2525 Haring Street

Brooklyn, NY 11235BBL 3-07447-0001Map

Owner of record: NYC Department Of Parks And Recreation

2525 Haring Street is a school building built in 1958 in Brooklyn, 11235. The owner of record is NYC Department Of Parks And Recreation. HPD has no housing violations on record for this property.

HPD violations
0
DOB violations
31
ECB violations
64
HPD complaints
0

What to know

Good
No open Class C

No open immediately-hazardous violations among recent records.

Good
No HPD violations

HPD has not cited this building.

Good
No unpaid ECB fines

No balance due on recent ECB violations.

Rent stabilization

No rent-stabilized units in 2018–2024 tax bills

Some apartments can still be regulated. Use the rent-stabilized checker or request the rent history from HCR.

Violations

Most recent first. Showing up to 50 per agency.

HPD housing violations · 0

No HPD violations on record

DOB building violations · 31

  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2024 external low pressure inspection

    Nov 14, 2025

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2023 external low pressure inspection

    Sep 23, 2024

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2020 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2021 external low pressure inspection

    Jun 30, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2019 external low pressure inspection

    Jun 20, 2023

    Dob violation - active
Show 21 more ↓
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - active
  • Low pressure boiler boiler required

    Violation issued-failure to file 2022 external low pressure inspection

    Apr 25, 2023

    Dob violation - active
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2016 cat 1 insp/tst

    Jan 26, 2018

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2015 cat 1 insp/tst

    Jan 3, 2017

    Dob violation - dismissed
  • Elevator affirmation of correction elevatorrequired

    Vio issued to elevator - fail to correct defects on 2014 cat 1 insp/tst

    Nov 14, 2016

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jan 6, 2012

    Dob violation - resolved
  • Elevator annual inspection / test elevatorrequired

    Violation issued to elevator-failure to file category 1 2010 inspection/test

    Dec 13, 2011

    Dob violation - dismissed
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 24, 2010

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Mar 19, 2008

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Jun 26, 2007

    Dob violation - resolved
  • Elevator elevatorrequired

    E-elevator elevatorrequired

    Nov 12, 2003

    Dob violation - resolved
  • Elevator elevatoroptional

    Ll1081-local law 10/81 - elevator elevatoroptional

    Jan 20, 1999

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    May 4, 1998

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Sep 16, 1997

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 29, 1995

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1994

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Aug 16, 1993

    Dob violation - active
  • Elevator elevatoroptional

    1

    Jun 28, 1993

    Dob violation - active
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Jun 1, 1993

    Dob violation - dismissed

ECB violations · 64

  • Class - 2

    Reissue ecb #35720804z. failure to maintain building in code-compliantmanner. no fire stopping per bc 712.3; 27-345. noted: at (basement)electric meter rm fire stopping inadequate/missing. remedy: provide/maint

    Mar 17, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue ecb #35720803r. failure to maintain building in code-compliantmanner. noted: a (basement)walls water penetration porous damage/spalling paint/plaster throughout various areas. remedy: repair and/or repl

    Mar 17, 2026 · Penalty $3,125

    Active
  • Class - 2

    Reissue ecb #35720802p. failure to maintain building in code-compliantmanner. noted: at roof level/bulkheads/facade with cracks vertical/horizontal throughout various areas. remedy: repair and/or replace.

    Mar 17, 2026 · Penalty $3,125

    Active
  • Class - 2

    Boiler #2 pilot gas piping leaking. correct all listed defects

    Aug 12, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.observed that all the walls in the basement have become porous & the walls have spalling paint & broken.rem:repair and/or replace.

    Jul 22, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.observed roof material bubbling at various locations water damage on lower floor ceiling.rem:repair and/or replace.

    Jul 22, 2025 · Penalty $1,250

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner.observed at various locations at roof level & exterior of building stop cracks,spalling bricks also masonry mortar.rem:repair and/or replace.

    Jul 22, 2025 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.no firestopping per bc 712.3;27-345.observed missing firestopping inside electric roomin basement observe door.rem:provide/maintain firestopping.

    Jul 22, 2025 · Penalty $1,250

    Active
  • Class - 2

    Reissue #35657981k failure to maintain building walls or appurtenances.crack starting from above exit 8&9 by exit 1 & exit 2a.remedy:maintain exterior building wall

    Mar 23, 2023 · Penalty $3,125

    Resolve
  • Class - 2

    Re-issue #35561359y(5/13/2021)failure to maintain bldg walls or appurtenances at corner of ave y & haring st.staggering arches approx.3' auditorium bldg & next to exit 2a,exp.#3 by exit 4 wall has vertical crac

    May 16, 2022 · Penalty $3,125

    Resolve
Show 40 more ↓
  • Class - 2

    Reissue #35561358m(5/13/2021)exit door not self-closing.at auditorium stages exit on both side are not self-closing when tested,at 1st fl exit 7.remedy:repair &/or replace doors(s)

