Violations at 2675 Nostrand Avenue

Brooklyn, NY 11235 · BBL 3-07474-0001 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

11 DOB violations, newest first.

  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jan 1, 2009

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - active
  • Construction other optional

    C-construction other optional

    May 21, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jul 25, 1994

    Dob violation - dismissed

ECB violations

The newest 50 of 66 ECB violations. The city keeps the complete history.

  • Class - 2

    Reissue ecb #35720914j. exit door not self-closing. noted: at (1st fl)exit 6 and 8 (2nd fl)stair e/f doors are in disrepair/not closing whentested. remedy: repair/replace door.

    Mar 17, 2026 · Penalty $1,562

    Active
  • Class - 2

    Reissue ecb #35720915l. failure to maintain manner. illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: at (1st fl) gym, auditorium, cafeteria emergency lights not working

    Mar 17, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue ecb #35720916n. failure to maintain building in code-compliantmanner. noted: at (3rd fl) stair c wire glass view panel cracked. remedy: repair and/or replace.

    Mar 17, 2026 · Penalty $3,125

    Active
  • Class - 2

    Found burnham (model#4fl 993) gas fired boiler in cellar with defective motorized damper correct violating condition submit certificate of correction

    Aug 19, 2025 · Penalty $1,250

    Active
  • Class - 2

    Xound burnham (model#4fl 993) gas fired boiler in cellar with defective motorized damper correct violating condition submit certificate of correction

    Aug 19, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: at 3rd floor at exit "c" wired glass view panel in the door is cracked. remedy: repair/replace door.

    Jul 3, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. noted: at auditorium at exit #11, 3 emergency exit lighting, 2 at cafet

    Jul 3, 2025 · Penalty $1,250

    Active
  • Class - 2

    Exit door not self-closing. noted: exit #8, both doors do not open/close properly needs excessive force to open. at cellar exit door that leads to the courtyard is rotted and do not close properly. remedy: repa

    Jul 3, 2025 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.-noted: smoke door at exit #9, smoke door at exit #6 and class room door room #235 do not close properly. remedy: make necessary repairs.

    Jul 3, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Reissued #35657979l failure to maintain building in code compliant manner:illumination for exits,exit discharges & public corridors per bc 1006.1; 27-381.noted:exit e 2 lights,exit c & d 2 lights & gymnasium 2

    Mar 20, 2023 · Penalty $1,562

    Resolve
  • Class - 2

    Boiler motorized draft regulator seized up/gas pressure gauge line not hard pipe with gas cock/burner relay fault screen defective/boiler feed pump not keeping up with water demand;ie; goes off on low water;cor

    Jun 21, 2022 · Penalty $625

    Active
  • Class - 2

    Low water alarm bell defective/burner relay fault code screen defective/gas pressure gauge line not hard pipe with gas cock/boiler feed pump not keeping up with water demand;ie; goes off on low water/vac system

    Jun 21, 2022 · Penalty $625

    Active
  • Class - 2

    Re-issue #35561360l(5/13/2021)failure to maintain bldg in code-compliant manner:at exit 2 main entrance exterior door(s) frame is deteriorated missing saddle.remedy:repair &/or replace.

    May 16, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Re-issue #355613621n(5/13/2021)failure to maintain bldg in code compliant manner.illuminated for exits,exit discharges & public corridors per bc1006.1,27-381 at 1st fl gym existing lights not operational when t

    May 16, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Failure to maintain bldg in codecompliant manner.illumination for exits,exit discharges&public corridors per bc1006.1;27-381.@1fl gym 1place3lights existing emergency lights arent operational when tested@time o

    May 13, 2021 · Penalty $625

    Resolve
  • Class - 2

    Reissue35495135m doi5.8.20 failure to maintain bldg in codecompliant manner.noted@1fl exit1 outside exit door,exp1 on 29st in bottom of doorframe rotten.need to repair or replace.repair &/or replace door.

    May 13, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35423283l failure to maintain bldg in code compliant manner. noted: observed on the 1st fl at exp#1 on 29 street the bottom of the door frame is rotten. remedy: repair & or replace.

    May 8, 2020 · Penalty $1,562

    Resolve
  • Class - 2

    Exit door not self closing. noted:at cellar,exit 7,(boiler room),1st fl exit 8 and 9,exit 1 and e,2nd fl exit d,auditorium exit 10 and 11,and the kitchen,exit doors are not working properly due to defective har

    May 15, 2019

    Resolve
  • Class - 2

    28-301.1 unlawful placement of furnishings,decorations or other objects at exits that obstruct access to,egress from or visibility thereof per fdny 2008 code;fc 1027.4. noted:at auditorium stage,both exits are

    May 15, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted: at exposure 2 (east 29 st), exit door has rotted door jamb. remedy: repair and/or replace

    May 15, 2019

    Resolve
  • Class - 2

    Failiure to maintain in code-complaint manner noted: @the 3rd fl, doorclosers are not workinh properly throughtout the entire floor, rem:repair and/or replace.

