Violations at 36-25 Crescent Street

Queens, NY 11101 · BBL 4-00344-0001 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

28 DOB violations, newest first.

  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2017 inspection report

    Nov 8, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2017 cat 1 insp/tst tst

    Sep 6, 2019

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 6, 2015

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2013 inspection/test

    Oct 31, 2014

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2012 cat 1 insp/tst

    May 30, 2014

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 7, 2013

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 20, 2012

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Apr 20, 2011

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 16, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 9, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Oct 5, 2006

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Nov 19, 2004

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Aug 30, 2004

    Dob violation - resolved
  • Elevator elevatorrequired

    4p5345

    Aug 14, 2001

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 2001

    Dob violation - dismissed
  • Elevator elevatorrequired

    4p5345

    Jul 31, 2000

    Dob violation - resolved
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Mar 8, 1996

    Dob violation - dismissed
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Apr 17, 1995

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Apr 25, 1991

    Dob violation - dismissed
  • Elevator elevatoroptional

    1

    Jun 29, 1990

    Dob violation - dismissed

ECB violations

The newest 50 of 86 ECB violations. The city keeps the complete history.

  • Class - 2

    Failure to maintain building in code-compliant manner. noted: fire rated smoke doors not closing properly or missing door closure on classrooms 109, 309 and or exits 4 and 5 on first floor including door in sta

    Feb 4, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: emergency lights not in operation upon testing of box #s32, 1 bu

    Feb 4, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissue on ecb #35691774r. noted: upon inspection failure to maintain building in code-compliant manner on exposure 2 and 3 corner, has missing chunks of concrete at base of landing to railing past and some mis

    Feb 4, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissue on ecb 35691825h. noted: upon inspection exit 10 auditorium door not opening or closing properly with excessive force required to open and not self-close property exterior door. remedy: repair/replace d

    Feb 4, 2026 · Penalty $625

    Active
  • Class - 2

    Exit door not self-closing noted exterior door at exit#10 in auditorium not opening or closing properly.door requires excessive force to open & will not self close due to rubbing on frame/saddle.rem:repair/repl

    Mar 7, 2025 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.noted exp#2 exterior steps outside at exit#6 & 7 have missing chunk of concrete along the top landing & railing post.rem:repair and/or replace.

    Mar 7, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.rear yard playground cracks in retaining wall shared with park alas fence post broken in half oil cast iron ones.rem:repair and/or replace.

    Feb 8, 2024 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner:no firestopping per bc 712.3,27-345.hole made wall to gas matter room to run new pipe,hole left open no firestop done.rem:provide/maintain firestopping.

    Feb 8, 2024 · Penalty $1,250

    Resolve
  • Class - 2

    Bc3303.46&27-101.8 unsafe storage of combustible material&equipment.noted:observed atoi@cellar level,excessive storage of wood,chairs,desk,cardboard,electronics,cubbies,plastic etc by gas meter rm.maintain stor

    Feb 4, 2022 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner noted:observed duringinsp fireproof selfclosing door@ext2,3,4 not selfclosing due to missing/defective hardware.repair/replace

    Feb 4, 2022 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg codecompliant manner.no firestopping per bc712.3:27.345.noted observed in gas meter rm over door sec of block has been removed (aprx6"x1').compromising firestopping.reissued#35546131m p

    Feb 4, 2022 · Penalty $3,125

    Resolve
  • Class - 2

    Boiler over 8 feet high ,ladder & platform missing,exposed wires,2-low water cut offs on 1-tapping,need to be on seperate tappings,valve on oil suction line missing on top of oil tank b/4 anti syphon valve

    May 10, 2021 · Penalty $625

    Resolve
  • Class - 2

    Boiler is over 8 feet high ladder &platform missing,exposed wires,2-low water cut offs on 1 tapping ,need to be on seperate tapping,valve for oil suction line missing and be b/4 anti syphon valve

    May 10, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. noted: at the auditorium eight rear exit,by exit 11;emergency light#11 is inoper

    Feb 4, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner;no fire stopping per712.3;27-345. noted: at the cellar level electrical meter room;has holes from 3 conduits on the top of the wall adjacent to the entrance doo

    Feb 4, 2021 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: the corner wall by the water foundation near room 213;has cracks & broken/missing tiles w/sharp edges. remedy: repair &/or replace.

