33-07 35 Avenue
Queens, NY 11106BBL 4-00610-0001Map
Owner of record: NYC Department Of Education
33-07 35 Avenue is a school building built in 1950 in Queens, 11106. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.
- HPD violations
- 0
- DOB violations
- 30
- ECB violations
- 74
- HPD complaints
- 3
What to know
No open immediately-hazardous violations among recent records.
HPD has not cited this building.
No balance due on recent ECB violations.
Rent stabilization
No rent-stabilized units in 2018–2024 tax bills
Violations
Most recent first. Showing up to 50 per agency.
HPD housing violations · 0
No HPD violations on record
DOB building violations · 30
- Failure to submit eer none
Failure to submit an eer per ad. code sec. 28-308.4 in 2020
Jun 20, 2021
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Mar 13, 2020
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 26, 2019
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst
Jan 26, 2018
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst
Jan 3, 2017
Dob violation - dismissed - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst
Nov 14, 2016
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Feb 24, 2015
Dob violation - resolved - Elevator affirmation of correction elevatorrequired
Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst
May 30, 2014
Dob violation - dismissed - Elevator elevatorrequired
Nyc department of education
Jan 29, 2014
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jan 23, 2013
Dob violation - resolved
Show 20 more ↓
- Elevator annual inspection / test elevatorrequired
Violation issued to elevator-failure to file category 1 2010 inspection/test
Dec 13, 2011
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Aug 18, 2010
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Dec 30, 2009
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 4, 2008
Dob violation - active - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 1, 2008
Dob violation - resolved - Elevator elevatorrequired
E-elevator elevatorrequired
Jun 3, 2005
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Nov 19, 2004
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Sep 1, 2004
Dob violation - resolved - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Apr 21, 2004
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Mar 21, 2003
Dob violation - dismissed - Elevator elevatorrequired
E-elevator elevatorrequired
Apr 15, 2002
Dob violation - resolved - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Elevator elevatoroptional
Ll1081-local law 10/81 - elevator elevatoroptional
Feb 19, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed
ECB violations · 74
- Class - 2
Reissue#35693187l date of issue:03.10.2025 failure to maintain building in code-compliant manner.at the time of inspection observed and noted at exposures 2 and 4.at spalling and missing concrete above windows
Feb 5, 2026 · Penalty $3,125
Active - Class - 2
Reissue#35693186j date of issue:03.10.2025 one exit door exit-no-3 at first floor kitchen area exit-3 has missing push bar exit door is not open by push bar.exit-3 is exit door and exit sign is there,in that pl
Feb 5, 2026 · Penalty $1,562
Active - Class - 2
Reissue#35693185l date of issue:03.10.2025 failure to maintain building in code-compliant manner.illumination for exists,exit discharges andpublic corridors per bc 1006.1;27-381.at the time of inspection observ
Feb 5, 2026 · Penalty $3,125
Active - Class - 2
Reissue#35693184x date of issue:03.10.25 failure to maintain building in code-compliant manner.noted at water penetration at hatches and supply room in cellar area.rem:repair or/and replace.
Feb 5, 2026 · Penalty $3,125
Active - Class - 2
Reissue#35721006z date of issue:7.23.25 failure to maintain building in code compliant manner.at the back side near and rear wall one place no firestopping at inside electrical room needs to be firestopped in m
Feb 5, 2026 · Penalty $3,125
Resolve - Class - 2
Failure to maintain building in code-compliant manner. noted at 4 floor parapet above windows at exposures 2 and 4 spalling and missing concrete. remedy: repair and/or replace.
Mar 10, 2025 · Penalty $1,250
Active - Class - 2
Reissue #35678686k. failure to maintain building in code-compliant manner. noted at water penetration at hatches and supply room in cellar. remedy: repair and/or replace.
Mar 10, 2025 · Penalty $3,125
Active - Class - 2
Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted at 3 floor box #30, 31, stair f, gym, 2 fl. #27, 29, and 1fl. #11
Mar 10, 2025 · Penalty $1,250
Active - Class - 2
Exit door not self-closing. noted at 1 floor exits 3(kitchen), 5, 8 and 9 doors are not closing properly. remedy: repair/replace doors.
Mar 10, 2025 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner. water leak coming from roof level, leak ave. in rooms 453, 454, 433, and 431. remedy:repair and/or replace.
Feb 23, 2024 · Penalty $625
Resolve
Show 40 more ↓
- Class - 2
Failure to maintain building in code-compliant manner. cellar level concrete cracking and deterioration letting water into area hatches to land supplies from outside. remedy: repair and/or replace.
