Violations at 37-25 13 Street

Queens, NY 11101 · BBL 4-00363-0001 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

16 DOB violations, newest first.

  • Immediate emergency anythingoptional

    Remedy: repair and/or replace 40lf of construction fence at expo1 (fro nt of bldg) in accordance with nyc bldg code requirements

    Dec 23, 2024

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator - failure to file category 1 2017 inspection/test

    Apr 5, 2019

    Dob violation - dismissed
  • Construction other optional

    C-construction other optional

    May 23, 2018

    Dob violation - active
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2013 inspection/test

    Oct 31, 2014

    Dob violation - dismissed
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2012 inspection/test

    Mar 31, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 6, 2014

    Dob violation - resolved
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2011 inspection report

    Mar 1, 2013

    Dob violation - dismissed
  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2011 inspection report

    Mar 1, 2013

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 19, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 20, 2011

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Feb 27, 2009

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 21, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed

ECB violations

The newest 50 of 102 ECB violations. The city keeps the complete history.

  • Class - 2

    Failure to maintain building in code-compliant manner. at the time of inspection noted: fpsc smoke doors #9, 11, and 2 not closing; classroom; #206, 208; 209, 215, 216 doors not self closing. reissue ecb 356918

    Feb 5, 2026 · Penalty $3,125

    Active
  • Class - 2

    Exterior door not self-closing. at the time of inspection noted: exterior exit doors #9, #10 and main entry door(from 13 street) not self-closing. reissue #35691827l-class 2. remedy: repair and/or replace door.

    Feb 5, 2026 · Penalty $1,562

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. at the time of inspection noted approx 75% emergency lights not working

    Feb 5, 2026 · Penalty $3,125

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.illumination forexits,exit discharges and public corridors per bc 1006.1;27-381.noted throughout school approx.75% emergency lights not working when tested.

    Mar 10, 2025 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self-closing noted:exterior doors at exit#9 & 10 and stair b bulkhead roof access,not opening or closing properly.rem:repair/replace door.

    Mar 10, 2025 · Penalty $625

    Active
  • Class - 2

    Reissue #35663196x. failure to maintain building in code-compliant manner. noted interior fpsc smoke doors not closing at 3rd fl corridor byrm #318, 2nd fl rm #204 exit #, 6, 9, 11 on 1st fl and basement level

    Mar 10, 2025 · Penalty $3,125

    Active
  • Class - 2

    Observed construction fence erected under active permit #q08009628, has approximately 40 linear feet of fence blown over and resting on k-rails at exp.1 (front of building), comply with code; repair and/or repl

    Dec 21, 2024 · Penalty $5,000

    Active
  • Class - 2

    Reissue#35663195y failure to maintain building in code-compliant manner.oil of tank room at cellar level water coming into room.rem:repair and/or replace.

    Feb 12, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to provide power for emergency exit lighting emergency lighting not working when tested no power maybe the battery.units by staircase c & staircase a exit 2,staircase b,and the ones onstages.rem:provide

    Feb 12, 2024 · Penalty $1,250

    Active
  • Class - 2

    Reissue #35644389z exit door not self closing:smoke doors by exit #3, exit #6, #9, #11, basement b 17 & smoke doors by exit #2.remedy:comply with code

    Jan 24, 2023 · Penalty $1,562

    Active
  • Class - 2

    Reissue #35311498m failure to maintain bldg walls or appurtenances.oil tank room @ cellar leaking water in unused oil tank room.remedy:complywith code.

    Jan 24, 2023 · Penalty $3,125

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner illumination for exits exit discharges and public corridors per bc 1006.1; 27-381.noted:at 1st floor by 104 basement c-04 by exit 9 c-03 and exit sign by ki

    Mar 16, 2022 · Penalty $625

    Resolve
  • Class - 2

    Reissue #35548347k noted:at east side of exp #1 foundation wall porous and allowing waer into oil tank room.remedy:repair and/or replace.

    Mar 16, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissued #35548349y noted:at roof level fan room has running cracks missing masonry some areas bulging throughout facade.remedy:repair and/or replace.

