roofy

33-07 35 Avenue

Queens, NY 11106BBL 4-00610-0001Map

Owner of record: NYC Department Of Education

33-07 35 Avenue is a school building built in 1950 in Queens, 11106. The owner of record is NYC Department Of Education. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
30
ECB violations
74
HPD complaints
3

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 30

  • Failure to submit eer none

    Failure to submit an eer per ad. code sec. 28-308.4 in 2020

    Jun 20, 2021

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 13, 2020

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 26, 2019

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Feb 24, 2015

    Dob violation - resolved
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    Nyc department of education

    Jan 29, 2014

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 23, 2013

    Dob violation - resolved
Show 20 more ↓
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2010 inspection/test

    Dec 13, 2011

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 18, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Dec 30, 2009

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 4, 2008

    Dob violation - active
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 1, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 3, 2005

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Nov 19, 2004

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Sep 1, 2004

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 21, 2004

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 21, 2003

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 15, 2002

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Mar 26, 2002

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Feb 19, 2002

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed

ECB violations · 74

  • Class - 2

    Reissue#35693187l date of issue:03.10.2025 failure to maintain building in code-compliant manner.at the time of inspection observed and noted at exposures 2 and 4.at spalling and missing concrete above windows

    Feb 5, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35693186j date of issue:03.10.2025 one exit door exit-no-3 at first floor kitchen area exit-3 has missing push bar exit door is not open by push bar.exit-3 is exit door and exit sign is there,in that pl

    Feb 5, 2026 · Penalty $1,562

    Active
  • Class - 2

    Reissue#35693185l date of issue:03.10.2025 failure to maintain building in code-compliant manner.illumination for exists,exit discharges andpublic corridors per bc 1006.1;27-381.at the time of inspection observ

    Feb 5, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35693184x date of issue:03.10.25 failure to maintain building in code-compliant manner.noted at water penetration at hatches and supply room in cellar area.rem:repair or/and replace.

    Feb 5, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue#35721006z date of issue:7.23.25 failure to maintain building in code compliant manner.at the back side near and rear wall one place no firestopping at inside electrical room needs to be firestopped in m

    Feb 5, 2026 · Penalty $3,125

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted at 4 floor parapet above windows at exposures 2 and 4 spalling and missing concrete. remedy: repair and/or replace.

    Mar 10, 2025 · Penalty $1,250

    Active
  • Class - 2

    Reissue #35678686k. failure to maintain building in code-compliant manner. noted at water penetration at hatches and supply room in cellar. remedy: repair and/or replace.

    Mar 10, 2025 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted at 3 floor box #30, 31, stair f, gym, 2 fl. #27, 29, and 1fl. #11

    Mar 10, 2025 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self-closing. noted at 1 floor exits 3(kitchen), 5, 8 and 9 doors are not closing properly. remedy: repair/replace doors.

    Mar 10, 2025 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. water leak coming from roof level, leak ave. in rooms 453, 454, 433, and 431. remedy:repair and/or replace.

    Feb 23, 2024 · Penalty $625

    Resolve
Show 40 more ↓
  • Class - 2

    Failure to maintain building in code-compliant manner. cellar level concrete cracking and deterioration letting water into area hatches to land supplies from outside. remedy: repair and/or replace.

    Feb 23, 2024 · Penalty $625

    Active
  • Class - 2

    Reissue#35548447h.noted at 3rd floor stairwell g outside of the gymnaisum,em by stair f,2nd floor em#27 by stair e,the emergency lights are inoperative.remedy:repair and/or replace.

    Mar 9, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35548448j.noted at exp2 corner wall near 35 avenue at roof level has spalling and missing masonry.remedy:repair and/or place.

    Mar 9, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35548444m.noted at 3rd floor stair a by the elevator bank,cafeteria entrance smoke by exit 4,exterior door at exit 5,auditorium leftstage and left rear,the exit doors are not self-closing properly.remed

    Mar 9, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35548445y.noted at roof level adjacent to chimney above exit 6has loose/hanging metal flashing.remedy:repair and/or replace.

