Violations at 1420 East 67 Street
Brooklyn, NY 11234 · BBL 3-08388-0002 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
25 DOB violations, newest first.
- Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2013 inspection report
Mar 3, 2015
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2013 inspection report
Mar 3, 2015
Dob violation - dismissed - Low pressure boiler boiler required
Violation issued for failure to file annual boiler 2013 inspection report
Mar 3, 2015
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 19, 2007
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 6, 2006
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 31, 2005
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 31, 2005
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Jan 31, 2005
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Construction other optional
C-construction other optional
May 10, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Mar 16, 1999
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
May 4, 1998
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Sep 16, 1997
Dob violation - dismissed
ECB violations
The newest 50 of 60 ECB violations. The city keeps the complete history.
- Class - 2
Failure to maintain building in code-compliant manner.at the time of inspection,there were multiple broken mirrors in dance room(211).brokenglass black window across from room 317.rem:repair and/or replace.
Mar 6, 2026 · Penalty $1,250
Active - Class - 2
Exit door not self-closing.at the time of inspection,the following exit discharge doors were not self-closing properly-exit#6,#1(main),exit c,exit d.rem:repair/replace door.
Mar 6, 2026 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner.use of prohibited door and/or hardware per bc 1008.1.8;27-371(j).at the time of inspection,the following doors for rooms had turn knob handles-244,243,242,2
Mar 6, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code-compliant manner.at the time of inspections,the following room doors were not self-closing-311,313,244,243,242,239,233,234,237,235,226,222,105,109,136,137,138,140,139,142,14
Mar 6, 2026 · Penalty $1,250
Active - Class - 2
Reissued#35672097p failure to maintain building in code-compliant manner.door not close properly at kitchen at door cafeteria entrance 1st floor room 112,138,smoke door by kitchen stair b by 230.rem:repair and/
Apr 29, 2024 · Penalty $1,562
Resolve - Class - 2
Reissued#35672098r failure to maintain building in code-compliant manner.basement level sprinkler central value room and halloway running continue cracks in various location.rem:repair and/or replace.
Apr 29, 2024 · Penalty $1,562
Resolve - Class - 2
Reissue#35672095l exit door not self-closing:exterior door#b & sprinkler central room at cellar level faded to close when tested.rem:repair and/or replace doors.
Apr 24, 2024 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted:at exp #1 top left corner,basement level sprinkler control valve room,& hallway:all have running step cracks in various areas throughout.remedy:repair
Mar 1, 2023 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code-compliant manner.noted:at 3rd fl stair b by 330,1st fl rm 112,138,smoke at exit 3,cafeteria kitchen entrance & smoke by kitchen exit,doors not working properly.remedy:repair
Mar 1, 2023 · Penalty $625
Resolve - Class - 2
Reissue #35578420p.noted:at 1st fl girls gymnasium,auditorium,hallway box #9 by 126,basement stairwell c,box #6 & cafeteria emergency lights inoperative.remedy:repair/replace lighting
Mar 1, 2023 · Penalty $1,562
Resolve - Class - 2
Reissue #35578422z.noted:exterior door exit b & sprinkler control valve rm not working properly.remedy:repair/replace door.
Mar 1, 2023 · Penalty $1,562
Resolve - Class - 2
Atoi observed@bsmt stairc&@sprinkler control valve rm exterior,exit doors not selfclosing repair/replace door.
