Violations at 2202 Avenue V

Brooklyn, NY 11229 · BBL 3-07381-0201 · Back to the property

HPD housing violations

No HPD violations on record

DOB building violations

4 DOB violations, newest first.

  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 27, 2001

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed
  • Boilers boiler required

    Ll6291-local law 62/91 - boilers boiler required

    Feb 7, 2000

    Dob violation - dismissed

ECB violations

The newest 50 of 56 ECB violations. The city keeps the complete history.

  • Class - 2

    Failure to maintain building in code compliant manner.noted:at 2nd fl stair d,e hallway smoke door near rm 256,gym 3rd fl stair c 5th fl stair f hallway smoke door near rm 555 doors are in disrepair racked.rem:

    Mar 13, 2026 · Penalty $1,250

    Active
  • Class - 2

    Failure to maintain building in code compliant manner.noted:at roof level bulkhead stair c/d basement gas meter rm with water damaged/penetration to cleanness/floors/walls staining w/spalling panels/plaster.rem

    Mar 13, 2026 · Penalty $1,250

    Active
  • Class - 2

    Reissue ecb#35692115h failure to maintain building in code compliant manner.illumination for exits,exit discharges and public corridors per bc 1006.1;27-381.noted:at 1st fl auditorium 2nd fl gym 5th fl gym emer

    Mar 13, 2026 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue #35672610r; failure to maintain building in code-compliant manner: illumination for exits, exit discharges and public corridors per bc 1006.1; 27-381. emergency exits lights not oerational when tested a

    Mar 20, 2025 · Penalty $3,125

    Resolve
  • Class - 2

    Reissued #35672610r. fail to maintain building in code-compliant manner: illuminating exit discharge of public corridors per bc 1006.1,27-381 at gymnasium. emergency lights not properly when tested. remedy: rep

    Jun 27, 2024 · Penalty $1,562

    Resolve
  • Class - 2

    Missing bolts & dogs on boiler doors ,leak on left side of boiler by hand hold gasket

    May 16, 2023 · Penalty $625

    Resolve
  • Class - 2

    Missing bolts & dogs on boiler doors,need valve on oil suction line b/4 anti syphon valve

    May 16, 2023 · Penalty $625

    Active
  • Class - 2

    Failure to maintain building in code-compliant manner.illumination for exits,exit discharges & public corridors per bc1006.1;27-381.noted:observed in gymnasium most emergency lights not operational when tested.

    Mar 15, 2023 · Penalty $625

    Resolve
  • Class - 2

    Re-issue #35560964h(5/4/2021)exit door not self-closing:3 exterior exit doors.not self-closing when tested at 1st fl level. remedy:repair/replace door(s)

    May 12, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reserve #35560967n(5/4/2021)failure to maintain bldg in code compliantmanner.illumination for exits,exit discharges & public corridor per bc1006.1,27-381.exit emergency light are not operational when tested at

    May 12, 2022 · Penalty $1,562

    Resolve
  • Class - 2

    Reissue35495130n doi5.6.20 failure to maintain bldg in codecompliant manner:illumination for exits,exit discharges&public corridors per bc1006.1;27-381 note on 2fl exith&1st fk corridor.these lights exisitng em

    May 4, 2021 · Penalty $1,562

    Resolve
  • Class - 2

    Exit door not selfclosing properly@1fl@exitf outside 1exit door not selfclosing properly@time of insp.repair &/or replace door.

    May 4, 2021 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in a code compliant manner: illumination for exits,exit discharges & public corridors per bc 1006.1;27-381. noted: on the 2nd fl exit h & the 1st fk corridor these lights were not worki

    May 6, 2020 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain bldg in code compliant-manner,staircase 3&4 roof level buklhead,water coming in,parts of ceiling cracking and falling. remedy:repair and/or replace

    May 24, 2019 · Penalty $625

    Resolve
  • Class - 2

    Failure to maintain building in code compliant manner.staircase 3 and 4 roof level bulkhead,water coming in parts of ceiling cracking and falling. remedy: repair and or replace.