Feb 23, 2024 · Penalty $625
Active - Class - 2
Reissue#35548447h.noted at 3rd floor stairwell g outside of the gymnaisum,em by stair f,2nd floor em#27 by stair e,the emergency lights are inoperative.remedy:repair and/or replace.
Mar 9, 2022 · Penalty $1,562
Resolve - Class - 2
Reissue#35548448j.noted at exp2 corner wall near 35 avenue at roof level has spalling and missing masonry.remedy:repair and/or place.
Mar 9, 2022 · Penalty $1,562
Resolve - Class - 2
Reissue#35548444m.noted at 3rd floor stair a by the elevator bank,cafeteria entrance smoke by exit 4,exterior door at exit 5,auditorium leftstage and left rear,the exit doors are not self-closing properly.remed
Mar 9, 2022 · Penalty $1,562
Resolve - Class - 2
Reissue#35548445y.noted at roof level adjacent to chimney above exit 6has loose/hanging metal flashing.remedy:repair and/or replace.
Mar 9, 2022 · Penalty $1,562
Resolve - Class - 2
Failure to maintain bldg in codecompliant manner:illumination for exits,exit discharges&public corridors per bc1006.1;27-381.noted:@3fl stairf by306&auditorium left rear emrgy lights inoperative.repair &/or rep
Mar 10, 2021 · Penalty $625
Resolve - Class - 2
Exit door not selfclosing.noted:@exterior exit door9 by 116
@auditorium left rear;exit doors arent working properly.repair/replace door.
Mar 10, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in codecompliant manner.noted:@roof level adjacent to chimney:theres a/c condenser installed on roof w/o dammage.repair &/or replace.
Mar 10, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in codecompliant manner:use of prohibited door &/or hardware per bc1008.1.8;27-371j noted;24fl stair&by453,rms453,452,451,449,1fl smoke@cafeteria main entrance&rear exit,1fl smoke by st
Mar 10, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner. noted: at the roof level adjacent to the chimney outside exit 6; there is loose/hanging metal flashing. remedy: repair and/or replace
Mar 10, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in codecompliant manner.noted:@exp2 corner wall near 35thave@roof level;has missing&spalling masonry.repair &/or replace.
Mar 10, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner illumination for exits discharges and publci corridors per bc 1006.1;27-381.at first floor near exit 1 (in side ) 1 place 3 lights are not operational when
Feb 11, 2020 · Penalty $625
Resolve - Class - 2
Exit door not self closing proeprly at 4th floor at staircase "g" one door not sel fclosing properly at 3rd floro near staircase "g: one door "entrance to gymnasium" one door not slef closing properly at 3rd fl
Feb 11, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner. illumination for exit, exit discharges and public corridors per bc 1006.1; 27-381. at3rd floor in front room no. 340 and at 2nd floor in front of room 240
Feb 13, 2019
Resolve - Class - 2
Reissue: 35311589h date of issue 01.01.2018. occupancy contrary to that allowed by the cofo building dept records, one car parking along rear yard obstructing exit flow of multiple exits. rmdy: remove car.
Feb 13, 2019
Resolve - Class - 2
Exit door not self closing at 9th floor corridor exit door near room no. 402 one door not self closing properly at the time of inspection when tested. rmdy: repair/replace door.
Feb 13, 2019
Resolve - Class - 2
Re-issue #35235381r/occupancy contrary to that allowed by the c of o or building dept records.noted:one car parked along rear yard obstructing exit flow of multiple exits.rem:remove car.
Feb 1, 2018
Resolve - Class - 2
Reissue #35195320j failure to maintain building in code compliant manner. noted: at cellar leel, constant drip of waste water from the bath room above. waste water drips at boiler room. rmdy: comply w/nov.
Mar 22, 2017
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner. noted: at cafeteriaone exit door at exit 4 not closing. rmdy: repair/replace door.
Mar 22, 2017
Resolve - Class - 2
Reissue #35084630n occupancy contrary to that allowed by the cofo orbuilding dept. noted: two cars parked along rear yard obstructing exitflow of multiple exits. rmdy: remove cars
Mar 22, 2017
Resolve - Class - 2
Failure to maintain bldg. noted: constant drip of waste water onto cellar. boiler room floor w/pooled water on floor. liquid has a toxic pungent odor. rmdy: comply w/notice of violation.
Oct 13, 2016
Resolve - Class - 2
Reissue 3504631p fail to maintain. no fire stopping at pipe pentration.locations:214,316.rem:maintian as per code
Jan 29, 2014
Resolve - Class - 2
Reissue 35023823m. missing fire stopping at rooms 214,316 pipe penetrations.rem: seal penetrations.
