Violations at 2202 Avenue V
Brooklyn, NY 11229 · BBL 3-07381-0201 · Back to the property
HPD housing violations
No HPD violations on record
DOB building violations
4 DOB violations, newest first.
- Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 27, 2001
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed - Boilers boiler required
Ll6291-local law 62/91 - boilers boiler required
Feb 7, 2000
Dob violation - dismissed
ECB violations
The newest 50 of 56 ECB violations. The city keeps the complete history.
- Class - 2
Failure to maintain building in code compliant manner.noted:at 2nd fl stair d,e hallway smoke door near rm 256,gym 3rd fl stair c 5th fl stair f hallway smoke door near rm 555 doors are in disrepair racked.rem:
Mar 13, 2026 · Penalty $1,250
Active - Class - 2
Failure to maintain building in code compliant manner.noted:at roof level bulkhead stair c/d basement gas meter rm with water damaged/penetration to cleanness/floors/walls staining w/spalling panels/plaster.rem
Mar 13, 2026 · Penalty $1,250
Active - Class - 2
Reissue ecb#35692115h failure to maintain building in code compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:at 1st fl auditorium 2nd fl gym 5th fl gym emer
Mar 13, 2026 · Penalty $1,562
Resolve - Class - 2
Reissue #35672610r; failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. emergency exits lights not oerational when tested a
Mar 20, 2025 · Penalty $3,125
Resolve - Class - 2
Reissued #35672610r. fail to maintain building in code-compliant manner: illuminating exit discharge of public corridors per bc 1006.1,27-381 at gymnasium. emergency lights not properly when tested. remedy: rep
Jun 27, 2024 · Penalty $1,562
Resolve - Class - 2
Missing bolts & dogs on boiler doors ,leak on left side of boiler by hand hold gasket
May 16, 2023 · Penalty $625
Resolve - Class - 2
Missing bolts & dogs on boiler doors,need valve on oil suction line b/4 anti syphon valve
May 16, 2023 · Penalty $625
Active - Class - 2
Failure to maintain building in code-compliant manner.illumination for exits,exit discharges & public corridors per bc1006.1;27-381.noted:observed in gymnasium most emergency lights not operational when tested.
Mar 15, 2023 · Penalty $625
Resolve - Class - 2
Re-issue #35560964h(5/4/2021)exit door not self-closing:3 exterior exit doors.not self-closing when tested at 1st fl level. remedy:repair/replace door(s)
May 12, 2022 · Penalty $1,562
Resolve - Class - 2
Reserve #35560967n(5/4/2021)failure to maintain bldg in code compliantmanner.illumination for exits,exit discharges & public corridor per bc1006.1,27-381.exit emergency light are not operational when tested at
May 12, 2022 · Penalty $1,562
Resolve - Class - 2
Reissue35495130n doi5.6.20 failure to maintain bldg in codecompliant manner:illumination for exits,exit discharges&public corridors per bc1006.1;27-381 note on 2fl exith&1st fk corridor.these lights exisitng em
May 4, 2021 · Penalty $1,562
Resolve - Class - 2
Exit door not selfclosing properly@1fl@exitf outside 1exit door not selfclosing properly@time of insp.repair &/or replace door.
May 4, 2021 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in a code compliant manner: illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. noted: on the 2nd fl exit h & the 1st fk corridor these lights were not worki
May 6, 2020 · Penalty $625
Resolve - Class - 2
Failure to maintain bldg in code compliant-manner,staircase 3&4 roof level buklhead,water coming in,parts of ceiling cracking and falling. remedy:repair and/or replace
May 24, 2019 · Penalty $625
Resolve - Class - 2
Failure to maintain building in code compliant manner.staircase 3 and 4 roof level bulkhead,water coming in parts of ceiling cracking and falling. remedy: repair and or replace.
May 24, 2019
Resolve - Class - 3
Failure to maintain building in code compliant manner. noted: at level 2 above auditorium entrance, water penetration, damaged ceiling. rmdy: repair damaged area.
Apr 5, 2018
Resolve - Class - 2
Failure to maintain bldg in code complaint manner. 125 gallons of point are being stored in the boiler room. remedy: remove point from boiler room.
May 25, 2017
Resolve - Class - 2
Failure to maintain bldg in a code complaint manner. illumination for exits,exit discharges & public corridors per bc 1006.1;27-381 fire exit des not illuminate at time of inspection,5th fl side entrance to aud
May 25, 2017
Resolve - Class - 2
Exit door not self closing,fire door not self closing near rm#412,not self closing doors: near stairs opposite side of room 309 fire exit door #9 & 3rd fl,2 firee entrance doors into kitchen,1st fl fire exit do
May 25, 2017
Resolve - Class - 2
Failure to maintain exit sign at cafeteria northside, evident sign onewas there also as per application date in 1983 shows exit light on plans. remedy : provide exit sign northside
Jun 21, 2013
Resolve - Class - 2
Defective floors at room 504, missing / hole in flooring / sub flooring in corner of room. remedy: repair floor
Jun 21, 2013
Resolve - Class - 2
Defective doors at 3 fl corridor door. doors swing too fast and hitting each other. remedy : repair door
Jun 21, 2013
Resolve - Class - 2
Doors not closing at 4th sty stair h. remedy: repair/replace door noted.