    Mar 9, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner:illumination for exits,exit discharges&public corridors per bc1006.1;27-381.noted:@3fl stairf by306&auditorium left rear emrgy lights inoperative.repair &/or rep

    Mar 10, 2021 · Penalty $625

    Resolve
  • Class - 2

    Exit door not selfclosing.noted:@exterior exit door9 by 116&#10@auditorium left rear;exit doors arent working properly.repair/replace door.

    Mar 10, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner.noted:@roof level adjacent to chimney:theres a/c condenser installed on roof w/o dammage.repair &/or replace.

    Mar 10, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner:use of prohibited door &/or hardware per bc1008.1.8;27-371j noted;24fl stair&by453,rms453,452,451,449,1fl smoke@cafeteria main entrance&rear exit,1fl smoke by st

    Mar 10, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: at the roof level adjacent to the chimney outside exit 6; there is loose/hanging metal flashing. remedy: repair and/or replace

    Mar 10, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner.noted:@exp2 corner wall near 35thave@roof level;has missing&spalling masonry.repair &/or replace.

    Mar 10, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner illumination for exits discharges and publci corridors per bc 1006.1;27-381.at first floor near exit 1 (in side ) 1 place 3 lights are not operational when

    Feb 11, 2020 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self closing proeprly at 4th floor at staircase "g" one door not sel fclosing properly at 3rd floro near staircase "g: one door "entrance to gymnasium" one door not slef closing properly at 3rd fl

    Feb 11, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner. illumination for exit, exit discharges and public corridors per bc 1006.1; 27-381. at3rd floor in front room no. 340 and at 2nd floor in front of room 240

    Feb 13, 2019

    Resolve
  • Class - 2

    Reissue: 35311589h date of issue 01.01.2018. occupancy contrary to that allowed by the cofo building dept records, one car parking along rear yard obstructing exit flow of multiple exits. rmdy: remove car.

    Feb 13, 2019

    Resolve
  • Class - 2

    Exit door not self closing at 9th floor corridor exit door near room no. 402 one door not self closing properly at the time of inspection when tested. rmdy: repair/replace door.

    Feb 13, 2019

    Resolve
  • Class - 2

    Re-issue #35235381r/occupancy contrary to that allowed by the c of o or building dept records.noted:one car parked along rear yard obstructing exit flow of multiple exits.rem:remove car.

    Feb 1, 2018

    Resolve
  • Class - 2

    Reissue #35195320j failure to maintain building in code compliant manner. noted: at cellar leel, constant drip of waste water from the bath room above. waste water drips at boiler room. rmdy: comply w/nov.

    Mar 22, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner. noted: at cafeteriaone exit door at exit 4 not closing. rmdy: repair/replace door.

    Mar 22, 2017

    Resolve
  • Class - 2

    Reissue #35084630n occupancy contrary to that allowed by the cofo orbuilding dept. noted: two cars parked along rear yard obstructing exitflow of multiple exits. rmdy: remove cars

    Mar 22, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg. noted: constant drip of waste water onto cellar. boiler room floor w/pooled water on floor. liquid has a toxic pungent odor. rmdy: comply w/notice of violation.

    Oct 13, 2016

    Resolve
  • Class - 2

    Reissue 3504631p fail to maintain. no fire stopping at pipe pentration.locations:214,316.rem:maintian as per code

    Jan 29, 2014

    Resolve
  • Class - 2

    Reissue 35023823m. missing fire stopping at rooms 214,316 pipe penetrations.rem: seal penetrations.

    Jan 16, 2014

    Resolve
  • Class - 2

    Reissue 35023833y.occupancy contrary to c of o noted 2 cars mercedes suv toyota prius parked along rear yard obstructing exit flow of multiple exits.rem: remove cars.

    Jan 16, 2014

    Resolve
  • Class - 2

    Missing fire stopping. at rooms 316 and 214, apprx 1'x1' penetration with conduit to concealed space above corridor. rmdy: provide/maintain fire stopping.

