
Active - Class - 2
Failure to maintain bldg in codecompliant manner:illumination for exits,exit discharges&public corridors per bc1006.1;27-381.noted:@auditorium,1fl em1-j by stairc,cafeteria em1-v by staird,&em1-p@staird stairwe
Mar 17, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in codecompliant manner.noted:@cellar level electrical meterrm;has holes in ceiling in various areas thruout.repair&/or replace.
Mar 17, 2021 · Penalty $625
Resolve - Class - 2
Reissue35486654j noted:@roof level fanrm;has missing masonry@ceiling&running step cracks on walls.repair &/or replace.
Mar 17, 2021 · Penalty $1,562
Active - Class - 2
Reissue35486656n noted:@4fl smoke by elevator stairy smoke by 470,smoke by 308,stairf by 213, auditorium single entrance,side&right rear 1flsmoke by elevator,smoke by exit12,exterior exit door@exit6,entrance@so
Mar 17, 2021 · Penalty $1,562
Resolve - Class - 2
Exit door not self closing properly,at 2nd fl. at staircase'f'near rm#213 2 door are not self closing properly,at 2nd fl corridor exit door near elevator'a'2 door are not self closing properly at the time of in
Feb 18, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. illumination for exits,exit discharges at public corridors per bc 1006.1;27-381 in auditorium right side piller from main entrance one place 3 lights are not
Feb 18, 2020 · Penalty $625
Resolve - Class - 2
Reissue#35401637m date of issue 2-20-19 failure to maintain bldg in code compliant manner at roof level fan room(east side)vertical cracks on wall & at ceiling breaking concrete,oxidizing steel room.
Feb 18, 2020 · Penalty $1,562
Active - Class - 2
Failure to maintain building in code compliant manner illumination forexits exit discharges and public corridors per bc 1006.1; 27-381. at cellar level cic, cid, at first fl 1c, 1d, 1f,1p,1g,1h and first floor
Feb 20, 2019
Resolve - Class - 2
Reissue #35291029y date of issue 01.25.2018 failure to maintain building in code compliant manner at roof level fan room (east side) vertical cracks on walls and at ceiling braking concrete, oxidizing steel. rm
Feb 20, 2019
Active - Class - 2
Reissue violation #34901876f failure to maintain building in code compliant manner.note:at roof level fan room(east side)vertical cracks on walls and at ceiling braking concrete,oxidizing steel.rem:repair or re
Jan 25, 2018
Active - Class - 2
Exit door not self closing. noted: at bulkhead staircase e 7 f,smoke door next to rm#308,audit area,exit#12 at 1st fl. the doors have defective in the top hing & closer. remedy: comply w/code/repair or replace.
Mar 6, 2017
Resolve - Class - 2
Failure to maintain bldg in code complaint manner. noted: at stairway'a'between 2nd & 3rd fl. the glass wall between 2 flights is broken. remedy: comply w/code/replace the glass.
Mar 6, 2017
Resolve - Class - 2
Reissue#34901876y failure to maintain bldg in code complaint manner. noted: at roof level,fan room(east side),vertical cracks in various places. remedy: comply w/code/repair vertical cracks.
Mar 6, 2017
Active - Class - 1
Failure to maintain. noted ongoing construction work being done after 4pm inside multiple rooms on multiple levels. crews working in corridors with material & tools all while after school programs in progress.
Mar 26, 2015
Resolve - Class - 2
Bc3310l8,27-1009d,rcny26 failure to adequately carry out duties of site safety mgr as outlined in dob manual with regards to performing periodic inspections to verify compliance w/sub chapter 19 (chapter 33) as
Feb 4, 2014
Resolve - Class - 1
Failure to safeguard all persons & property affected by construction operations. noted at existing occupied public school construction operations at extension causing unsafe condition onsite,also failure to
Feb 4, 2014 · Penalty $2,400
Resolve - Class - 1
Sec. 3314.8 failure to provide required guardrails & toe boards for scaffold platform. noted on multiple scaffold platforms no guardrails or toeboards in place. remedy: provide guardrails toe boards.
Feb 4, 2014 · Penalty $1,600
Resolve - Class - 1
Sec. 3314.1;27-1009a scaffold has not been maintain properly in a safemanner so as not to endanger persons by falling material. noted: throughout excessive debris on working platforms of scaffolds,also noted
Feb 4, 2014 · Penalty $800
Resolve - Class - 2
Failure to maintain adequate housekeeping per section requirements.noted on all levels excessive amounts o fdebris, i.e. broken block, pipe,sheetrock,etc. also 3rd floor ponding water approx 1"inch deep.rmdy:ma
Feb 4, 2014
Resolve - Class - 1
Sec. 3303.9 failure to provide/maintain required egress during alteration work. noted: on all levels excessive material/debris scattered throughout exit corridors. remedy: remove materials from corridors/passag
Feb 4, 2014 · Penalty $1,600
Resolve - Class - 1
Failure to provide unobstructed exit passageway on 5th floor stairwella & b obstructed w/scaffolds & other equipment. workers throughout floor appl #402886506. remedy: stop all work on 5 floor only remove obstr
Feb 4, 2014 · Penalty $1,200
Resolve - Class - 2
Defective doors. at transportable units, the interior doors are rackedto frame w/bent hinges and not closing properly. remedy: repair doors.
Mar 20, 2012
Resolve - Class - 2
Defective exterior wood. at transportable units t3 & t4, defective ramp & railings - rotten and loose sections - t1 entry flring spongy & rotting. remedy: repair/replace.
Mar 20, 2012
Resolve - Class - 2
Occupancy contrary. at rear schoolyard, 6 cars parked between main school and mini bldg via legal curb cut for trash dumpsters along 43rd street w/students in schoolyard. remedy: remove cars.
Mar 20, 2012
Resolve - Class - 2
Defective flring. at cafeteria in front of room 109, cracked and looseasphalt tile w/rotted sub flring. flr is spongy creating a trip condition. remedy: repair flring, replace flr tile.
Mar 20, 2012
Resolve - Class - 2
Stairway storage. at exit stairwells left and right of stage, storage of combustible boxes and school supplies, cabinet and copy machine. remedy: remove all items.
Mar 20, 2012
Resolve - Class - 2
Doors not self closing. at 2nd flr, smoke doors left & right of auditorium have broken and missing door closers. remedy: provide door closers.
Mar 20, 2012
Resolve - Class - 3
Reissue #34893323r. defective concrete wall. at cellar electric meter room, cracked croncrete wall flr to ceiling. remedy: repair concrete wall.
Mar 20, 2012
Resolve - Class - 2
Reissue #34901875m. defective concrete. at cellar level leading to heat chamber, spalling concrete ceiling w/exposed rebars. remedy: repair concrete ceiling.
Mar 20, 2012
Resolve - Class - 2
Reissue #34901876y cracked brick masonry. at roof fan room, several vertical cracks, interior brick masonry. remedy: repair brick masonry.
Mar 20, 2012
Resolve - Class - 2
Interior wall is vertically cracked in various places in the fan room (east side) at the roof level. remedy: repair/replace vertical cracks.
Feb 10, 2011
Resolve