    May 16, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35423277p date of issue 5-15-2019 exit door not self closing properly. noted: at auditorium right rear & left door on stage are not working properly. at 1st fl exit 7 outside 3 exit doors are not self

    May 13, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue#35423173k date of issue 5-15-2019 failure to maintain bldg walls or appurtenances. noted: @ exp#3(ave y side),by exit 4,cormer wall has a vertical running crack approx 5 feet. remedy: maintain exterior

    May 13, 2021 · Penalty $3,125

    Resolve
  • Class - 2

    Re-issue#35423278r failure to maintain building in code compliant manner:no fire stopping per bc 712.3;27-345. noted:observed in the cellar electrical room conduits that are penetrating through the wall. remedy

    May 13, 2020 · Penalty $3,125

    Resolve
  • Class - 2

    Exit door not self closing. noted: at auditorium, right rear and left door on stage are not working properly due to defective hardware. remedy: repair/replace door

    May 15, 2019

    Resolve
  • Class - 2

    Failure to maintain building wall(s) or appurtenances noted:@exp 3 (ave y side), by exit 4, corner wall has a vertical running crack approximately 5'.rem: maintain exterior building wall.

    May 15, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.noted: @the auditorium on the left side of the septs to the stage, ceiling has spalling paint.rem: repair and/or replace.

    May 15, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner:no fire stoppingper bc 712.3;27-345. noted:at cellar,electrical room has conduits thatare penetrating through the wall above the door. remedy:provide/mainta

    May 15, 2019

    Resolve
  • Class - 2

    Re issue #35328652m noted: @1st amd 3rd floor, wi down door holder installed on multiple doors. rem:provide legal hardware.

    May 15, 2019

    Resolve
  • Class - 2

    Failure to maintain building in code-compliant manner noted: @exp 4 byexit 7, handicap ramp and steps has cracks in various locations.rem:repair and/or replace.

    May 15, 2019

    Resolve
  • Class - 2

    Reissue #35267189n failure to maintain bldg in code compliant mannernoted: at 2nd floor set back, missing railing apprx 30 ft at front of building. rmdy: install protective railing/fence.

    Apr 10, 2018

    Resolve
  • Class - 2

    Reissue #35267187j failure to maintain bldg in code compliant manneruse of prohibited door hardware per bc 1008.1.8; 27-371 (j). noted: comply with notice of violation.

    Apr 10, 2018

    Resolve
  • Class - 1

    *05j01; 67l10,68bb11,17m11. class 1 item 05j- adjsut zone lock restrictor; 17h-replace where needed.

    Jan 17, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. noted @ basement gas meter room cracked wall approx 7ft by the door. rem: repair wall.

    May 16, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner: use of prohibited door and/or hardware per bc 1008.1.8; 27-371 (j). noted: at 3rd and 1st floors installed kick stop on multiple doors.

    May 16, 2017

    Resolve
  • Class - 2

    Sec: fc 313. observed @ the basement boiler room storage of approx 8 gas power operated machines/equipments. rem: comply w/ code.

    May 16, 2017

    Resolve
  • Class - 2

    Exit door not self closing. observed @ 2nd & 1st flrs not self closing doors @ exit 5 & exit 6 respectively. rem: repair &/or replace doors.

    May 16, 2017

    Resolve
  • Class - 2

    Unlawful placement of furnishings, decorations or other objects @ exitthat obstract access to egress from or visibility thereof per fdny 2008 code, fc 1027.4. observed @ 3rd flr, 2nd & 1st corridor opposite fle

    May 16, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant manner. observed @ the 2nd flr overhand rppf missing protecting railing/fencing approx 30ft. rem: install protecting railing/fencing.

    May 16, 2017

    Resolve
  • Class - 3

    Work without a permit.re-issue ecb #35101220m conversion of rooms.room118 removed gas lines,room 132 removed plumbing fixtures. remedy: comply with nov.

    Sep 21, 2015

    Resolve
  • Class - 2

    Re-issue ecb# 35023303r work w/o permit. at room 118, installed gas lines w/o a permit; @ room 132 removed plumbing fixtures and door & converted space to storage area. remedy: obtain work permits

    Jul 23, 2014

    Resolve
  • Class - 2

    Reissue: 34953911p, 349280212. missing/defective doors at room 132, 3 floor stair a; 2 floor stair a,c. rmdy: repair/replace doors.

    Jun 17, 2013

    Resolve
  • Class - 2

    Work w/o permit. illegal work noted at room 118. gas line installed for 2 stoves and 1 dryer. rmdy: obtain permit,remove.

    Jun 17, 2013

    Resolve
  • Class - 2

    At 1st sty restroom #132. removed plumbing fixtures and door. remedy: obtain permit.