    Feb 4, 2021 · Penalty $625

    Resolve
  • Class - 2

    Reissue#35475908r. noted: at the 2nd fl stair a by 2007,exterior exitsdoors at 4 & 5,inside classroom 101,exit 7,inside classroom 103,exit 6exits 8&9,the exit door inside the elevator room & exit 2&3;the exit &

    Feb 4, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted: at room 202 (thru the gymnasium at exit/stair d)the bathroom inside that room & 206;the doors are not working properly. remedy: repair &/or replace.

    Feb 4, 2021 · Penalty $625

    Resolve
  • Class - 2

    Exit door not self-closing, 1st floor exit-9 right side one door & 2ndfl stair a exit-4 one door. not self-closing properly at the time of inspection. remedy: repair or replace door

    Feb 4, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner illumination forexits,exit discharges and public corridors per bc 1006.1;27-381. behind auditorium fixture 11,13 2 place each place exit signs existing emer

    Feb 4, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. note emergency light throughout entire school in hallways on all floor not worki

    Jan 23, 2018

    Resolve
  • Class - 2

    35234650l exit doors not self closing: note at 1st fl exit 2,3,4,5,8&9a;so at 3rd fl exit 2&3 doors not closing properly. at 1st fl exit doors 2,3,4,5,8&9 the door buck is rotten at the bottom & the middle jam

    Jan 23, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code complaint manner. lack of emergency lighting for exits, exit discharges and public corridors per bc 1006.1; 27-542. noted at 1st floor, auditorium area, inoperative emergenc

    Feb 23, 2017

    Resolve
  • Class - 2

    Failure to maintain building in codw complaint manner. noted water damage to ceiling with spalling due to water pemetration through roof at the following places. bulkhead stair case c,d, gym are, rm#402,316,310

    Feb 23, 2017

    Resolve
  • Class - 2

    Exit door not self closing. noted at 1st floor, exit 2,3 exit 9,10 & exit 4,5 & exit 8,9 & exit 2,3 at 3rd floor, the doors have defective in the top wing where the screw hole is loose and the door not close p

    Feb 23, 2017

    Resolve
  • Class - 2

    Reissue nov#35119203x. failure to maintain building in code-compliant manner. noted: noted at cellar level entire valves and flange bolts heavy corrosion, rosted through location: main domestic water and main

    Feb 23, 2017

    Resolve
  • Class - 2

    Failure to maintain building code compliant: no fire stopping per bc 712.3; 27-345. noted: at room 217,no fire stopping with apprx 1'x2' hole in mop sink room wall to concealed space above adjacent corridor.

    Jul 8, 2016

    Resolve
  • Class - 2

    Reissue #35084669k. failure to maintain bldg code compliant: use of prohibited hardware per bc 1008.18; 27-371(j) noted: locakable dead bolt and key cylinder lock installed on bulkhead roof doors a&c.code

    Jul 8, 2016

    Resolve
  • Class - 2

    Reissue #35119205j failure to maintain bldg code compliant. noted: defective exterior door frames has corroded and rusted through.some are loose with pcs missing, adjacent masonry crumbling.rmdy:comply w/code.

    Jul 8, 2016

    Resolve
  • Class - 2

    Failure to maintain.note: defective exit doors/frames (heary)corrosion /rusten through missing bottom connections.location 1st floor exits 2/3 9/10 4/5 8/9.rem:replace doors/frames

    Jan 21, 2015

    Resolve
  • Class - 2

    Reissue #35084671j note:hole in ceiling in front of 3rd floor elevatorrem:maintain as per code.