    Mar 16, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissued #35548426z.noted:at smoke by exit 3 & exterior door smoke by exit 6 smoke by esit 9 smoke by exit 11 basement b17 and smoke by exit 2;exit doors not working properly.remedy:repair/replace door.

    Mar 16, 2022 · Penalty $1,562

    Active
  • Class - 2

    Exit door not selfclosing.noted:@smoke by 318,smoke by 222,smoke by 204,smoke by exit11,&exterior door,smoke by exit3&exterior door,&exterior door@exit6;exit doors arent working properly.repair &/or replace.

    Mar 5, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner.noted:@roof level,fanrm;exp1 left corner wall has loose bricks&missing mortar.also,right side by ladder&exp4 have running step cracks.repair &/or replace.

    Mar 5, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner.noted:rms318,205&132;doors arent working properly.repair &/or replace.

    Mar 5, 2021 · Penalty $625

    Resolve
  • Class - 2

    Reissue35467689x noted:@east side of exp1,foundation wall has become pourous&is allowing water into oil tank rm.repair &/or replace.

    Mar 5, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Exit door not self closing 1st floor staircase- one door right side 2nd floro staircase "b: one door 3rd floor at stair case 'a" 3rd fl coridoor eixt door (one) near rm no-318 3rd fl staircase "b: one door exit

    Feb 6, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner illumination for exit,exit discharges and public corridors per bc 1006.1:27-381 at first floor exit light nox no 1-06 ,box 1-03 light box no -1-09 one place

    Feb 6, 2020 · Penalty $625

    Resolve
  • Class - 2

    Reissue #35383906f date of issue :02-01-2019.miscellaneous violation sec 28-301.1 failure to provide vilation matural or mechanical to occupied space per m401.2 at basement in sprinkler room unsafe.comply with

    Feb 6, 2020 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue #35383907r date of issue:02-01-2019 failure to maintain building wall(s) or appurtenances at the east side exp #1 at foundation leaking water into oil tank roo approx 3" of water in floor maintain exter

    Feb 6, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue #35311498m date of issue 01.24.2018 failure to maintain building wall(s) or appurtenances at the east side epx #1 at foundation leaking water into oil tank room approx 3"of water in floor.maintain exter

    Feb 1, 2019

    Resolve
  • Class - 2

    28-301.1=reissue #35311499y date of issue 01.24.2018.miscellaneous violation sec 28-301.1 failure to provide ventilation natural or mechanical to ossupied space per m 401.2 at basement in sprinkler room unsaf s

    Feb 1, 2019

    Resolve
  • Class - 2

    Reissue# 35234661r. failure to maintain bldg in code compliant manner. note: @ 3rd flr bulkhead stairway c missing door check due to defective closure no arm. rem: repair &/or replace closure.

    Jan 24, 2018

    Resolve
  • Class - 2

    Sec. 28-301.1 failure to provide ventilation natural or mechanical to occupied space per mc 401.2. note: at basement in sprinkler room unsafe storage of gas equipment lawnnower snow blower,& gas vaccum,also woo

    Jan 24, 2018

    Resolve
  • Class - 2

    Failrue to maintain bldg walls or appurtenances. note at the east sideexp#1 at foundation leaking water into oil tank room approx 3" of water on floor. remedy: maintain exterior bldg wall.

    Jan 24, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. note: at roof level on upper roof leak leaking water in room 324 leak is around roof drain through ceiling also roof leaking at lower roof over room 217 near

    Jan 24, 2018

    Resolve
  • Class - 2

    Reissued 35216216j failure to maintain bldg in code compliant manner. note at 3rd fl bulkhead stairway'c'missing door check due to defective closer no arm. remedy: repair &/or replace.

    Jan 24, 2018

    Resolve
  • Class - 2

    Reissued#35234662z failure to maintain bldg walls & appurtenances: note at roof level acrossed from stairway'c'missing lower flashing approx3feet plus. remedy: repair &/or replace.