Mar 31, 2022 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in codecompliant manner:no firestopping per bc712.3;27-345.noted:observed@sprinkler control valve rm,water penetration over entry door.provide/maintain firestopping
Mar 31, 2022 · Penalty $1,250
Resolve - Class - 2
Reissue35553600l failure to maintain bldg in codecompliant manner:illuminate for exits,exit discharges&public corridors per bc1006.1;27-381.noted:observed@1fl girls gym2 existing emergency lights arent op when
Mar 31, 2022 · Penalty $1,562
Resolve - Class - 2
Reissue35502788m failure to maintain bldg in code compliant manner:illumination for exits,exit discharges&public corridors per bc1006.1,27-381.noted:on 1fl girls gym 2emergency lights weren't working when teste
Feb 23, 2021 · Penalty $1,562
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. no fire stopping per bc 712.3/27-345. noted: at basement gas meter rm fire stopping missing/none throughout in various locations w/holes in walls. remedy: prov
Aug 28, 2020 · Penalty $1,250
Resolve - Class - 2
Failure to maintain bldg in code compliant manner illuminations for exits,exit discharges & oublic corridors per bc 1006.1-27-381. noted: at1st fl gym,auditorium & cafeteria emergency were non operational when
Aug 28, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. noted: at basement gas meter rm foundation wall has become pourous allowing water penetration & damage to walls & floor. remedy: repair &/or replace.
Aug 28, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant manner. noted: at(3rd fl)stair d(1st fl)cafeteria,(document)exit c & exit door near gas meter rm doors are in disrepair/racked. remedy: repair &/or replace.
Aug 28, 2020 · Penalty $625
Resolve - Class - 2
Reissued#35383738p(3/6/19)failure to maintain bldg in code compliant manner. at basement level,boiler room on(pit)level & ground water seeping on concrete surface/slabs show deteriorated water damages.
Mar 9, 2020 · Penalty $1,562
Resolve - Class - 2
Reissue 35316973p. failure to maintain bldg in code compliant manner. observed @ bsmt level boiler room pit & ground water seeping in concrete slab floor w/water damage. remedy: repair or replace.
Mar 6, 2019
Resolve - Class - 2
Sec. 28-301.1 unlawful display of art work in cooridors. note: at inspection 3rd fl hanging combustible materials throughout on ceiling fromwall to wall. remedy: comply w/the notice of violation.
Feb 28, 2018
Resolve - Class - 2
Reissue#35235769n failure to maintain bldg in a code compliant manner.note: at basement level room#24,27,30 concrete floor spalling & causing uneven payment. as also in room b34 vacuum pump are in porous condit
Feb 28, 2018
Resolve - Class - 2
Reissue#35235770k failure to maintain bldg in a code compliant manner.note: at basement level boiler room pit & ground water seeping in concrete slab floor w/water damage. remedy: repair &/or replace.
Feb 28, 2018
Resolve - Class - 2
Re-issue #35146914x.failure to maintain building in code complilant manner.noted:at basement level,boiler room,pit and ground water seeping in concrete slab floor.remedy:comply with code/repair or replace
Mar 31, 2017
Resolve - Class - 2
Re-issue #35195433x.failure to maintain building in code compliant manner.noted:at basement level, room#24,27,30,concrete floor spalling and causing uneven payment.remedy:comply with code/replace pavement.
Mar 31, 2017
Resolve - Class - 2
Re-issue #35195435j. exit door not self closing.noted: at 3rd floor,bulkhead staircase(d)& at 2nd floor staircase (d) and at basement room #b24,the doors are defective in the top hinge and remain after use.
Mar 31, 2017
Resolve - Class - 2
Operation of a place of assembly w/o a current certificate of operation.noted:@basement,cafeteria area,the place of assembly certificate #301464573 posted for 600 person has expired.rem:comply w.code.
Jun 24, 2016
Active - Class - 2
Operation of a place of assembly w/o a current certificate of operation.noted:@1st flr,gym area,the place of assembly certificate #301314469posted for 300 person &certificate #301314496 posted for 300 person(to
Jun 24, 2016
Active - Class - 2
Operation of a place of assembly w/o acurrent certificate of operation.noted:@1st flr,auditorium area,the place of assembly certificate #301314487 posted for 601 person is expired.rem:comply w.code.
Jun 24, 2016
Active - Class - 2
Exit door not self closing.noted:@3th flr bulkhead stair(d),2nd flr stair(b)&(d),the doors have defective hinges &closers.rem:comply w.code.