    Jul 15, 2013

    Resolve
  • Class - 2

    Occupancy contrary to c/o 2 cars parked in rear areaway via handicap cut along 33rd street. cofo #401156404f indicates type and number of open spaces - none. rmdy: discontinue illegal use or amend c/o if feas

    Jul 15, 2013

    Resolve
  • Class - 2

    Missing fire stop. at slop sink room 316 no fire stop to concealed space with conduit penetration. rem:provide fire stopping.

    Mar 13, 2012

    Resolve
  • Class - 2

    Defective door. at exit #10, one of 2 doors jams when closed requiringexcessive force to open. rem:repair door.

    Mar 13, 2012

    Resolve
  • Class - 1

    Defectivve stone facade. at 4th flr along 34th street & at corner 35thave & 34th street spalling decorative stone facade with pieces dislodging in several areas. rem:make safe immediately repair facade stores.

    Mar 13, 2012

    Resolve
  • Class - 2

    Occupancy contrary. at side yard along 33rd street,3 cars parked in yard via 5' handicap curb cut adjacent to 34-37 33rd street. rem:discontinue illegal use or obtain approvals & curb cut permit if feasible.

    Mar 13, 2012

    Resolve
  • Class - 2

    Reissue 34908361r missing fire stop. at cellar electric room open wiremesh over door. 401156404 at boiler room open fire wall above door with conduit penetration. rem:provide fire stopping.

    Mar 13, 2012

    Resolve
  • Class - 2

    Reissue #34908358x water penetration. the roof & exterior wall has become porous allowing water to penetrate into room 231,449,454 w/pail inplace in room 454. rem:waterproof exterior.

    Mar 13, 2012

    Resolve
  • Class - 2

    Reissue #34908357y partial corridor obstruction. desks & chairs line both sides of the corridor. throughout flrs 1,2,3,4. rem:remove all items maintain corridor width clear.

    Mar 13, 2012

    Resolve
  • Class - 2

    Missing fire stop at cellar lvl electrical room has open wire grill above double steel doors electrical room has upgraded electrical service at cellar lvl boiler room door missing fire stop above w/ various pip

    May 5, 2011

    Resolve
  • Class - 3

    Fire alarm box at rear of gym the fire alarm box has been pulled out of the wall and left hanging rem: secure fire alarm pull box

    May 5, 2011

    Resolve
  • Class - 3

    Defective plaster surface at 4th floor room 401 near window the plaster surface is spalling and crumbling rem: repair plaster surface

    May 5, 2011

    Resolve
  • Class - 2

    Partial fire corridor obstruction partial corridor obstructions at 1 2 3 & 4 floors w/ tables chairs and boxes of school supplies rem: remove all item maintain corridor width clear

    May 5, 2011

    Resolve
  • Class - 2

    Defective doors the fire proof self closing exit doors are racked to frame and jammed shut required extreme force to open at street exit door #1 main entrance #10&12 auditorium exit to street on left and right

    May 5, 2011

    Resolve
  • Class - 2

    Water penetration the roof and exterior walls have become porous allowing rain water to penetrate into classroom 449 & 454 and 231 w/ pail of rain water present in room 454 at time of insp rem: water proof area

    May 5, 2011

    Resolve
  • Class - 2

    Re 34692964x. corridor smoke doors missing 4th fl next to rm 405. remedy: install doors.

    Feb 12, 2009

    Resolve

Complaints

  • Heat/hot water

    Entire building

    Jan 26, 2016 · Apt BLDG

    Close
  • Nonconst

    Vermin

    Jul 17, 2009 · Apt 5

    Close
  • Plumbing

    Toilet

    Jul 17, 2009 · Apt 5

    Close

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1950
Floors
4
Residential units
—
Building area
105,830 ft²
Lot area
37,054 ft²
Zoning
R5
Community board
401
Council district
26
Block / lot
610 / 1
Assessed value
$10,075,500
Landmark / historic district
No

Questions about 33-07 35 Avenue

Who owns 33-07 35 Avenue?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Education.

Does 33-07 35 Avenue have violations?

NYC HPD has no housing violations on record for this property.

Is 33-07 35 Avenue rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 33-07 35 Avenue built?

City records list 1950 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.