    Apr 18, 2012

    Active
  • Class - 3

    Work does not conform to approved documents.@ lunchroom,4 occupied offices contrary to pa-071 for job#301450427 which indicates 2 offices & store room.rem:conform to approved documents or amend documents.

    Sep 21, 2011

    Resolve
  • Class - 2

    Occupancy contrary to dob records.restroom#132 w/ fixtures removed & used as storage room w/ no door,the restroom door to fire corridor has been removed leaving the door buck opening for open access.rem:discont

    Sep 21, 2011

    Resolve
  • Class - 2

    Roof moisture penetration.the roof has become porous allowing moisture to penetrate into 3 flr corridor adjacent to elevator.rem:water proof roof.

    Sep 21, 2011

    Resolve
  • Class - 2

    Prohibited hardware.@ bulkhead doors stairway a & c dead bolt installed capable of receiving padlock.rem:remove illegal hardware.

    Sep 21, 2011

    Resolve
  • Class - 2

    27-371(b))plexi vision panels.@ 3 flr,plexi(thermo plastic)visions panels installed in classroom doors throughout.rem:provide code compliant vision panels.

    Sep 21, 2011

    Resolve
  • Class - 2

    Defective/inoperative doors.all smoke doors all flrs w/ wood blocks jammed in hinge side.preventing doors from closing.(for handicap/wheel chair access)only during school hours.rem:maintain code compliant fpsd

    Sep 21, 2011

    Resolve
  • Class - 3

    Reissue#34848003p defective security,intruder gates.all intruder/security roof gates have erosion @ the base w/ rusting through in several areas.rem:repair gates or remove gates.

    Sep 21, 2011

    Resolve
  • Class - 2

    Fail to maintain. observed inadequate fresh air ventilation gas meter room (noted: exhaust fan in room operates only when room lights are turned on) residential type bath fan. remedy: provide code compliant ven

    May 14, 2010

    Resolve
  • Class - 2

    Fail to maintain. observed: exterior exit overhang, exit 7, stair b spalling concrete exposed rusted rebar. remedy: maintain bldg

    May 14, 2010

    Resolve
  • Class - 2

    Fail to maintain. observed: bldg racked interior f.p.s.c doors 3 fl stairs a,b,c, 2 fl stair bb first floor stair a,c. binding corridor smoke doors flrs 3,2 exit 7 first floor. remedy: maintain bldg

    May 14, 2010

    Resolve
  • Class - 2

    Fail to maintain. observed: exit light inoperative exit 1, first floor(note: custodian states light burns out with every rainstorm. no leaksobserved) remedy: maintain bldg

    May 14, 2010

    Resolve
  • Class - 3

    Fail to maintain. observed: rooftop perimeter security fences rotted,rusted large holes in frames observed at base. remedy: maintain bldg

    May 14, 2010

    Resolve
  • Class - 2

    Fail to maintain. observed light switch located in gas meter room is standard toggle switch. remedy: provide code complaint light switch

    May 14, 2010

    Resolve
  • Class - 2

    Fail to maintain bldg adequate fire stopping observed: at electric meter meter room, diamond lathe transom over entry doors, circular holes in entry doors. remedy: maintain fire stopping

    May 14, 2010

    Resolve
  • Class - 3

    Fail to maintain. observed: spalling plaster on ceiling, exposed scratch layer, 3 fl ceiling outside elevator exit 3 ceiling at cafeteria. remedy: maintain bldg

    May 14, 2010

    Resolve
  • Class - 2

    No fire stopping - 1- room b-3 - interior wall. 2- room b-5 into hallway. 3- gas meter room wall. remedy: install fire stopping as per code.

    Jun 25, 2009

    Resolve

Complaints

No HPD complaints in our records

Complaint data is still being backfilled from NYC Open Data.

Sales history

No recorded sales in our data

Sales come from the NYC Department of Finance rolling sales file.

Building details

Building type
School building (W1)
Year built
1958
Floors
3
Residential units
—
Building area
71,940 ft²
Lot area
93,720 ft²
Zoning
R3-2
Community board
315
Council district
48
Block / lot
7447 / 1
Assessed value
$8,188,650
Landmark / historic district
No

Questions about 2525 Haring Street

Who owns 2525 Haring Street?

The owner of record in NYC Department of City Planning PLUTO data is NYC Department Of Parks And Recreation.

Does 2525 Haring Street have violations?

NYC HPD has no housing violations on record for this property.

Is 2525 Haring Street rent stabilized?

No rent-stabilized units appear in its 2018–2024 tax bills. Individual apartments can still be regulated, so request the rent history from NYS Homes and Community Renewal if unsure.

When was 2525 Haring Street built?

City records list 1958 as the year it was built.

Source: NYC Open Data (DCP PLUTO, HPD, DOB, ECB/OATH, DOF). Records can lag the city's systems. Data refreshed weekly.