    May 24, 2019

    Resolve
  • Class - 3

    Failure to maintain building in code compliant manner. noted: at level 2 above auditorium entrance, water penetration, damaged ceiling. rmdy: repair damaged area.

    Apr 5, 2018

    Resolve
  • Class - 2

    Failure to maintain bldg in code complaint manner. 125 gallons of point are being stored in the boiler room. remedy: remove point from boiler room.

    May 25, 2017

    Resolve
  • Class - 2

    Failure to maintain bldg in a code complaint manner. illumination for exits,exit discharges & public corridors per bc 1006.1;27-381 fire exit des not illuminate at time of inspection,5th fl side entrance to aud

    May 25, 2017

    Resolve
  • Class - 2

    Exit door not self closing,fire door not self closing near rm#412,not self closing doors: near stairs opposite side of room 309 fire exit door #9 & 3rd fl,2 firee entrance doors into kitchen,1st fl fire exit do

    May 25, 2017

    Resolve
  • Class - 2

    Failure to maintain exit sign at cafeteria northside, evident sign onewas there also as per application date in 1983 shows exit light on plans. remedy : provide exit sign northside

    Jun 21, 2013

    Resolve
  • Class - 2

    Defective floors at room 504, missing / hole in flooring / sub flooring in corner of room. remedy: repair floor

    Jun 21, 2013

    Resolve
  • Class - 2

    Defective doors at 3 fl corridor door. doors swing too fast and hitting each other. remedy : repair door

    Jun 21, 2013

    Resolve
  • Class - 2

    Doors not closing at 4th sty stair h. remedy: repair/replace door noted.

    Apr 18, 2012

    Resolve
  • Class - 2

    No a/c window support at 2fl along east 22 street a/c window unit installed w/o metal support bracket rem: provide a/c support or remove window a/c unit

    Sep 20, 2011

    Resolve
  • Class - 2

    Missing fire stop at cellar electric room no fire stop at ceiling conduit penetrations rem: provide fire stop

    Sep 20, 2011

    Resolve
  • Class - 2

    Spalling plaster spalling plaster at exit 10 vestibule wall & ceiling auditorium stage rear ceiling repair plaster surface

    Sep 20, 2011

    Resolve
  • Class - 2

    Plexi vision panels at 4th fl various rooms throughout plexi thermoplastic vision panels installed rem: provide code compliant vision panels

    Sep 20, 2011

    Resolve
  • Class - 2

    Broken door checks the fire proof doors not self closing at 3fl stairway c smoke doors adjacent to room 256 rem: replace door checks so doors properly self close

    Sep 20, 2011 · Penalty $2,500

    Resolve
  • Class - 2

    Racked doors the fire proof doors are racked to frame at 5fl stairway f g roof storage room rem: repair if feasible or replace doors

    Sep 20, 2011 · Penalty $2,500

    Resolve
  • Class - 2

    Reissue #34854963n spalling plaster concrete spalling plaster walls and/or ceiling at 5fl rooms 501 507 511 and roof store room w/ spalling concrete ceiling exposing rebar rem: repair all surfaces

    Sep 20, 2011

    Resolve
  • Class - 2

    Fail to maintain adequate firestopping observed. several open penetrations around conduits passing thru ceiling of room. remedy: maintain firestopping

    Jun 3, 2010

    Resolve
  • Class - 2

    Fail to maintain. spalling plaster on walls & ceiling rms. 501,507,511. at rooftop storeroom by stair 6 exposed rebar on ceilings. remedy: maintain bldg

    Jun 3, 2010

    Resolve
  • Class - 2

    Fail to maintain. racked, binding fpsc doors at stair 6 5th fl exit drrm 105. remedy: maintain bldg

