Violations at 4001 Fillmore Avenue
Brooklyn, NY 11234 · BBL 3-08484-0001 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
16 DOB violations, newest first.
- Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 13, 2004
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 26, 2002
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed
ECB violations
The newest 50 of 54 ECB violations. The city keeps the complete history.
- Class - 2
Exit door not self-closing. noted: at(1st fl) exit j, auditorium, stair h, f(2nd fl) stair e, f, g(3rd fl) stair g, hallway smoke door near rm 354 doors in disrepair/not closing when tested. remedy: repair/repl
Mar 10, 2026 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner. noted: (roof)bulkhead/stair c, d with water damage to ceiling/wall with staining, plaster and paint spalling. remedy: comply with code.
Mar 10, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. lack of emergency lighting for exits, exit discharges and public corridoors per bc 1006.1; 27-542. noted: at(3rd fl) library rm 315 without emergency light
Mar 10, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: at(1st fl) auditorium, cafeteria(2nd fl) gym emergency lights no
Mar 10, 2026 · Penalty $1,250
Active - Class - 2
Reissue ecb #35688759l. failure to maintain building in code-compliantmanner. noted: at 2nd and 3rd floor classrooms doors missing/no door closers throughout. remedy: repair and/or replace.
Mar 10, 2026 · Penalty $3,125
Active - Class - 2
Exit door not self-closing. noted: exit 1 the door on the left, exit jthe door on the left, exit e-f the door on the left, exit a-b the dooron the left, and exit c-d the door in the middle and right. all these
Mar 24, 2025 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: in the cafeteria two lights, exit a-b two lights and in the audi
Mar 24, 2025 · Penalty $1,250
Resolve - Class - 2
Re-issue #35677257h. failure to maintain building in code-compliant manner: noted: observed on the second and third floor most of the classroom doors are missing the door closers. remedy: repair and/or replce.
Mar 24, 2025 · Penalty $3,125
Active - Class - 2
Reissue#35671628k failure to maintain building walls or appurtenances.at cellar level area in gas meter room electric room boiler room.water in filtered throught foundation walls.rem:maintain exterior building
Apr 17, 2024 · Penalty $3,125
Resolve - Class - 2
Reissue#35671629m failure to maintain building in code-compliant manner.classroom doors in various locations at a 3 story building missing door closets,hinges,etc.rem:repair and/or replace.
Apr 17, 2024 · Penalty $1,562
Active - Class - 2
Failure to maintain building in code-compliant manner.noted:classroom doors(old)throughout the building missing door closers.rem:repair/replace door.
Feb 28, 2023 · Penalty $625
Active - Class - 2
Failure to maintain building wall(s)or appurtenances.noted:at cellar at gas meter room,exterior wall became porous allowing the rain water into the gas meter room.rem:maintain exterior wall(s).
Feb 28, 2023 · Penalty $1,250
Resolve - Class - 2
Failure to maintain bldg in code compliant manner:illumination for exits,exit discharges&public corridors per bc1006.1,27-381.noted:on 1fl above rm356,also on stairsd&c,also in hallways 3lights.all these lights
Feb 26, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. no fire stopping per bc 712.3;27-345. noted: at electrical room,2 metal conduits w/no fire stopping around them. remedy: provide/maintain fire stopping.
Feb 26, 2018
Resolve - Class - 2
Reissue#35236009p failure to maintain bldg walls or appurtenances. noted: at gas meter room,foundation wall along the kimball street has become porous allowing the rain water to enter into gas meter room.
Feb 26, 2018
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner: provide required corridor width per bc 1016.2; 27-369. noted: auditorium area, exit passageway behind stage obstructed with musical instruments and chairs.rmdy
Apr 4, 2017
Resolve - Class - 2
Reissue: 35200696l failure to maintain building wall(s) or appurtenancesw. noted: at basement level, gas meter room, electric room,stair case lead to boiler room, foundation wall has become porous allowing
Apr 4, 2017
Resolve - Class - 2
Failure to maintain bldg wall(s) or appurtenances. noted: @ gas meter room, foundation wall @ kimball st side has become porous allowing the rain water to get inside. rem: make necessary repairs.
Aug 5, 2016
Resolve - Class - 2
Reissue#35107731l. place of assembly contrary to approved constructiondocuments. noted: corridor doors leading into cafeteria @ exit 6 swing into opposite direction. rem: comply w/ nov. comply w/ commissioner's
Aug 5, 2016
Resolve - Class - 2
Reissue #35022867h place of assembly contrary to construction documentpa #300570264. noted corridor doors leading into cafeteria at exit 6 are shown to be swinging into cafe. doors swing in towards corridor w/
Aug 1, 2014
Resolve - Class - 1
Work after hours w/o variance permit to 28-105.12.5. noted: masonry work in progress w/o a variance @ time of inspection. remedy: stop all work except to make safe. obtain after hours variance.
Nov 16, 2013 · Penalty $8,000
Resolve - Class - 2
Pa contrary to construction documents pa #300570264. noted corridor doors leading into cafeteria at exit 6 are shown to be swinging into cafe. doors swing in towards corridor w/exit sign on corridor side which
Jun 6, 2013
Resolve - Class - 2
Doors not closing at: 1st story auditorium entrance, stairs j & e, 3rd story stairs g,f,e,d,c & cross corridor near room 354. remedy: repair and/or replace doors.