    Jan 21, 2015

    Resolve
  • Class - 2

    Failure to maintain.note entire valvest + failure bolts heavy corrosion/rusted through.locations:main domestic water, main sprinklers.rem:maintain + repair defective valves

    Jan 21, 2015

    Resolve
  • Class - 2

    Plaster damage at 3rd floor front of elevator hole approx 5"in(missingfire(probably)rem: repair ceiling.

    Jan 14, 2014

    Resolve
  • Class - 2

    Reissue 35023844j. operating roll down gates throughout building front of 110,316,216.rem: keep gate from being rolled down during school hours.

    Jan 14, 2014

    Resolve
  • Class - 2

    Reissue 35023845l. illegal hardware on roof access doors a & c with key cylinders.rem: remove key cylinder provide hook & eye.

    Jan 14, 2014

    Resolve
  • Class - 2

    Prohibited hardware. at bulkhead "c", dead bolt & key cylinder installed when code indicates hook & eye. rmdy: provide code compliant hardware.

    Jul 16, 2013

    Resolve
  • Class - 2

    Unsecured roll down gate. adjacent to room 110 & 316, roll down gate not secured in the open position allowing gate to be closed obstructing fire corridor. rmdy: secure roll down gate.

    Jul 16, 2013

    Resolve
  • Class - 2

    Missing fire stop at: mop sink room 306 & 206, no fire stop provided at floor & ceiling with conduit penetrations to concealed spaces. remedy: provide/maintain fire stopping.

    Feb 16, 2012

    Resolve
  • Class - 2

    Door not self closing at: cellar level marked b (basement) stairway c, the fire proof door is missing door closer. remedy: provide door closer so door properly self closes.

    Feb 16, 2012

    Resolve
  • Class - 3

    Loose light fixtures @ roof level, the exterior area lighting fixtureare not secured against rotations and swing freely in wind. remedy:secure all fixtures against rotation

    Mar 18, 2011

    Resolve
  • Class - 2

    Moisture penetration @ the 3rd fl gym. water penetration @ several areas throughout ceiling. remedy: determine cause, make repairs as required

    Mar 18, 2011

    Resolve
  • Class - 2

    Partial obstruction - auditorium exit e, w/ rolling cart, steel heliumgas bottle, chairs. - 3rd fl adjacent to room 321 w/ rolling cart and chairs - 2nd fl adjacent to room 221 w/ pop corn machine, 4' round ta

    Mar 18, 2011

    Resolve
  • Class - 2

    Defective doors. the fire proof self closing doors are racked and pulling away from frame at - 1st fl main entrance main door. - basement level stair way c. remedy: repair doors to open and self close prperly

    Mar 18, 2011

    Resolve
  • Class - 2

    Reissue # 34846306n defective plaster surfaces. at 1st fl room 110 ( nurse office ) spalling and loose ceiling plaster from prior moisture penetration. remedy: repair plaster surface

    Mar 18, 2011

    Resolve
  • Class - 2

    The ceramic wall tiles is bulging & out of plumb located at the 3rd fllevel next to the elevator. remedy: repair and/or replace wall ceramictiles.

    May 11, 2010

    Resolve
  • Class - 2

    The plaster is spalling from the ceiling located in room 110 (nurse office) on the 1st floor level. remedy: repair and/or replace plaster.

    May 11, 2010

    Resolve
  • Class - 2

    Reissue: 34761516z concrete/plaster is cracked located in room 317a on the 3rd floor level. remedy: repair and/or replace concrete/plaster.

    May 11, 2010

    Resolve
  • Class - 3

    Re 34692940l concrete ceiling is cracked rm 317a closet 3floor rem: repair concrete

    Feb 19, 2009

    Resolve
  • Class - 2

    Reissue: 34592163h failure to maintain building in code compliant manner. noted: elevator machine room is isolated from oil tank with sprrinkler head by concrete wall on the 1st flr level. remedy: obtain a vali

    Jul 16, 2008

    Resolve
  • Class - 2

    Reissue: 34526486r,34592164j (partial) failure to maintain building incode compliant manner. noted: closet at room 317a. the concrete ceiling is cracked adjacent to the beams on the 3rd flr level. remedy: repai

    Jul 16, 2008

    Resolve