Apr 18, 2012
Resolve - Class - 2
No a/c window support at 2fl along east 22 street a/c window unit installed w/o metal support bracket rem: provide a/c support or remove window a/c unit
Sep 20, 2011
Resolve - Class - 2
Missing fire stop at cellar electric room no fire stop at ceiling conduit penetrations rem: provide fire stop
Sep 20, 2011
Resolve - Class - 2
Spalling plaster spalling plaster at exit 10 vestibule wall & ceiling auditorium stage rear ceiling repair plaster surface
Sep 20, 2011
Resolve - Class - 2
Plexi vision panels at 4th fl various rooms throughout plexi thermoplastic vision panels installed rem: provide code compliant vision panels
Sep 20, 2011
Resolve - Class - 2
Broken door checks the fire proof doors not self closing at 3fl stairway c smoke doors adjacent to room 256 rem: replace door checks so doors properly self close
Sep 20, 2011 · Penalty $2,500
Resolve - Class - 2
Racked doors the fire proof doors are racked to frame at 5fl stairway f g roof storage room rem: repair if feasible or replace doors
Sep 20, 2011 · Penalty $2,500
Resolve - Class - 2
Reissue #34854963n spalling plaster concrete spalling plaster walls and/or ceiling at 5fl rooms 501 507 511 and roof store room w/ spalling concrete ceiling exposing rebar rem: repair all surfaces
Sep 20, 2011
Resolve - Class - 2
Fail to maintain adequate firestopping observed. several open penetrations around conduits passing thru ceiling of room. remedy: maintain firestopping
Jun 3, 2010
Resolve - Class - 2
Fail to maintain. spalling plaster on walls & ceiling rms. 501,507,511. at rooftop storeroom by stair 6 exposed rebar on ceilings. remedy: maintain bldg
Jun 3, 2010
Resolve - Class - 2
Fail to maintain. racked, binding fpsc doors at stair 6 5th fl exit drrm 105. remedy: maintain bldg
Jun 3, 2010
Resolve - Class - 2
Reissue 34792244x fail to maintain. missing/defective door closes at exit 6 1st fl 2 closers. exit c1 lunchroom. remedy: maintain bldg
Jun 3, 2010
Resolve - Class - 2
Reissue 34698106r 1st fl lunch rm occupancy over 300 persons exit doors swing against flow of egress
Jun 23, 2009
Resolve - Class - 2
Defective doors and frames. 1- all exterior bulkhead roof doors, & frames & saddles rotted. 2- exit #9 ground flr - saddle rotted. remedy: repair/replace accordingg to code.
Jun 23, 2009
Resolve - Class - 2
Hardware defective. 1- gate to roof 5/f chained padlocked. 2- roof - exterior 5/6 hdwr. not functional. 3- stwy- 3/4 roof - door hardware broken. 4- interior doors - 5 flr stwy 6 no closer - stwy 7/g no closer
Jun 23, 2009
Resolve - Class - 3
Standing water - 1- s.w. corner rear yard approx 20' x 40'. 2- basement flood at old coal shute. remedy: maintain/contain all water flow as per code.
Jun 23, 2009
Resolve - Class - 2
Shed doesn't meet building code specifications noted: there are missing vertical enclosures (parapets) 24' along e 22 st. remedy: conform to code.
Feb 20, 2009 · Penalty $10,000
Resolve - Class - 1
Reissue: 34570097l. hazardous. 1st floor lunch room occupancy of over 300 persons exit door swing against flow of egress. remedy: change swing of doors/provide (panic) hardware.
Aug 20, 2008
Resolve - Class - 3
Defective doors, gym door on 5th floor & corridor door on 3 floor nearroom 354. doors dragging on floor & not opening or closing properly. remedy: replace doors.
Aug 20, 2008
Resolve - Hazardous
Reissue # 34504804x:noted: wood fl @ rooms 503 approx 3' x 8' is defective,rotten & trip hazard.remedy:repair/ replace fl.
May 17, 2007
Resolve - Hazardous
Reissue # 34504806j.noted: 1st fl lunch room occupancy of over 300,old wood doors open into lunch room from hall.remedy:replace or repair doors to swing w/ flow of egress.
May 17, 2007
Resolve - Hazardous
Exit doors swing against the flow of egress. location: 1st floor lunchroom occupancy of over 300 (small kids and teachers) old wood doors open "into" lunch room from hall. remedy: replace all wood door's and
Feb 17, 2006
Resolve - Hazardous
Reissue #344752882 water penetration through exterior walls effecting class rooms #407, 452, 405, 403, 401, 501, 503, 505, 552, 507, stairwell 3/4 at 5th floor. remedy: make all necessary repairs to prevent
Feb 17, 2006
Resolve - Hazardous
Reissue #34475289k. wood floor at rm #503, section appx. 3'x 8' is defective, rotten and a trip hazard. remedy: make all necessary repairs to floor in rm# 503.
Feb 17, 2006
Resolve - Non-hazardous
Plaster spalling,cracked,missing in classrooms #407,452,501,503,505,507.remedy:repair plaster
Apr 27, 2005
Resolve - Non-hazardous
Wood floor rotten 3'x 8' section in rm# 503.remedy:repair wood floor in rm #503
Apr 27, 2005
Resolve - Non-hazardous
Water penetration through walls into classroom #407,452,405,403,401,501,503,505,552,507,and stair 3/4 at 5th fl.remedy:stop water penetration make all necessary repairs.
Apr 27, 2005
Resolve - Non-hazardous
Failure to maintain note exterior stairway exit # 9 leading to playground is missing handrail remedy:install handrail
Mar 4, 2004
Resolve