Jan 26, 2012
Resolve - Class - 2
Reissue # 34928040y. exit passageway of auditorium state exit partially obstructed by stored music & other misc. equipment. remedy: remove obstructions immediately.
Jan 26, 2012
Resolve - Class - 2
Reissue # 34928042h. roof leaks at: various locations throughout water penetrating roof damaging plaster ceilings on 3rd story & gymnasium ceiling. remedy: repair and/or replace roof & damaged plaster.
Jan 26, 2012
Resolve - Class - 2
Roof leak. the roof has become porous allowing rain water to penetrateinto various 3rd flr classrooms. remedy: water proof roof.
Sep 23, 2011
Resolve - Class - 2
Failure to provide panic hardware. no panic hardware at stage exit & @exit door along path of egress to stwy i vestibule from auditorium pa (for 464 persons) remedy: provide code-compliant hardware
Sep 23, 2011
Resolve - Class - 2
Partial obstruction. at auditorium left exit by stage, path of egress reduced approx 75% w/stack of folding benches, music equipment and instruments. remedy: remove all items, maintain corridor/path of egress
Sep 23, 2011
Resolve - Class - 2
Racked doors. the fire proof doors are racked to frame and jam shut atexterior left door stairway i, stairway i vestibule door from rear stag corridor. remedy: replace doors.
Sep 23, 2011
Resolve - Class - 2
Defective doors.noted:staircase doors on 1st,2nd,3rd flr e,f,g,h lines.
Jun 17, 2010
Resolve - Class - 1
Exit passageway obstructed @ both sides of auditorium & behind stage w/ music equipment/tables,speakers.remedy:remove obstructions.
Jun 17, 2010
Resolve - Class - 2
Failure to maintain lose separating and cracking section of concrete approx. 1' x 6' location below boiler rm staircase in boiler rm remedy:repair noted defect
Jun 30, 2009
Resolve - Class - 3
Failure to maintain mortar missing from brick work location south facade at exits 1st ave to play ground at 1st fl grade level remedy:repairfacade
Jun 30, 2009
Resolve - Class - 2
Brick facade has become porous and allowing rain water into the bldg causing interior damages by staircase leading to the boiler room (1st ffl level). remedy: water-proof brick facade.
Nov 21, 2008
Resolve - Hazardous
Exit door-total obstruction- hazardous (1) in auditorium (occ.464) right side of stage in vestibule, end of fire exit passageway, totally obstructed by snowblower & landscaping equipment. (2)in auditorium (occ.
Feb 8, 2007
Resolve - Hazardous
Reissue #34508893p. fire smoke door on 3rd floor not self closing, missing hinge & door closer new:-1st floor-auditorium-right front door byexit does not close-auditorium- right rear door in vestibule does not
Feb 8, 2007
Resolve - Hazardous
Use of illegal hardware. illegal use- gym (occupancy 310) exit doors have passage lock hardware. panic hardware is required by bldg coderem medy: remove illegal hardware, install hardware to bldg code standards
Feb 8, 2007
Resolve - Hazardous
Failure to maintain-exterior reissue# 34508892n. water penetration through exterior wall in room #215,308,315 water damage noticed. remedy: repair leak/ repair damage casued by leak
Feb 8, 2007
Resolve - Hazardous
Required width in corridor 2nd flr by general office decreased by obstruction (2 tables) remedy: remove obstruction.
Mar 24, 2006
Resolve - Hazardous
Fire smoke stop door on 3rd flr not self-closing. missing hinge and door closer. remedy: repair/replace door/hardware.
Mar 24, 2006
Resolve - Hazardous
Water penetration through exterior wall in rooms #308, 309, 215. remedy: repair/maintain exterior brick wall.
Mar 24, 2006
Resolve - Hazardous
Water penetration through the roof into rm 315 (library) (around drainpipe) remedy: maintain/repair roof leaks.
Mar 24, 2006
Resolve - Non-hazardous
Failure to use panic hardware where required by law. location auditorium exit i, & right side rear stage, occupancy 450. remedy: provide panic hardware.
Feb 28, 2003
Resolve - Non-hazardous
Failure to maintain. noted-exit doors operate "fairly"- inconsistant, sticking, swelling, deteriorated frames. location: exit c&d. exit i. exit j, exit a&b, total 12. remedy: replace exit doors to insure
Feb 28, 2003
Resolve - Non-hazardous
Failure to maintain building- cracks in ceilings. rm. 306,303,310,311,gym office, stairwell 9 3rd fl. rm 215, 208, 252, 206, 107, 119, 2nd fl corridor rm 203,204, 301, 211, 261, 256, 210, 205, 300, 302, 315, 21
Jan 17, 2002
Resolve - Hazardous
Failure to maintian - noted defects secure buckling of floor ( in kithcen ) by serving liner and in front of store room entrance way ( hazardous ) remedy : repair floors
Jan 17, 2002
Resolve - Non-hazardous
Failure to maintain building approx 4' x 6' openning cut in chain link permiter fence 9 kimble st ) remedy : repair fence
Jan 17, 2002
Resolve - Non-hazardous
Failure to provide emergency lighting fixture within corridor and stair e-f and c-d on 2&3 floor;including vestibule exit c-d stair c-d and adjoining corridor on first floor.failure to provide emergency power t
Sep 6, 2001
Resolve - Hazardous
Exit door totalk obstruction
Jul 9, 2001
Resolve - Non-hazardous
Failure to maintain defects cracked plaster walls
Jul 9, 2001
Resolve