    Jan 24, 2018

    Resolve
  • Class - 2

    35064637x failure to maintain bldg in code compliant manner. note: water damage to ceiling at 3rd fl room 324. north-east corner of roof leaking causing damage to ceiling & wall above window in corner of room.

    Jan 24, 2018

    Resolve
  • Class - 2

    Reissue #35084637x.failure to maintain bldg in code compliant manner. noted: water damage to ceiling at room #217 and cafeteria area. rmdy: comply with code/repair or replace the ceiling

    Feb 24, 2017

    Resolve
  • Class - 2

    Reissue #.failure to maintain bldg walls or appurtenances. noted: roof stairway c missing lower flashing. rmdy: comply with code/installmetal flash.........................................................

    Feb 24, 2017

    Resolve
  • Class - 2

    5hissue #35216216j.failure to maintain bldg in code compliant manner. noted: at 3rd floor, bulkhead stairway "c", missing door check due to defective in the closer. rmdy: comply with code/repair the door

    Feb 24, 2017

    Resolve
  • Class - 2

    Reissue #35216216j.failure to maintain bldg in code compliant manner. noted: at 1st floor, stairway "c", 2nd floor, smoke door and stairway (a) and (b), the doors have defective in the top hinge and not close

    Feb 24, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner(interior). noted: 1st fl stairway'c'right side 2nd door hitting the floor. 2nd fl corridorsmoke doors both doors not closing. 2nd stairway'b'2nd door right side

    Nov 14, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner(interior). noted: 3rd fl bulkhead stairway'c'missing door check. remedy: comply w/the notice of violation.

    Nov 14, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner(exterior). noted: roof stairwell'c'is missing lower flashing. remedy: comply w/the notice of violation.

    Nov 14, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner(interior). noted: roof bulkhead stairway'b'w/water damage at lower wall adjacent to roof door. remedy: comply w/the notice of violation.

    Nov 14, 2016

    Resolve
  • Class - 2

    Failure to maintain exterior wall(s). noted: cracked decorative stone facade. at left window of 2nd floor along 37 avenue, 2 areas left of entry along 13 st. the decorative facade stones have cleared cracks.

    Jul 6, 2016

    Resolve
  • Class - 2

    Failure to maintain.note approx. 2'x 1 hole in ceilings of slop sink closets:locations rms 110a,212a,312a.rem:maintain as per code

    Jan 21, 2015

    Resolve
  • Class - 2

    Plaster damage room 217,306 along walls,ceiling.rem: repair walls/ceiling.

    Jan 17, 2014

    Resolve
  • Class - 2

    Reissue 35023861l. missing fire stopping at rooms 110a,212a,112a,312a,ceiling/wall pipe penetrations.rem: seal penetrations around pipe.

    Jan 17, 2014

    Resolve
  • Class - 3

    Reissue 35023862n. masonry steps on 37th ave shifting granite stones/steps.rem: repair steps.

    Jan 17, 2014

    Resolve
  • Class - 2

    Sec. 1006.1;27-542 defective emergency lighting. at 1st fl gym,5 broken emergency lights for p/a under #401889006 for 240 persons. remedy: replace defective lighting.

    Jul 22, 2013

    Resolve
  • Class - 2

    Defective plaster ceiling adjacent to room 110a - girls rest room sinkarea,broken 3 coat plaster ceiling w/approx 1'x1' hole. remedy: repair plaster ceiling.

    Jul 22, 2013

    Resolve
  • Class - 3

    Reissue #34944219k defective masonry steps. at main entry & 37 ave exit,the granite stone steps are missing mortar joints & are displaced/dislodged. remedy: reset stone masonry.

    Jul 22, 2013

    Resolve
  • Class - 2

    Reissue #34941222l missing fire stopping. at rooms 110a,112a,212a,312a,ceiling penetrations w/conduits missing fire stop. remedy: provide/maintain fire stopping.

    Jul 22, 2013

    Resolve
  • Class - 2

    Defective plaster surface at: 3rd floor room 306, spalling & crumbling plaster surface at ceiling with concealed intermitent leak. remedy: make all repairs.

    Feb 24, 2012

    Resolve