    Jun 3, 2010

    Resolve
  • Class - 2

    Reissue 34792244x fail to maintain. missing/defective door closes at exit 6 1st fl 2 closers. exit c1 lunchroom. remedy: maintain bldg

    Jun 3, 2010

    Resolve
  • Class - 2

    Reissue 34698106r 1st fl lunch rm occupancy over 300 persons exit doors swing against flow of egress

    Jun 23, 2009

    Resolve
  • Class - 2

    Defective doors and frames. 1- all exterior bulkhead roof doors, & frames & saddles rotted. 2- exit #9 ground flr - saddle rotted. remedy: repair/replace accordingg to code.

    Jun 23, 2009

    Resolve
  • Class - 2

    Hardware defective. 1- gate to roof 5/f chained padlocked. 2- roof - exterior 5/6 hdwr. not functional. 3- stwy- 3/4 roof - door hardware broken. 4- interior doors - 5 flr stwy 6 no closer - stwy 7/g no closer

    Jun 23, 2009

    Resolve
  • Class - 3

    Standing water - 1- s.w. corner rear yard approx 20' x 40'. 2- basement flood at old coal shute. remedy: maintain/contain all water flow as per code.

    Jun 23, 2009

    Resolve
  • Class - 2

    Shed doesn't meet building code specifications noted: there are missing vertical enclosures (parapets) 24' along e 22 st. remedy: conform to code.

    Feb 20, 2009 · Penalty $10,000

    Resolve
  • Class - 1

    Reissue: 34570097l. hazardous. 1st floor lunch room occupancy of over 300 persons exit door swing against flow of egress. remedy: change swing of doors/provide (panic) hardware.

    Aug 20, 2008

    Resolve
  • Class - 3

    Defective doors, gym door on 5th floor & corridor door on 3 floor nearroom 354. doors dragging on floor & not opening or closing properly. remedy: replace doors.

    Aug 20, 2008

    Resolve
  • Hazardous

    Reissue # 34504804x:noted: wood fl @ rooms 503 approx 3' x 8' is defective,rotten & trip hazard.remedy:repair/ replace fl.

    May 17, 2007

    Resolve
  • Hazardous

    Reissue # 34504806j.noted: 1st fl lunch room occupancy of over 300,old wood doors open into lunch room from hall.remedy:replace or repair doors to swing w/ flow of egress.

    May 17, 2007

    Resolve
  • Hazardous

    Exit doors swing against the flow of egress. location: 1st floor lunchroom occupancy of over 300 (small kids and teachers) old wood doors open "into" lunch room from hall. remedy: replace all wood door's and

    Feb 17, 2006

    Resolve
  • Hazardous

    Reissue #344752882 water penetration through exterior walls effecting class rooms #407, 452, 405, 403, 401, 501, 503, 505, 552, 507, stairwell 3/4 at 5th floor. remedy: make all necessary repairs to prevent

    Feb 17, 2006

    Resolve
  • Hazardous

    Reissue #34475289k. wood floor at rm #503, section appx. 3'x 8' is defective, rotten and a trip hazard. remedy: make all necessary repairs to floor in rm# 503.

    Feb 17, 2006

    Resolve
  • Non-hazardous

    Plaster spalling,cracked,missing in classrooms #407,452,501,503,505,507.remedy:repair plaster

    Apr 27, 2005

    Resolve
  • Non-hazardous

    Wood floor rotten 3'x 8' section in rm# 503.remedy:repair wood floor in rm #503

    Apr 27, 2005

    Resolve
  • Non-hazardous

    Water penetration through walls into classroom #407,452,405,403,401,501,503,505,552,507,and stair 3/4 at 5th fl.remedy:stop water penetration make all necessary repairs.

    Apr 27, 2005

    Resolve
  • Non-hazardous

    Failure to maintain note exterior stairway exit # 9 leading to playground is missing handrail remedy:install handrail

    Mar 4, 2004

    Resolve