DOB building violations

6 DOB violations, newest first.

  • Low pressure boiler boiler required

    Violation issued for failure to file annual boiler 2010 inspection report

    Sep 28, 2012

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 3, 2008

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 13, 2004

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed

ECB violations

The newest 50 of 61 ECB violations. The city keeps the complete history.

  • Class - 2

    Exit door not self-closing properly at the time of inspection. noted and observed at 1st floor auditorium in main entrance one exit door notself-closing properly, 1st floor exit-5(inside) one exit door, at 1st

    Jun 6, 2025 · Penalty $625

    Resolve
  • Class - 2

    Reissue #35682933k date of issue: 07-19-2024. failure to maintain building in code-compliant manner. at the time of inspection noted and observed that at cellar level there are signs of water coming from underg

    Jun 6, 2025 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue #35682934m date of issue: 07-19-2024. failure to maintain building in code-compliant manner. illumination for exits, exit dischagresand public corridors per bc 1006.1; 27-381. at the time of inspection

    Jun 6, 2025 · Penalty $3,125

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: in the gymnasium there is two emergency lights that was not oper

    Jul 19, 2024 · Penalty $625

    Resolve
  • Class - 2

    Re-issue #35643451x. failure to maintain building in code-compliant manner. noted: observed at cellar level, there are signs of water comingfrom underground at various locations throughout the cellar. remedy: r

    Jul 19, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Re-issue #35643452h. occupancy contrary to that allowed by certificateof occupancy per building dept. records. noted: on the fourth floor room 401 has been converted into a classroom. remedy: discontinue illega

    Jul 19, 2024 · Penalty $3,125

    Resolve
  • Class - 2

    Failure to maintain building & all parts thereof in a code-compliant manner: illegal off-street parking maintained without dob approval contrary to zr 25-621, bc 3202.2.2.4, and/or dot specifications, creating

    Jan 27, 2023 · Penalty $625

    Resolve
  • Class - 1

    Failure to notify dept of accident/incident that resulted in fatality or injury.note:one worker fell five feet off plank suffered twisted ankle taken to hospital.as per check of dept records permit holder faile

    Sep 8, 2022

    Resolve
  • Class - 1

    Observed 2 approximately 8ft deep excavations at exp 4 with no guardrails in place as required per bc3304.4.4. this is a hazard for workers and visitors as someone may fall into excavation and get killed or inj

    Aug 2, 2022 · Penalty $5,000

    Resolve
  • Class - 1

    Observed two approximately 8ft deep excavations at exp4 with less than 45degree angle (up to 0) in multiple locations contrary to approved plans specifying 1:1 (45degree) angle for soil type b as per soe101.00.

    Aug 2, 2022 · Penalty $2,500

    Resolve
  • Class - 2

    Reported to incident - worker stepped on elevated unsecured 2inx10in plank and fell twisting ankle later taken to a hospital. observed construction site at foundation with planks resting on formwork. as per bc3

    Aug 2, 2022 · Penalty $5,000

    Resolve
  • Class - 2

    Re-issued #35561182h.occupancy constrary to that allowed by the certificate of occupancy or bldg dept records.at the time of inspection observed,at 4th fl rm#401 has converted & occupied as classroom.remedy:dis

    May 19, 2022 · Penalty $3,125

    Resolve
  • Class - 2

    Re-issued #35561181x.failure to maintain bldg in code compliant mannernoted:at cellar level water leak from underground in various locationsincluding gas meter room.remedy:repair &/or replace.

    May 19, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue:35445350p.occupancy contrary to that allowed by the cofo on bldg dept records.noted:4th floor 401 converted to classroom.remedy:discontinue illegal use.

    May 17, 2021 · Penalty $3,125

    Resolve
  • Class - 2

    Reissue:35495249k.failure to maitnain buildignn in code compliant manner.noted:water seeds throughout the concrete @ cellar level.remedy:comply with code.

    May 17, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Sec. 28-301.1 unlawful display of artwork in corridors greater than 20% for fdny 2008 code fc 803.3.2. noted: artwork displayed in corridors& decoration hanging off the ceiling throughout the bldg is greater th

    May 5, 2020 · Penalty $1,250

    Resolve
  • Class - 2

    Occupancy contrary to that allowed by the c of o or bldg dept records.noted: at 4th fl room 401 converted into classroom w/omly one door to enter. remedy: discontinue illegal use or amend c of o.

    May 5, 2020 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.noted:at cellar,water seeps through the concrete pad from under ground.remedy:make necessary repairs.

    May 5, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: illumination for exits,exit discharges & publuc corridors per bc 1006.1;27-381. noted: at auditorium 3 emergency exit lighting observed inperative when tested.

    May 5, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. main electrical room cracking in bricks water coming thru-wall. remedy: repair &/or replace.

    Mar 13, 2018

    Resolve
  • Class - 2

    Reissue#35235684y failure to maintain bldg walls or appurtenances. at roof level parapet walls have large cracks in them & loose caping stone. remedy: maintain exterior bldg wall.

    Mar 13, 2018

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner:illumination forexits,exit discharges and public corridors per bc1006.1;27-381.noted:emergency light packs on 3rd flr-near room 313,stair "a"at gyms exit 8

    Apr 13, 2017

    Resolve
  • Class - 2

    Re-issue #35207885m failrue to maintain bilding wall(s)or appurtances.noted:at roof-parapet walls on main roof and lower roof over the gym, have loose coping stones, cracked bricks with missing mortar at brick

    Apr 13, 2017

    Resolve
  • Class - 2

    Failure to maintain building wall(s) or appurtenances. noted: parapet walls about gym. coping stone & corner of parapet wall just below loose caping stone bricks are cracked & allows for water penetration on rm

    Sep 21, 2016

    Resolve
  • Class - 2

    Failure to maintain bldg wall(s) and or appurtenances: parapet walls above gym. coping stone and corner of parapet wall just below loose caping stone bricks are cracked and allows for water penetration on ro

    Apr 28, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg wall(s) and/or appurtenances: facade water penetration. water penetrating from facade into gym ceiling by windowsroom 4208. rmdy: comply w/nov.