Jun 24, 2016
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner.lack of emergency lighting for exits,exit discharges &public corridors per bc 1006.1,27-542.noted:@ 1st flr auditorium area inoperative emergency lights w.batte
Jun 24, 2016
Resolve - Class - 2
Failure to maintain bldg in code-compliant manner.noted:@basement,boiler room,ground water seeping in concrete slab flr.also @basement room #24,#27,#30 concrete flr spalling &causing balling &uneven pavement.re
Jun 24, 2016
Resolve - Class - 2
Failure to maintain bldg in code compliant manner.in basement boiler room pit,ground water seeping in concrete slab fl.rem comply w/ nov.
Sep 29, 2015
Resolve - Class - 2
Failure to maintain bldg in code compliant manner.in rooms b30,b27,b24concrete fl spalling & causing uneven pavement.rem comply w/ nov.
Sep 29, 2015
Resolve - Class - 2
Door racked at 2nd floor corridor doors adjacent to room 229, 231, 2113rd floor exit stairway 'b' corridor doors adjacent to room 336, 313, and 1st floor corridor door adjacent to room 134. remedy: repair or re
Jul 25, 2014
Resolve - Class - 2
Doors racked at stair c at basement stair d from cafeteria, and corridor doors adjacent to rooms 111,211 & 313. remedy: repair/replace doors
Jun 7, 2013
Resolve - Class - 1
Failure to provide unobstructed exit passageway. noted: contractor (#0029960-gc) excavated 2 egresses at the avenue n side of building,so that the school's auditorium & gymnasium had to be vacated due to the
Jul 16, 2012 · Penalty $1,200
Resolve - Class - 1
Failure to provide unobstructed exit passageways @ 1st fl gymnasium & auditorium exit was obstructed by construction work.remedy:provide required unobstructed exit ways.
Jul 13, 2012
Resolve - Class - 3
Light fixtures not functioning at: 1st story public corridor adjoining gym entry 6 drop in light fixtures not functioning/illuminated (new bulbs installed without illuminating). remedy: replace fixtures.
Feb 16, 2012
Resolve - Class - 2
Doors not closing at: 1st story cross corridor doors near room 110 & stair d, 3rd story cross corridor doors near room 313. remedy: repair and/or replace doors.
Feb 16, 2012
Resolve - Class - 2
Water damaged ceilings at: 3rd story laminated acoustical ceiling tile displaced/missing/water damaged various locations. remedy: repair and/or replace defects noted.
Feb 16, 2012
Resolve - Class - 3
Defective corridor doors 3 floor near room 331 and 313 doors hitting floor and not closing properly.remedy:replace doors.
Nov 18, 2008
Resolve - Hazardous
Exit door not self closing, doors that do not close are: back right ofstage in auditorium. back door on stage in auditorium. girls gym door by room 100. stairs b & c, vestibule door by exit, 1 door each remedy:
Feb 7, 2007
Resolve - Hazardous
Required width decreased by obstruction (tables) in corridor from doorby stage to exit (lef door) remedy: remove obstruction.
Mar 24, 2006
Resolve - Non-hazardous
Failure to maintain.defect is:cross corridor doors on each floors are loose,sagging and not self closing.remedy:repair and/or replace doors.
Jul 14, 2004
Resolve - Non-hazardous
Failure to maintain.defect are:water penetrating through boiler room floor and mortar joints around hatch door in boiler room.remedy:repair wall.
Jul 14, 2004
Resolve - Non-hazardous
Failure to maintain:defect is:plaster wall in 1st floor corridor above exit #3 &4 is loose and bulging.remedy:repair wall.
Jul 14, 2004
Resolve - Non-hazardous
Failure to maintain:defect is:missing handrails in stair case #5 & 6 between 2nd and 3rd floors.remedy:provide handrails.
Jul 14, 2004
Resolve - Non-hazardous
Failure to maintain.defects are:missing bathroom stall doors and corroded partitions in the following locations.locations are:1)1st,2nd and 3rd floors bathrooms.2)basement boys bathroom.remedy:replace partition
Jul 14, 2004
Resolve