    May 15, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted:at the auditorium main entrance,exit d on 1st fl,2nd fl exit smoke corridor door by rm 237,3rd fl exit c,and cellar bottom door by main entrance,exit

    May 15, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner. noted:@main entrance, exp 2 (e 29.st), exit 9, exp 3 (nostrand ave), missing mortar between steps and has cracks through.rem: repair and/or replace

    May 15, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code-compliantmanner: illumination forexits; exit discharges & public corridors per bc 1006-1; 27-381. noted: @the gymnasium, exit light #9, auditorium right wall, 1 light,

    May 15, 2019 · Penalty $1,562

    Resolve
  • Class - 2

    Sec: 28-301.1. unlawful placement of furnishings, decorations or other objects @ exits that obstruct access to egress from or visibility thereof per fdny 2008 code; fc 1027.4. noted @ 1st flr behind the auditor

    May 16, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: illumination for exits. exit discharges & public corridor per bc 1006.1; 27-381. observed @ 1st flr exit 1 & corridor opposite room 131 not operational emergen

    May 16, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. use to prohibited door &/or hardware per bc 1008.1; 27-371(j). observed @ all flrs installed door kick stops on multiple doors in the school bldg. rem: provide

    May 16, 2017

    Resolve
  • Class - 2

    Exit door not self closing. noted @ 3rd flr staircase 'a', 2nd flr exits c & a, 1st flr exit 1 & 8 not self closing doors. rem: repair or replace doors.

    May 16, 2017

    Resolve
  • Class - 3

    Failure to maintain bldg property in code compliant manner. observed: a metal pole of fence gate is apprx 15'high, and is stable but is leaning toward public sidewalk. rmdy: repair defects.

    Jan 18, 2017

    Resolve
  • Class - 2

    Reissue 349539123r defective doors gym entry/exit door 1 flr,also 3rd flr stair b. rmdy: repair/replace doors.

    Jun 18, 2013

    Resolve
  • Class - 2

    Re-issue #34928033x water penetrating bldg envelope at: rear wall of auditorium stage. remedy: repair/replace defect noted.

    Apr 18, 2012

    Resolve
  • Class - 2

    Re-issue #34928034h. loose/deteriorating mortar joints at: parapet voorhies avenue exposure. remedy: repair/replace defects noted.

    Apr 18, 2012

    Resolve
  • Class - 2

    Doors not closing at: gym main entry/exit. remedy: repair/replace doors.

    Apr 18, 2012

    Resolve
  • Class - 2

    Work w/o permit. at 1st flr room 100, erected wood deck w/guard rails & stairs. remedy: obtain approval and permit or restore to prior legalcondition.

    Sep 22, 2011

    Resolve
  • Class - 2

    Loose mortar joints. at parapet wall along voorhies ave, loose and weathered mortar joints at various areas. remedy: repair facade mortar joints.

    Sep 22, 2011

    Resolve
  • Class - 2

    Moisture penetration. at auditorium stage rear wall on right, the exterior wall has become porous allowing moisture to penetrate through cmublock wall. remedy: water proof exterior wall.

    Sep 22, 2011

    Resolve
  • Class - 2

    Prohibited hardware. at auditorium, the entry doors from lobby have automatic door stops that prevent the proper operation of fire proof doors. doors in locked open position w/auditorium in use at time of

    Sep 22, 2011

    Resolve
  • Class - 2

    Reissue #34481949h work w/o permit. at cellar level, installed 8' high(non full height) partition w/hollow core wood dividing corridor requiring key entry. remedy: obtain permit if feasible or restore to prior

    Sep 22, 2011

    Resolve
  • Class - 2

    Sec. 28-301.1 failure to maintain egress clear & unobstructed observed: at cellar level corridor outside gas boiler room. erected 8'high drywall partition with door. wall blocks view to stairwell exit. door swi

    May 12, 2010

    Resolve
  • Class - 2

    Sec. 28-301.1 failure to maintain egress clear & unobstructed observed: front auditorium exits used for storage of black board,furniture,vertical lift scaffold system. remedy: remove obstruction.

    May 12, 2010

    Resolve
  • Class - 2

    Failure to maintain observed: at auditorium rear,hole in plaster ceiling,spalling plaster at wall adjacent to hole. remedy: maintain building.

    May 12, 2010

    Resolve
  • Class - 2

    Defective hardware - 1- roof bulkhead doors - interior key cylinder inplace. remedy: install hardware as per code.

    Jun 24, 2009

    Resolve
  • Class - 3

    Sec. bc 1509. reissue: 34576653k. failure to provide required protective railing around perimeter of roof bldg is a 3 sty structure. remedy:provide protection on roof.

    Aug 20, 2008

    Resolve
  • Class - 2

    Exterior facade/parapet has multiple cracks, missing mortar joints bulging. noted: at nw side cornice slight shift & missing mortar, also above exit doors on left side of main entrance (29 st) bulging of brick

    Aug 20, 2008

    Resolve
  • Non-hazardous

    Sec 27-334:reissue # 34504807l:failure to provide required protective railing around perimeter of roof @ north,east,west elevation of 3 story structure. remedy:provide protective railing.

    May 21, 2007

    Resolve
  • Hazardous

    Reissue #34481941n failure to provide required protective railing; around perimeter of roof at north, east and west elevations of 3 sty. structure. remedy: provide protective railings as required. around

    Feb 22, 2006

    Resolve
  • Non-hazardous

    Noted:exit stair passage(cellar,nostrand ave)lighting,defective-no lighting defective-no lightning w/ defective bulbs/circuits.remedy:repair/replace lighting as required,maintain exit

    May 20, 2005

    Resolve
  • Hazardous

    Noted: erected partial height (8 feet high) partition with door withincellar space creating separate corridor space blocking exits & exit signs. remedy: obtain permit or restore to prior legal condition.

    May 13, 2005

    Resolve
  • Non-hazardous

    Noted:exit doors not self-closing:1 nostrand ave cellar exit stair door 2 1st floor main entry/exit door right hand leaf.remedy:repair.replace doors/hardware as required,maintain exit doors

    May 13, 2005

    Resolve
  • Non-hazardous

    Noted:failure to provide/maintain fire-stopping within:1 paint room-wall penetrations 2 boiler room -south wall penetrations.remedy:provide/maintain fire stopping

    May 13, 2005

    Resolve