    Apr 28, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner: provide required corridor width per bc 1016.2; 27-369. at main entrance, security desk blocking exit stairway. rmdy: comply with nov.

    Apr 28, 2015

    Resolve
  • Class - 2

    Failure to maintain bldg in code-compliant manner: reissue ecb # 35018998x: racked doors. at stairway a,b,c,d on 1st flr; stairway b second flr; stairway d on 4th floor and door for bulkhead of staircase

    Apr 28, 2015

    Resolve
  • Class - 2

    Failure to maintain. note: vertical cracks in bricks locations: 4th floor corner in court yard opposite transportables & above lintel at auditorium window on brighton 7 street. remedy: maintain building wall.

    May 22, 2014

    Resolve
  • Class - 2

    Failure to maintain. note: defective doors/frames at exits: locations: exit 5 from cafeteria (2), exit b1 from cafeteria (1), exit b2 2nd floor (1), auditorium -left of stage front exit. remedy: repair/replace

    May 22, 2014

    Resolve
  • Class - 1

    Electrical work w/o permit. electrical wiring of branch circuit to dining room receptacle outlet for salad bar refrigeration unit. at 4:05 pm observed that said wiring had been installed prior to obtaining

    Oct 4, 2013

    Resolve
  • Class - 3

    Defective wood railing. at transportable unit t2, rotted wood railing post w/temp support. remedy: replace rotted members/maintain exterior rails.

    Jul 1, 2013

    Resolve
  • Class - 3

    Missing ceiling tile. at kitchen, missing metal ceiling tile approx 1'x4' w/adjacent tile loose. remedy: replace missing tile.

    Jul 1, 2013

    Resolve
  • Class - 3

    Spalling spalling plaster. remedy: repair plaster surfaces.

    Jul 1, 2013

    Resolve
  • Class - 2

    Missing fire stopping. at slop sink room (476) and corridor adjacent to room 409, penetration w/remaining holes in 3 coat plaster and wire lathe to concealed space above. remedy: close all holes - maintain

    Jul 1, 2013 · Penalty $2,500

    Resolve
  • Class - 2

    Doors not closing. at 1st stwy a,b,c, 2nd flr stwyb, 4th stwyd, doors are racked to frame - loose hinges - broken door closers. remedy: repair doors/replace door closers.

    Jul 1, 2013

    Resolve
  • Class - 3

    Reissued#34861736z cars parked in yard contrary to dept records rem: discontinue illegal use or amend cert of occupancy

    Mar 14, 2012

    Resolve
  • Class - 2

    1001.3)failure to maintain egress clear & unobstructed.east entrance on ocean view ave is 50% blocked by security desk adjacent to room 111 partially blocking entrance to classroom.maintain egress clear & unobs

    Jun 18, 2010

    Resolve
  • Class - 2

    Occupancy contrary to that allowed by cert of occupancy or by dob records.noted:reissue 34779790r-school yard playground used as parking lot.remedy:discontinue illegal use or amend c of o.

    Jun 18, 2010

    Resolve
  • Class - 2

    Operation of a place of assembly w/o a current certificate of operation.noted:p.a. permits have expired (6/2009) for cafeteria,auditorium & gym.remedy:renew p.a. permits.

    Jun 18, 2010

    Resolve
  • Class - 2

    Exterior wall has multiple areas of missing/loose mortar joints at allsides/corners parapet level. remedy: secure all loose mortar. make repairs.

    Jun 9, 2009

    Resolve
  • Class - 2

    Illegal occupancy at school yard illegally parked cars inside play yard (approx 50 cars) evident sighs of existing play yard. now being converted for off street parking. remedy: discontinue illegal use or amend

    Jun 9, 2009

    Resolve
  • Class - 2

    Sec.28-307.1 corridor width decreased by obstructions noted on all flrs benches,book carts cabinets,tables,chair,plants,computer charger case,fans all obstructing corridors. remedy: remove obstruction.

    Sep 10, 2008

    Resolve
  • Non-hazardous

    Plaster cracked, missing, spalling in gymnasium. remedy: repair plaster.

    May 4, 2005

    Resolve
  • Non-hazardous

    Failure to maintain:defects noted:leaking roof at west side over gym causing ceiling damages and collapsing condition in gym.remedy:make requirement/repairs to roof ceiling

    Jul 12, 2004

    Resolve
  • Non-hazardous

    Reissue 34386238x-021303x03mm06 failure to maintain.windows througout bldg are broken,inoperable and/or nailed shut.remedy: defective windows throughout bldg.

    Jul 12, 2004

    Resolve
  • Non-hazardous

    Failure to maintain noted all windows throughtout building are broken loose, drafty nailed shut, inoperable. remedy: replace all windows throughout building.

    Feb 13, 2003

    Resolve
  • Non-hazardous

    Failure to maintain noted. bathroom stall paritions rusted corroded, doors missing locations. boys bathroom 4 floor. boys bathroom cafeteria remedy; replace bathroom partitions.

    Feb 13, 2003

    Resolve
  • Non-hazardous

    Failure to maintain building noted defects boiler room sw corner of baley room under staircase broken & cracked concrete wall rebar exposed stress crack in support beam, same location.

    Feb 11, 2002

    Resolve
  • Non-hazardous

    Failure to maintain building noted defects cracked plaster ceiling in room 325 at windows. remedy; make repairs.

    Feb 11, 2002

    Resolve