Jan 16, 2014
Resolve - Class - 2
Reissue 35023833y.occupancy contrary to c of o noted 2 cars mercedes suv toyota prius parked along rear yard obstructing exit flow of multiple exits.rem: remove cars.
Jan 16, 2014
Resolve - Class - 2
Missing fire stopping. at rooms 316 and 214, apprx 1'x1' penetration with conduit to concealed space above corridor. rmdy: provide/maintain fire stopping.
Jul 15, 2013
Resolve - Class - 2
Occupancy contrary to c/o 2 cars parked in rear areaway via handicap cut along 33rd street. cofo #401156404f indicates type and number of open spaces - none. rmdy: discontinue illegal use or amend c/o if feas
Jul 15, 2013
Resolve - Class - 2
Missing fire stop. at slop sink room 316 no fire stop to concealed space with conduit penetration. rem:provide fire stopping.
Mar 13, 2012
Resolve - Class - 2
Defective door. at exit #10, one of 2 doors jams when closed requiringexcessive force to open. rem:repair door.
Mar 13, 2012
Resolve - Class - 1
Defectivve stone facade. at 4th flr along 34th street & at corner 35thave & 34th street spalling decorative stone facade with pieces dislodging in several areas. rem:make safe immediately repair facade stores.
Mar 13, 2012
Resolve - Class - 2
Occupancy contrary. at side yard along 33rd street,3 cars parked in yard via 5' handicap curb cut adjacent to 34-37 33rd street. rem:discontinue illegal use or obtain approvals & curb cut permit if feasible.
Mar 13, 2012
Resolve - Class - 2
Reissue 34908361r missing fire stop. at cellar electric room open wiremesh over door. 401156404 at boiler room open fire wall above door with conduit penetration. rem:provide fire stopping.
Mar 13, 2012
Resolve - Class - 2
Reissue #34908358x water penetration. the roof & exterior wall has become porous allowing water to penetrate into room 231,449,454 w/pail inplace in room 454. rem:waterproof exterior.
Mar 13, 2012
Resolve - Class - 2
Reissue #34908357y partial corridor obstruction. desks & chairs line both sides of the corridor. throughout flrs 1,2,3,4. rem:remove all items maintain corridor width clear.
Mar 13, 2012
Resolve - Class - 2
Missing fire stop at cellar lvl electrical room has open wire grill above double steel doors electrical room has upgraded electrical service at cellar lvl boiler room door missing fire stop above w/ various pip
May 5, 2011
Resolve - Class - 3
Fire alarm box at rear of gym the fire alarm box has been pulled out of the wall and left hanging rem: secure fire alarm pull box
May 5, 2011
Resolve - Class - 3
Defective plaster surface at 4th floor room 401 near window the plaster surface is spalling and crumbling rem: repair plaster surface
May 5, 2011
Resolve - Class - 2
Partial fire corridor obstruction partial corridor obstructions at 1 2 3 & 4 floors w/ tables chairs and boxes of school supplies rem: remove all item maintain corridor width clear
May 5, 2011
Resolve - Class - 2
Defective doors the fire proof self closing exit doors are racked to frame and jammed shut required extreme force to open at street exit door #1 main entrance #10&12 auditorium exit to street on left and right
May 5, 2011
Resolve - Class - 2
Water penetration the roof and exterior walls have become porous allowing rain water to penetrate into classroom 449 & 454 and 231 w/ pail of rain water present in room 454 at time of insp rem: water proof area
May 5, 2011
Resolve - Class - 2
Re 34692964x. corridor smoke doors missing 4th fl next to rm 405. remedy: install doors.
Feb 12, 2009
Resolve
Complaints
- Heat/hot water
Entire building
Jan 26, 2016 · Apt BLDG
Close - Nonconst
Vermin
Jul 17, 2009 · Apt 5
Close - Plumbing
Toilet
Jul 17, 2009 · Apt 5
Close
Sales history
No recorded sales in our data
Building details
- Building type
- School building (W1)
- Year built
- 1950
- Floors
- 4
- Residential units
- —
- Building area
- 105,830 ft²
- Lot area
- 37,054 ft²
- Zoning
- R5
- Community board
- 401
- Council district
- 26
- Block / lot
- 610 / 1
- Assessed value
- $10,075,500
- Landmark / historic district
- No
Questions about 33-07 35 Avenue
Who owns 33-07 35 Avenue?
The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.
Does 33-07 35 Avenue have violations?
NYC HPD has no housing violations on record for this property.
Is 33-07 35 Avenue rent stabilized?
No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.
When was 33-07 35 Avenue built?
City records list 1950 as the year it was built.
Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.